8 Finishing the outdoor unit installation

Installation manual

19

2(A)MXM40+50 + 2(A)MXF40+50
R32 Split series
3P600450-3G – 2021.03

2

1

2

Connect the wires between the indoor and outdoor units so that
the  terminal  numbers  match.  Make  sure  to  match  the  symbols
for piping and wiring.

3

Make sure to connect correct wiring to correct room (A to A, B
to B).

e

-A

a

-A

a

-B

e

-B

b

c

d

1

2

3

L

N

1

2

3

f

a

Terminal for room (A, B)

b

Circuit breaker

c

Residual current device

d

Power supply wire

e

Interconnection wire for room (A, B)

f

Wire retainer

4

Tighten  the  terminal  screws  securely  using  a  Phillips
screwdriver.

5

Check that the wires do not disconnect by pulling them lightly.

6

Firmly secure the wire retainer to avoid external stress on wire
terminations.

7

Pass  the  wiring  through  the  cutout  on  the  bottom  of  the
protection plate.

8

Make  sure  the  electrical  wiring  does  not  contact  with  the  gas
piping.

1

2

3

1 2 3 1 2 3

1

2

3

L

N

A

B

9

Reattach the switch box cover and the service cover.

8

Finishing the outdoor unit
installation

8.1

To finish the outdoor unit
installation

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn off the power supply before servicing.

▪ Install the switch box cover before turning on the power

supply.

1

Insulate and fix the refrigerant piping and cables as follows:

g

b

a

f

e

c

d

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Field wiring (if applicable)

e

Liquid pipe

f

Liquid pipe insulation

g

Finishing tape

2

Install the service cover.

9

Configuration

9.1

About ECONO mode prohibition
setting

This setting disables the input control signal from the user interface.
Use  this  setting  when  you  wish  to  block  reception  of  input  controls
(cooling/heating) from indoor unit user interfaces.

9.1.1

To turn on ECONO mode prohibition
setting

Prerequisite: 

The main power supply MUST be turned off.

1

Remove the top plate of the outdoor unit (2 screws on sides)

2

Remove  the  electric  box  cover  by  sliding  it.  Be  careful  not  to
bend the electric box hook.

3

Cut the jumper (J23).

Summary of Contents for 2MXM-N9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 2AMXM40M4V1B9 2AMXM50M4V1B9 2AMXF40A2V1B 2AMXF50A2V1B 2MXF40A2V1B 2MXF50A2V1B 2MXM40N2V1B9 2MXM50N2V1B9...

Page 2: ...izate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v...

Page 3: ...kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respectiv...

Page 4: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 5: ...zate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v...

Page 6: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 7: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 8: ...fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standard...

Page 9: ...aisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele re...

Page 10: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 11: ...nd testing 21 10 3 1 To perform a test run 21 11 Disposal 21 12 Technical data 21 12 1 Wiring diagram 22 12 1 1 Unified wiring diagram legend 22 12 2 Piping diagram Outdoor unit 23 1 About the documen...

Page 12: ...e which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas leakage Use flare nut...

Page 13: ...pply before servicing Install the switch box cover before turning on the power supply 3 About the box 3 1 Outdoor unit 3 1 1 To remove the accessories from the outdoor unit 1 1 1 1 1 c d e f g 1 h 1 a...

Page 14: ...ssary construct a pedestal See 4 2 Mounting the outdoor unit 414 for more details In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit If...

Page 15: ...20 mm to prevent condensation on the surface of the insulation 5 1 3 Refrigerant piping length and height difference The shorter the refrigerant piping the better the performance of the system The pi...

Page 16: ...eration cycle which may result in equipment damage and even injury 1 Connect the liquid refrigerant connection from the indoor unit to the liquid stop valve of the outdoor unit a c b a b a Liquid stop...

Page 17: ...ls or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit i...

Page 18: ...the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical parts inside the product Do NOT branch the power supply for the drain pump etc from the t...

Page 19: ...1 2 3 L N A B 9 Reattach the switch box cover and the service cover 8 Finishing the outdoor unit installation 8 1 To finish the outdoor unit installation DANGER RISK OF ELECTROCUTION Make sure that t...

Page 20: ...ck Heat mode lock limits the unit to heat operation 9 3 1 To turn on heat mode lock 1 Remove the top plate 2 screws and the front plate 8 screws 2 To set heat mode lock remove the S99 connector 3 To r...

Page 21: ...ulti shall not be selected as the priority room 10 2 Checklist during commissioning To perform a wiring check To perform an air purge To perform a test run 10 3 Trial operation and testing Before star...

Page 22: ...emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live Symbol Meanin...

Page 23: ...4CuT EVA EV B 9 5CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT HPS1 9 5CuT 9 5CuT 12 7CuT 6 4CuT 6 4CuT a b c d e f g g h i j A B A B k l l m n o o p q r s t n m i h g c c A Room A B Room B a 4 way valve ON...

Page 24: ...3P600450 3G 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: