9. Calibration 

 

Because this product is adjusted, there is not need of calibration especially.  
However, if discrepancy arises in an output in long-term use, please adjust in the next way. 
Remove the terminal cover and VR cap before adjustment, and attach the VR cap and terminal cover after adjustment. 

(1) For the output load, connect an actual load (within the output load range indicated on the name plate) 

or a simulated load with the same resistance value as the actual load. 

(2) Apply the auxiliary power supply (rated) and the input equivalent to 50% of the rated output value,  

and energize for 15 minutes. 

(3) Enter the lower limit of the rated output range and adjust with BIAS adjustment VR so that the output  

becomes the lower limit. 
Next, enter the upper limit of the rated output range and adjust the MAX adjustment VR so that the  
output reaches the upper limit. 
(The screwdriver for adjustment:Tip width of 1.8 to 2.3mm,  Phillips-head screwdriver or flat-blade 
screwdriver) 

 
 

10. Type composition 

 

Frequency Transducer 

Type      Specification code 

F T T 2 - 9 1 A -

 

① ② ③ ④ ⑤

 

 

① Model 

② Input 

③ Rated voltage   ④ Output (Output load range) 

⑤ Auxiliary supply 

B  Model B 

1  45 to 55Hz  1  AC100V 

2  DC0 to 1V   (200Ω or more)   

AC80 to 264V 

 

 

2  55 to 65Hz  2  AC105V 

3  DC0 to 5V   (600Ω or more)  F  DC80 to 264V 

 

 

3  45 to 65Hz  3  AC110V 

4  DC0 to 10V  (2kΩ or more) 

 

AC/DC power supply 

 

 

Z  Other 

4  AC115V 

5  DC1 to 5V   (600Ω or more)  3  DC20 to 57V 

 

 

 

 

5  AC200V 

A  DC0 to 1mA  (10kΩ or less)  Z  Other 

 

 

 

 

6  AC210V 

B  DC0 to 5mA  (2kΩ or less) 

 

 

 

 

 

 

7  AC220V 

C  DC0 to 10mA (1kΩ or less) 

 

 

 

 

 

 

Z  Other 

F  DC4 to 20mA (550Ω or less)   

 

 

 

 

 

 

 

Z  Other 

 

 

 

 
 
 
 
 
 
 
 
 
 

   

 

      Tokyo Office : 11-13, Hitotsuya 1-chome, Adachi-ku, Tokyo, 121-8639, JAPAN. 
                     TEL:+81-3-3885-2411 , FAX:+81-3-3858-3966 

      Kyoto Office : 1-19, Ichinobe-Nishikawahara, Jyoyou-shi, Kyoto, 610-0114, JAPAN. 
                     TEL:+81-774-55-1391 , FAX:+81-774-54-1353 
 

       Revision A,  DATE:November 1, 2022 

 

Summary of Contents for FTT2-91A

Page 1: ...Q 222 035 INSTRUCTION MANUAL FREQUENCY TRANSDUCER FTT2 91A MODEL B...

Page 2: ...ase do not install in the place where sunlight hits directly Discoloration and degradation of a name plate and deformation of the case by the surface temperature rise may occur If the average daily te...

Page 3: ...our company Failure caused by violating various conditions regarding use storage etc specified by the supplier When the faults or defects are caused by a reason not belongs to purchased or delivered p...

Page 4: ...thod 4 5 Connection 6 6 Handling explanation 6 7 Specification 7 1 Rating 7 7 2 Performance 7 7 3 Electrical strength Mechanical strength 8 7 4 Noise immunity 8 7 5 EMC 9 7 6 Structure and environment...

Page 5: ...Inspection certificate 1 Packed in an envelope Terminal screw in a bag M4 screw 7 piece set 1 4 Mounting method Please install indoors in a place with low mechanical vibration dust and corrosive gas...

Page 6: ...ve this product from the IEC DIN rail Please insert a flathead screwdriver in the hole where a slider is square Next a slider is lowered in the direction of an arrow This product can be removed from t...

Page 7: ...t correctly after paying attention to the following points 1 When applying the auxiliary power supply and input check that the voltage and input signal of the auxiliary power supply conform to the spe...

Page 8: ...specification code for other ratings 7 2 Performance Item Specification Class index 0 5 Response time 1 second or less Ripple 1 p p or less Fluctuation value of influence due to ambient temperature Us...

Page 9: ...rated voltage DC100 110V DC57V continuous DC48V Short time over input Input 2 times 10 seconds of rated voltage once 2 times 1 second of rated voltage 10 times 10 second intervals Aux supply 1 5 times...

Page 10: ...1000 4 6 Power frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During testing Within 20 error After test Within inherent error EN61000 6 2 EN61000...

Page 11: ...rranty period One year period 7 7 Technical standards Item Specification Transducer JIS C 1111 2019 IEC 60688 2012 CE marking EMC Directive 2014 30 EU EN 61000 6 2 EN 61000 4 2 3 4 5 6 8 11 EN 61000 6...

Page 12: ...ange and adjust the MAX adjustment VR so that the output reaches the upper limit The screwdriver for adjustment Tip width of 1 8 to 2 3mm Phillips head screwdriver or flat blade screwdriver 10 Type co...

Reviews: