Operation & Function
6. Error Display
1) How to start : Push the TEMP button 30 times. And then keep pressing the button for 5 seconds.
2) How to exit : Returns to normal mode after 20 seconds automatically.
3) Error display in detail
- Cause : Defrost sensor is disconnected or short.
- Control : Defrosting is active for 30 minutes.
( Heater is on for 30 minutes and then off. )
- Cause : Refrigerator sensor is disconnected or short.
- Control : Compressor is on/off according to room temperature.
Error display
Explanation
Remark
Low LED is flicker
Mid LED is flicker
R.T.
~ 10
℃
11 ~ 15
℃
16 ~ 29
℃
35
℃
~
Comp. on/off
6 / 34 (min.)
10 / 30 (min.)
16 / 24 (min.)
20 / 20 (min.)
- Cause : Defrost mode ends after limit time 80 minutes.
( When evaporator is fully cover by frost or temperature
fuse is abnormal or Heater is disconneted. )
- Action : Need to check all defrost parts.
- Cause : After 2 hours' compressor runing time, defrost sensor is over -5
℃
( Cycle is abnormal : refrigerant leakage or block )
- Action : Need to check all cycle parts.
4) If there is no error, all LED is off when error display.
High LED is flicker
Quick LED is flicker