2 Specific installer safety instructions

Installation manual

9

50A9
R32 Split series
3P600450-8T – 2022.09

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

2

Specific installer safety
instructions

Always observe the following safety instructions and regulations.

Unit installation (see 

"4 Unit installation"

 [

4

 11])

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

Installation site (see 

"4.1 Preparing the installation site"

 [

4

 11])

CAUTION

▪ Check  if  the  installation  location  can  support  the  unit's

weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.

▪ Provide sufficient service space.

▪ Do  NOT  install  the  unit  so  that  it  is  in  contact  with  a

ceiling or a wall, as this may cause vibrations.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

Piping installation (see 

"5 Piping installation"

 [

4

 12])

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

CAUTION

▪ No  brazing  or  welding  on  site  for  units  with  R32

refrigerant charge during shipment.

▪ During installation of the refrigeration system, joining of

parts with at least one part charged shall be performed
taking  into  account  the  following  requirements:  inside
occupied  spaces  non-permanent  joints  are  NOT
allowed  for  R32  refrigerant  except  for  site  made  joints
directly connecting the indoor unit to piping. Site made
joints directly connecting piping to indoor units shall be
of non-permanent type.

CAUTION

Do  NOT  connect  the  embedded  branch  piping  and  the
outdoor  unit  when  only  carrying  out  piping  work  without
connecting  the  indoor  unit  in  order  to  add  another  indoor
unit later.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

CAUTION

Do  NOT  open  the  valves  before  flaring  is  complete.  This
would cause refrigerant gas leakage.

DANGER: RISK OF EXPLOSION

Do NOT open the stop valves before the vacuum drying is
finished.

Charging refrigerant (see 

"6 Charging refrigerant"

 [

4

 15])

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

▪ The  refrigerant  inside  the  unit  is  mildly  flammable,  but

normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater,  or  a  cooker,  this  may  result  in  fire,  or  the
formation of a harmful gas.

▪ Turn  OFF  any  combustible  heating  devices,  ventilate

the room, and contact the dealer where you purchased
the unit.

▪ Do  NOT  use  the  unit  until  a  service  person  confirms

that the part from which the refrigerant leaked has been
repaired.

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

WARNING

NEVER  directly  touch  any  accidental  leaking  refrigerant.
This could result in severe wounds caused by frostbite.

Electrical installation (see 

"7 Electrical installation"

 [

4

 16])

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
national wiring regulation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provides  full
disconnection under overvoltage category III.

Summary of Contents for 2MXM40A2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 2MXM40A2V1B9 2MXM50A2V1B9 ...

Page 2: ...gimusel et neid kasutatakse vastavuses meie juhistele са в съответствие със следната директива и или регламент и при условие че продуктите се използват в съответствие с нашите инструкции atitinka toliau nurodytas direktyvas arba reglamentus su sąlyga kad gaminiai bus eksploatuojami laikantis mūsų instrukcijų atbilst šādām direktīvām vai regulām ja vien šie izstrādājumi tiek lietoti saskaņā ar mūsu...

Page 3: ...tagelse af enligt bestämmelserna för i henhold til bestemmelsene i noudattaen säännöksiä za dodržení ustanovení prema odredbama követi a z zgodnie z postanowieniami urmând prevederile 19 20 21 22 23 24 25 v skladu z določbami vastavalt nõuetele следвайки клаузите на vadovaujantis šio dokumento nuostatomis atbilstoši šādu standartu prasībām nasledovnými ustanoveniami şu standartların hükümlerine EN...

Page 4: ...nstilling av sikkerhetsanordning for trykk P bar Produksjonsnummer og produksjonsår se modellens merkeplate Suurin sallittu paine PS K bar Pienin suurin sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximá...

Page 5: ...08 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032E23 11 2022 as set out in A and judged positively by B according to the Certificate C DICz is authorised to compile the Technical Construction File DICz Daikin Ind...

Page 6: ...ctrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032E23 11 2022 D DAIKIN TCF PED 0146B E HPi Verification Services Ltd NB1521 F D1 G II H as set out in A and judged positively by B according to the Certificate C as set out in the Technical Construction File D and judged positively by...

Page 7: ...urated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q HPi Verification Services Ltd The Manor House Howbery Business Park Wallingford OX10 8BA United Kingdom Name and address of the Notified body that judged positively on compliance with the Pressure Eq...

