NOTES ON INSTALLATION OF DAFI WATER HEATERS

DAFI energy saving water heaters can be installed above, or under your basin or sink. Shower installations are also possible, but never 

inside the shower cubicle. Installation of your water heater in the ceiling or behind the wall, or in a cupboard next to the shower should be 

considered.

DAFI water heater Installation Requirements:

1. DAFI water heaters must be installed as close to the point of use as possible to minimise pipeline heat loss.

2. Water pressure must not be less than 60kPa (0.6 bar) and not exceed 600kPa (6bar). If water pressure is too high, a pressure reducing 

valve must be installed.

3. Water quality e.g. mains supply, borehole, river etc. Should water quality be suspect, a filter must be installed.

4. Single phase or 3 phase power supply with own isolator switch must be available as close as possible to point of usage. 

DAFI water heater Installation Procedure:

Installing the DAFI energy saving water heater is not complicated, but it needs to installed by a professional plumber and

electrician for problem-free operation.

Water supply:

• To be undertaken by a qualified Plumber

• Incoming water supply should be clean and without any suspended solids or organic materials.

• The "static" incoming cold water supply pressure to be accurately measured to ascertain operating conditions.

• The maximum operating pressure of all DAFI Heater models is 600 kPa (6 Bar).

• A suitable Pressure Reducing Valve is to be installed before the heater unit, should this 600 kPa limit be exceeded.

• Heater manifold nut assembly must only to be tightened with the spanner supplied in each box.

• All air to be vented from the heater unit prior to connecting the 240 volt or 400 volt 50 Hz power supply.

• A cut-off valve should be installed on the water inlet line to the DAFI heater.

• All heater units for under sink installation can be installed at any angle.

Recommendations:

• Installing a composite pipe from your DAFI water heater to the point of usage will further reduce heat loss and save more energy.

• For optimum performance enhancement Spray Nozzle provided should be attached to tap. For models 3.7 kW & 4.5 kW

Spray Nozzle is highly recomended. Spray Nozzle spread water and rise pressure of hot water.

• Beware of over tightening , use plastic key provided. Do not use metal spanner!

• For performance see table FT - flow/temperature

Tips:

1.Each installation is indywidual. Performance of Dafi Heater depends on: voltage drop, temperature of cold water, pressure , type of taps, 

distance of instalation from point of use, etc. Selection of right power should be done by experienced and competent trade person.

2. Before you buy check if obtained flow corresponds to your demands.

Electric supply:

To be undertaken by a qualified Electrician

1. Each heater unit is to be wired to the Distribution Board via the existing Earth Leakage System.

Minimum 3 core cable sizes*

- 2.5mm² for 3.7 kW & 4.5kW (240V)

- 4 mm² or 2x2.5mm²(ring) for 5.5 kW & 7.3kW - (240V)

- 2.5mm² for 7.5kW these models is two phase no neutral -(400V)

- 4 mm² 9 kW & 11kW these models are two phase no neutral -(400V)

*size of cable need to be confirmed with installation method and voltage drop

2. Models 7.5 kW - 11kW are non-domestic unles three phase supply system in property.

Any combination of two phases no neutral (eg brown/black=400V).

3. A dedicated suitably sized breaker to be installed on the Distribution Board for each heater unit.

4. A suitable sized 2 pole electric isolator (not fuse spur) to be installed.

5. DAFI heater units are not to be connected to the electrical supply by standard BS 1363 wall plug.

 SPECIFICATIONS

[kW]

  Rated power consumption

3.7

4.5

5.5

7.3

7.5

9

11

[~V]

  Rated voltage

1/N/PE~ 240V 50Hz

2/PE~ 400V 50Hz

[A]

       Rated current

16

19.6

24

31.7

18.75 22.5

25

[A1] 

  Automatic breaker

16

20

25

32

20

25

32

[B1] 

  Water

ciency measured in 

                 liters / the minimum   

                 temperature of  owing water      

                15°C and pressure 200 000 Pa

40°C

1.9

2.4

2.9

4

4

4.7

5.8

45°C

1.7

2

2.5

3.3

3.3

4

5.1

 

≤ 1300 cm - 15°C 

FT - flow/temperature

Summary of Contents for IPX4

Page 1: ...ELECTRIC INSTANTANEOUS DAFI WATER HEATER OPERATING INSTRUCTIONS IPX4 IPX5...

Page 2: ...bove 30 l about 83 The DAFI heater is provided with the hygiene certificate of the National In stitute of Hygiene CE certificate of compliance which gives the title to identify the product with the sa...

Page 3: ...nd M 22x1 M 24x1 aera tor reducer is supplied fig 1 a b 3 Construction of the water heater The DAFI heater consists of the heating block placed on the water unit The water unit is made of the base whi...

Page 4: ...cept responsibility for the damage and effects re sulting from unauthorised modifications and repairs of the heater 6 Sequence for connection of the device to the water supply system and the wiring sy...

Page 5: ...llation with the connection and nipples it is recommended to install the DAFI shut off valve at the water inlet to the heater If the valve is included in the set it may be purchased in the retail netw...

Page 6: ...e DAFI heater tap is screwed in fig 11a b reducer shower connector with the M 22 x 1 5 female thread and G 1 2 male thread to which the G1 2 elbow and then the DAFI heater tap are screwed in fig 11b F...

Page 7: ...ut off valve let the necessary water flow through it in order to remove the contamination and air which are present inside the water system Con nect the DAFI heater using the reducing nipples and hose...

Page 8: ...box for the auxiliary electrical equipment 2 in accordance with the markings on the box 3 then push it so that the body seal 4 could press against the wall on its whole circumference and fix it by me...

Page 9: ...iven in these operating instructions ensures proper operation of the DAFI heater NOTE In accordance with the International Safety Standards heating equipment should be subject to periodical surveys ev...

Page 10: ...are not subject to decomposition the equipment does not contain any other hazardous components 3 heating mass about 1 kg At the same time it is announced that in accordance with the regula tions of th...

Page 11: ...alve should be installed on the water inlet line to the DAFI heater All heater units for under sink installation can be installed at any angle Recommendations Installing a composite pipe from your DAF...

Page 12: ...Manufacturer FORMASTER S A 25 818 KIELCE Fabryczna 24 str Poland phone 48 41 3464810 ext 123 fax 48 41 3464870 www formaster com...

Reviews: