18
AGZ 025D through 190D
OMM 1087-1
Description
Default
Range
High Condenser Pressure Unload
4137 KPA(600 PSI)
3241 to 4137 KPA (470 to 600 PSI)
Evaporator Flow Proof
5 sec
5 to 15 sec
Recirculate Timeout
3 min
1 to 10 min
Evaporator Water Freeze
2.2°C (36°F)
See Auto Adjusted Ranges, page 18
Low OAT Start Time
165 sec
150 to 240 sec
External Alarm Configuration
Event
Event, Alarm
Clear Alarms
Off
Off, On
Network Clear Alarms
Off
Off, On
Circuit Setpoints (exist individually for each circuit):
Description
Default
Range
Mode/Enabling
Circuit mode
Enable
Disable, Enable, Test
Compressor 1 Enable
Enable
Enable, Disable
Compressor 2 Enable
Enable
Enable, Disable
Compressor 3 Enable
Enable
Enable, Disable
Network Compressor 1 Enable
Enable
Enable, Disable
Network Compressor 2 Enable
Enable
Enable, Disable
Network Compressor 3 Enable
Enable
Enable, Disable
EXV control
Auto
Auto, manual
EXV position
See Special Setpoints,
0% to 100%
Suction SH Target
5.56°C (10
°° )
4.44 to 6.67 °C (8 to 12 °F)
Max Evap Pressure
1076 KPA(156.1 PSI)
979 to 1172 KPA (142 to 170 PSI)
Condenser
Condenser Target 100%
37.8°C (100°F)
32.22 to 48.9 °C (90 to 120 °F)
Condenser Target 67%
32.2°C (90°F)
32.22 to 48.9 °C (90 to 120 °F)
Condenser Target 50%
32.2°C (90°F)
29.44 to 43.3 °C (85 to 110 °F)
Condenser Target 33%
29.4°C (85°F)
29.44 to 43.3 °C (85 to 110 °F)
VFD Max Speed
100%
90 to 110%
VFD Min Speed
25%
25 to 60%
Fan Stage Up Deadband 1
8.33°C (15°F)
8.33 to 13.89 °C (15 to 25 °F)
Fan Stage Up Deadband 2
5.56°C (10°F)
5.56 to 8.33 °C (10 to 15 °F)
Fan Stage Up Deadband 3
5.56°C (10°F)
5.56 to 8.33 °C (10 to 15 °F)
Fan Stage Up Deadband 4
5.56°C (10°F)
5.56 to 8.33 °C (10 to 15 °F)
Fan Stage Down Deadband 1
11.11°C (20°F)
8.33 to11.11 °C (15 to 20 °F)
Fan Stage Down Deadband 2
11.11°C (20°F)
8.33 to11.11 °C (15 to 20 °F)
Fan Stage Down Deadband 3
8.33 °C (15 °F)
5.56 to 8.33 °C (10 to 15 °F)
Fan Stage Down Deadband 4
5.56 °C (10 °F)
3.33 to 5.56 °C (6 to 10 °F)
Sensor Offsets
Evap pressure offset
0 KPA (0 PSI)
-100 to 100 KPA (-14.5 to 14.5 PSI)
Cond pressure offset
0 KPA (0 PSI)
-100 to 100 KPA (-14.5 to 14.5 PSI)
Suction temp offset
0°C (0°F)
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
Note – Condenser Target 67% and Condenser Target 33% will be available only when Number of
Compressors is 6. Condenser Target 50% will be available only when Number of Compressors is 4.
Auto Adjusted Ranges
Some settings have different ranges of adjustment based on other settings:
Summary of Contents for AGZ-D 25