Page 8: ...fore commissioning 19 10 2 Checklist during commissioning 19 10 3 Trial operation and testing 19 10 3 1 To perform a test run 19 11 Maintenance and service 20 12 Disposal 20 13 Technical data 20 13 1 Wiring diagram 20 13 1 1 Unified wiring diagram legend 20 13 2 Piping diagram Outdoor unit 21 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance rep...

Page 9: ...ct the refrigerant piping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause abnormal pressure in the refrigeration cycle which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to pr...

Page 10: ...let or outlet Do NOT remove the fan guard When the fan is rotating at high speed it will cause injury Maintenance and service see 11 Maintenance and service 420 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING WARNING Before carrying out any maintenance or repair activity ALWAYS switch off the circuit breaker on the supply panel remove the fuses or open the protection devices of the un...

Page 11: ... 300 mm of work space below the ceiling surface and 250 mm for piping and electrical servicing b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a bedroom so that the operation noise will cause no trouble Note If the sound is measured under actual installation conditions the measured value might be higher than the sound pressu...

Page 12: ...des proper drainage Prepare 4 sets of M8 or M10 anchor bolts nuts and washers field supply 20 mm mm 311 5 7 4 2 4 0 2 4 0 a a 100 mm above expected level of snow 4 2 2 To install the outdoor unit 4 M8 M10 4 2 3 To provide drainage NOTICE If the unit is installed in a cold climate take adequate measures so that the evacuated condensate CANNOT freeze NOTICE If the drain holes of the outdoor unit are...

Page 13: ...e thermal insulation pipes for the gas and liquid refrigerant piping 5 1 3 Refrigerant piping length and height difference The shorter the refrigerant piping the better the performance of the system The piping length and height differences must comply with the following requirements Shortest allowable length per room is 3 m Refrigerant piping length to each indoor unit 20 m Refrigerant piping tota...

Page 14: ... Connect the gas refrigerant connection from the indoor unit to the gas stop valve of the outdoor unit NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 5 3 Checking the refrigerant piping 5 3 1 To check for leaks NOTICE Do NOT exceed the unit s maximum working pressure see PS High...

Page 15: ...t in severe wounds caused by frostbite NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Contact your installer for more information 6 2 To determine the additional ref...

Page 16: ...ategory III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical parts inside the product Do NOT branch the power supply for the drain pump etc fr...

Page 17: ...ice d Power supply wire e Interconnection wire for room A B f Wire retainer 4 Tighten the terminal screws securely using a Phillips screwdriver 5 Check that the wires do not disconnect by pulling them lightly 6 Firmly secure the wire retainer to avoid external stress on wire terminations 7 Pass the wiring through the cutout on the bottom of the protection plate 8 Make sure the electrical wiring do...

Page 18: ...nd the electric box cover CAUTION When reinstalling the electric box cover be careful not to pinch the fan motor lead wire 9 3 About heat mode lock Heat mode lock limits the unit to heat operation 9 3 1 To turn ON heat mode lock 1 Remove the top plate 2 screws and the front plate 8 screws 2 To set heat mode lock remove the S99 connector 3 To reset the heat pump mode cooling heating plug the connec...

Page 19: ...d piping match for each indoor unit Check if the priority room setting is set for 2 or more rooms Keep in mind that the DHW generator for Multi or the Hybrid for Multi shall not be selected as the priority room 10 2 Checklist during commissioning To perform a wiring check To perform an air purge To perform a test run 10 3 Trial operation and testing Before starting the test run measure the voltage...

Page 20: ...ide 13 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required 13 1 Wiring diagram The wiring diagram is delivered with the unit located inside of the outdoor unit bottom side of the top plate 13 1 1 Unified wiring diagram legend For ...

Page 21: ...ensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Fer...

Page 22: ...d b High pressure switch with automatic reset n Filter c Muffler o Motor operated valve d Discharge pipe thermistor p Muffler e Compressor q Outdoor air temperature thermistor f Accumulator r Heat exchanger g Branch pipe M Fan motor h Thermistor gas Refrigerant flow cooling i Gas stop valve Refrigerant flow heating j Field piping gas ...

Page 23: ......

Page 24: ...3P600450 8T 2022 09 Copyright 2022 Daikin Verantwortung für Energie und Umwelt ...

Reviews: