INSTRUCTION MANUAL 

 

POWER FACTOR TRANSDUCER 

 

SPTT2-92A-12 
SPTT2-92A-33 
SPTT2-92A-34 

 

〔 MODEL B 〕 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 

Summary of Contents for SPTT2-92A-12

Page 1: ...Q 222 040 INSTRUCTION MANUAL POWER FACTOR TRANSDUCER SPTT2 92A 12 SPTT2 92A 33 SPTT2 92A 34 MODEL B...

Page 2: ...ase do not install in the place where sunlight hits directly Discoloration and degradation of a name plate and deformation of the case by the surface temperature rise may occur If the average daily te...

Page 3: ...our company Failure caused by violating various conditions regarding use storage etc specified by the supplier When the faults or defects are caused by a reason not belongs to purchased or delivered p...

Page 4: ...thod 4 5 Connection 6 6 Handling explanation 7 7 Specification 7 1 Rating 7 7 2 Performance 8 7 3 Electrical strength Mechanical strength 9 7 4 Noise immunity 9 7 5 EMC 10 7 6 Structure and environmen...

Page 5: ...92A 12 M4 screw 4 piece set 1 M4 screw 5 piece set 1 SPTT2 92A 33 M4 screw 4 piece set 1 M4 screw 7 piece set 1 SPTT2 92A 34 M4 screw 4 piece set 2 M4 screw 5 piece set 1 4 Mounting method Please inst...

Page 6: ...e this product from the IEC DIN rail Please insert a flathead screwdriver in the hole where a slider is square Next a slider is lowered in the direction of an arrow This product can be removed from th...

Page 7: ...tening torque 1 0 to 1 3 N m SPTT2 92A 12 SPTT2 92A 33 SPTT2 92A 34 Connection diagram SPTT2 92A 12 SPTT2 92A 33 SPTT2 92A 34 AUX SUPPLY L P1 K U 2 1 V 1S E A B OUTPUT P2 AUX SUPPLY P1 A B OUTPUT P2 A...

Page 8: ...power supply and voltage input are applied is the output equivalent to the power factor 1 7 Specification 7 1 Rating Item Specification Input Power factor LEAD 0 5 to 1 to LAG 0 5 Please specify LEAD...

Page 9: ...erter output Cycle control PWM inverter SCR phase angle control Adjustment range The output adjustment range is BIAS 5 of the output span MAX 5 of the output span Use only when adjustment is required...

Page 10: ...es 1 second of rated voltage 10 times 10 second intervals 40 times 1 second and 20 times 4 seconds and 10 times 16 seconds of rated current 2 times 1 minute intervals 10 times 1 second of rated curren...

Page 11: ...61000 4 6 Power frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During testing Within 20 error After test Within inherent error EN61000 6 2 EN61000...

Page 12: ...its 10 to 55 5 to 90 RH Non condensing Storage temperature limits 40 to 70 Product warranty period One year period 7 7 Technical standards Item Specification Transducer JIS C 1111 2019 IEC 60688 2012...

Page 13: ...ust in the next way Remove the terminal cover and VR cap before adjustment and attach the VR cap and terminal cover after adjustment 1 For the output load connect an actual load within the output load...

Page 14: ...r less Z Other Power Factor Transducer Three phase four wire Type Specification code SPTT2 92A 34 Model Input Rated voltage Rated current Output Output load range Auxiliary supply B Model B 1 LEAD 0 5...