background image

Q-222-035 

 

 

1. Features of product 

 

 

Complied to JIS C 1111:2019 and IEC 60688:2012 

 

Free power supply specifications compatible with 80 to 264 VAC and 80 to 264 VDC, and 24 VDC/48 VDC  
power supply specifications are available. 

 

Power consumption and weight have been reduced by about 50% compared to our conventional products. 

 

Compatible with two types of mounting methods for IEC/DIN rail mounting and wall mounting. 

 
 

2. Outline dimension 

 
    Please refer to the wiring diagram for the terminal arrangement. 

Terminal cover

(With VR cap)

(With VR cap)

BIAS adjustment VR

MAX. adjustment VR

7-M4screw

110

92

28

5

40

120

130

1

(12.5)

7

1

 

 
Note(

) Dimensions when IEC/DIN rail (height 15mm) is installed. (Please use a rail with a width of 35mm) 

The terminal cover is standard equipment. 

 
 

3. Bundled items 

 

① Inspection certificate:1 (Packed in an envelope) 

② Terminal screw in a bag.  M4 screw 7-piece set:1  

 
 

4. Mounting method 

 

Please install indoors in a place with low mechanical vibration, dust, and corrosive gas. 
And, please select indoors that are not affected by a strong electromagnetic field by large current bus, 
saturable reactor etc. in the vicinity.  There is no restriction on mounting position.  
Mounting can be done on 35mm width DIN rail mounting or screw mounting.  
For screw mounting, please install with M4 screw or M5 screw. (However, the screw is not attached.   
The tightening torque of a screw, M4:1.00 to 1.30N・m, M5:2.0 to 2.5N・m) 
There is no particular rule for the side-by-side spacing. 
Considering heat dissipation and wiring space, please leave 90mm or more space between the top and bottom.  
Please leave space between terminal and metal panel for 10mm or more. 

<Caution> Be sure to turn off the power and input signals before installing or removing the product to  

prevent danger. 

 

Summary of Contents for FTT2-91A

Page 1: ...Q 222 035 INSTRUCTION MANUAL FREQUENCY TRANSDUCER FTT2 91A MODEL B...

Page 2: ...ase do not install in the place where sunlight hits directly Discoloration and degradation of a name plate and deformation of the case by the surface temperature rise may occur If the average daily te...

Page 3: ...our company Failure caused by violating various conditions regarding use storage etc specified by the supplier When the faults or defects are caused by a reason not belongs to purchased or delivered p...

Page 4: ...thod 4 5 Connection 6 6 Handling explanation 6 7 Specification 7 1 Rating 7 7 2 Performance 7 7 3 Electrical strength Mechanical strength 8 7 4 Noise immunity 8 7 5 EMC 9 7 6 Structure and environment...

Page 5: ...Inspection certificate 1 Packed in an envelope Terminal screw in a bag M4 screw 7 piece set 1 4 Mounting method Please install indoors in a place with low mechanical vibration dust and corrosive gas...

Page 6: ...ve this product from the IEC DIN rail Please insert a flathead screwdriver in the hole where a slider is square Next a slider is lowered in the direction of an arrow This product can be removed from t...

Page 7: ...t correctly after paying attention to the following points 1 When applying the auxiliary power supply and input check that the voltage and input signal of the auxiliary power supply conform to the spe...

Page 8: ...specification code for other ratings 7 2 Performance Item Specification Class index 0 5 Response time 1 second or less Ripple 1 p p or less Fluctuation value of influence due to ambient temperature Us...

Page 9: ...rated voltage DC100 110V DC57V continuous DC48V Short time over input Input 2 times 10 seconds of rated voltage once 2 times 1 second of rated voltage 10 times 10 second intervals Aux supply 1 5 times...

Page 10: ...1000 4 6 Power frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During testing Within 20 error After test Within inherent error EN61000 6 2 EN61000...

Page 11: ...rranty period One year period 7 7 Technical standards Item Specification Transducer JIS C 1111 2019 IEC 60688 2012 CE marking EMC Directive 2014 30 EU EN 61000 6 2 EN 61000 4 2 3 4 5 6 8 11 EN 61000 6...

Page 12: ...ange and adjust the MAX adjustment VR so that the output reaches the upper limit The screwdriver for adjustment Tip width of 1 8 to 2 3mm Phillips head screwdriver or flat blade screwdriver 10 Type co...