5 Piping installation

Installation manual

16

2(A)MXM40+50 + 2(A)MXF40+50

R32 Split series

3P600450-3G – 2021.03

Port

Class

Reducer

B

25, 35

2MXF40

A

20, 25, 35

B

20, 25, 35

2MXM50, 2AMXM50

A

15, 20, 25, 35, 42

(a)

B

15, 20, 25, 35

1+2

42, 50

2AMXF50

A

25, 35

B

25, 35

1+2

2MXF50

A

20, 25, 35

B

20, 25, 35

1+2

(a)

Use optional accessory.

Reducer type

Connection

1

Ø12.7 mm → Ø9.5 mm

2

Ø12.7 mm → Ø9.5 mm

Connection example:

▪ Connecting a Ø9.5 mm pipe to a Ø12.7 mm gas pipe connection

port

a

b

d

e

c

a

Outdoor unit connection port

b

Reducer type 1

c

Reducer type 2

d

Flare nut for Ø12.7 mm

e

Inter-unit piping

Coat the threaded connection port of the outdoor unit where the flare
nut comes in with refrigeration oil.

NOTICE

Use  an  appropriate  wrench  to  avoid  damaging  the
connection  thread  by  overtightening  the  flare  nut.  Be
careful NOT to overtighten the nut, or the smaller pipe may
be damaged (about 2/3-1× the normal torque).

5.2.2

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

1

Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.

a

c

b

a

b

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect  the  gas  refrigerant  connection  from  the  indoor  unit  to
the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between
indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the
refrigerant piping is wrapped with finishing tape.

5.3

Checking the refrigerant piping

5.3.1

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

ALWAYS  use  a  recommended  bubble  test  solution  from
your wholesaler.

NEVER use soap water:

▪ Soap  water  may  cause  cracking  of  components,  such

as flare nuts or stop valve caps.

▪ Soap  water  may  contain  salt,  which  absorbs  moisture

that will freeze when the piping gets cold.

▪ Soap  water  contains  ammonia  which  may  lead  to

corrosion  of  flared  joints  (between  the  brass  flare  nut
and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

5.3.2

To perform vacuum drying

DANGER: RISK OF EXPLOSION

Do NOT start the unit if it is vacuumed.

NOTICE

Connect the vacuum pump to 

both

 the service ports of the

gas stop valves.

Summary of Contents for 2MXM-N9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 2AMXM40M4V1B9 2AMXM50M4V1B9 2AMXF40A2V1B 2AMXF50A2V1B 2MXF40A2V1B 2MXF50A2V1B 2MXM40N2V1B9 2MXM50N2V1B9...

Page 2: ...izate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v...

Page 3: ...kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respectiv...

Page 4: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 5: ...zate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v...

Page 6: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 7: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 8: ...fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standard...

Page 9: ...aisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele re...

Page 10: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 11: ...nd testing 21 10 3 1 To perform a test run 21 11 Disposal 21 12 Technical data 21 12 1 Wiring diagram 22 12 1 1 Unified wiring diagram legend 22 12 2 Piping diagram Outdoor unit 23 1 About the documen...

Page 12: ...e which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas leakage Use flare nut...

Page 13: ...pply before servicing Install the switch box cover before turning on the power supply 3 About the box 3 1 Outdoor unit 3 1 1 To remove the accessories from the outdoor unit 1 1 1 1 1 c d e f g 1 h 1 a...

Page 14: ...ssary construct a pedestal See 4 2 Mounting the outdoor unit 414 for more details In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit If...

Page 15: ...20 mm to prevent condensation on the surface of the insulation 5 1 3 Refrigerant piping length and height difference The shorter the refrigerant piping the better the performance of the system The pi...

Page 16: ...eration cycle which may result in equipment damage and even injury 1 Connect the liquid refrigerant connection from the indoor unit to the liquid stop valve of the outdoor unit a c b a b a Liquid stop...

Page 17: ...ls or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit i...

Page 18: ...the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical parts inside the product Do NOT branch the power supply for the drain pump etc from the t...

Page 19: ...1 2 3 L N A B 9 Reattach the switch box cover and the service cover 8 Finishing the outdoor unit installation 8 1 To finish the outdoor unit installation DANGER RISK OF ELECTROCUTION Make sure that t...

Page 20: ...ck Heat mode lock limits the unit to heat operation 9 3 1 To turn on heat mode lock 1 Remove the top plate 2 screws and the front plate 8 screws 2 To set heat mode lock remove the S99 connector 3 To r...

Page 21: ...ulti shall not be selected as the priority room 10 2 Checklist during commissioning To perform a wiring check To perform an air purge To perform a test run 10 3 Trial operation and testing Before star...

Page 22: ...emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live Symbol Meanin...

Page 23: ...4CuT EVA EV B 9 5CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT HPS1 9 5CuT 9 5CuT 12 7CuT 6 4CuT 6 4CuT a b c d e f g g h i j A B A B k l l m n o o p q r s t n m i h g c c A Room A B Room B a 4 way valve ON...

Page 24: ...3P600450 3G 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: