SMLC-213-154
30
(4) 141H to 143 Zero-phase voltage detection setting
Setting of the alarm value of a zero-phase voltage factor, the response time, and a display change is performed.
141H
Zero-phase
voltage upper
limit
RESET/
SHIFT
RESET/SHIFT
142
Response time
RESET/
SHIFT
143
Ground-fault phase
detection display
automatic change
◆ 141H Zero-phase voltage upper limit
The upper limit of zero-phase voltage is setting.
Setting range. 5 to 150%(1% step) and OFF(Non use).
Selection by + and - , set value is updated by SET .
Default setting:5280V
◆ 142 Response time
The response time (90% response) of zero-phase voltage is setting.
Selection by + and - , set value is updated by SET .
Default setting:0.1 seconds <秒>
◆ 143 Ground fault phase detection display automatic change
Set the whether it changes from a measurement display (an instantaneous
measurement display, the maximum, and the minimum measurement display)
to a ground fault phase detection display automatically at the case of
ground fault phase occurrence.
Selection by + and - , set value is updated by SET .
Default setting:OFF (Not change)
<Caution> In addition to this setting, the display can be switched to
the ground fault detection display by a switch operation.
Please refer to "4.3.3 Ground fault phase detection display
change" about switch operation.
Zero-phase voltage upper limit
Setting No.
Current setting
New setting
Response time
Setting No.
Current setting
New setting
Zero-phase voltage upper limit
Setting No.
Current setting
New setting
0.05sec
<秒>
0.1sec
<秒>
0.15sec
<秒>
0.2sec
<秒>
0.5sec
<秒>
5sec
<秒>
3sec
<秒>
2sec
<秒>
1sec
<秒>