background image

INSTALLATION (CONTINUED)

13

AIR PURGING

Air and moisture remaining in the refrigerant system may create
adverse conditions as indicated below:

• pressure in the system rises
• operating current rises
• cooling efficiency drops
• moisture in the refrigerant circuit may freeze and block capillary

tubing

• water may lead to corrosion of parts in the refrigerant system

Therefore, the indoor unit and tubing between the indoor and
outdoor unit must be leak tested and evacuated to remove any
noncondesables and moisture from the system.

AIR PURGING WITH VACUUM PUMP (TEST
RUN)

Confirm each tube (narrow and wide tubes) between the indoor
and outdoor units has been properly connected and all wiring for
the test run has been completed. Remove the valve caps from
the wide and narrow service valves on the outdoor unit. Note that
both narrow and wide tube service valves on the outdoor unit are
kept closed at this stage (shipping position).

Leak Test

1. With the service valves on the outdoor unit remaining closed,

remove the threaded cover on the wide tube service port.
(Save for reuse.)

2. Attach a manifold valve (with pressure gauge) and dry nitro-

gen gas cylinder to this service port with charge hoses.

CAUTION:

Be sure to use a manifold valve for air purging. If it is not avail-
able, use a stop valve for this purpose. The “Hi” knob of the man-
ifold valve must always be kept closed.

3. Pressurize the system to no more than 150 P.S.I.G. with dry

nitrogen gas and close the cylinder valve when the gauge
reading reaches 150 P.S.I.G.  Next, test for leaks with liquid
soap.

CAUTION:

To avoid nitrogen entering the refrigerant system in a liquid state, the top of the nitrogen gas cylinder must be higher
than its bottom when you pressurize the system.  Usually, the cylinder is used in a vertical standing position.

4. Do a leak test of all joints of the tubing (both indoor and outdoor) and both wide and narrow service valves.  Bubbles

indicate a leak.  Be sure to wipe off the soap with a clean cloth.

5. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at

the nitrogen cylinder.  When the system pressure is reduced to normal, disconnect the hose from the cylinder.

Lo

Hi

Pressure
Gauge

Manifold Valve

Outdoor Unit

Indoor Unit

Charge Hose

Nitrogen Gas
Cylinder
(Vertical
Position)

Summary of Contents for DSB-071LH

Page 1: ...S1 MODEL DSB 071LH OWNER S MANUAL SPLIT AIRCONDITIONING SYSTEM ...

Page 2: ...nit s weight A frame may be necessary for added support When installing in a room make sure the tubes are well insulated to protect the walls and furniture from sweating of the tubes When installing in moist or uneven locations make sure to use a raised level concrete pad or concrete blocks to provide a level solid foundation for the out door unit this prevents water damage and vibration When inst...

Page 3: ...y and Inserting Wall Cap 12 Air Purging 13 Air Purging with Vacuum Pump 13 Test Run 15 Pump Down 15 OPERATING SECTION Location of Controls 16 Indoor Unit 16 Outdoor Unit 16 Remote Controller 18 Remote Display 19 Operation 19 Connecting the AC Cord 19 Setting the Unit for Remote Operation 20 How to Install Batteries 21 Celsius to Fahrenheit Conversion Chart 21 To Set the Unit to Auto Mode 22 To Ope...

Page 4: ...nal installer if necessary ACCESSORIES SUPPLIED WITH THE UNIT COPPER TUBING Copper tubing supplied is available at most dealers or A C shops Make sure the new copper tubing has the exact same specifications and diameter as the original copper tubing and is as short as possible BASIC ACCESSORIES 3 ON OFF ENTER CANCEL TIMER RESET SWING FAN SPEED MODE SLEEP ON OFF TEMP 1 5 6 2 3 4 7 8 INSTALLATION SE...

Page 5: ...m PVC Pipe 2 Tape 2TQ1008000 1 PVC 80W X 0 1T X 3 5m 3 Copper Tubing Extension 3100002600 1 1 2 1 4 Copper Tube 4 Insulator Plate 3103301000 1 F US 225 X 120 X 8T 5 Putty 2221040001 1 80g 6 Connection Cord 3102797200 1 1 5mm2 X 6m X 3P 7 Signal line Cord 3102796360 1 1 5mm2 X 6m X 2P 8 Cap Wall 3100900600 2 P P Complete Optional 3100019000 1 Accessories 1 2 3 4 5 6 7 8 ...

Page 6: ...95in from side wall Maximum Height 7M 21Ft Maximum Length 7M 21Ft Any tube length between 7 and 15 meters must be precharged with freon using the following calulation Length 5 x 30 grams Adding additonal tubing will decrease efficiency 6 0 c m 1 0 c m 7 0 c m 60 cm 3 9 inches 23 6 inches 23 6 inches 27 6 inches Plug into 220V AC Outlet Wall Wall Cap Drain Hose Pipes Not Supplied Wall Bracket AC Co...

Page 7: ...tion that is well ventilated Leave enough room around the unit for air intake ex haust and possible maintenance 2 Determine if the hole is to be made at the left or right hole location 10 mm 10 mm 150 mm 60 mm 3 Using drill with hole cutting attachment or equivalent cut a hole 65mm 2 56 in diameter The hole should be made at a slight downward slant to the outdoor side Measure the thickness from th...

Page 8: ...Loosen one screw for fixing the Connection Cover Loosen one screw at the Connection Cover Remove the Connection Cover 2 Fish the indoor outdoor wire from the rear of the in door unit through the front of the unit For easier connection make sure enough wire is pulled through the front Use the wire as shown below Brown Yellow Green Blue Blue Black INSTALLING THE INDOOR OUTDOOR WIRE TO THE INDOOR UNI...

Page 9: ...ubing are wrapped with the rubber insulation Using the tape wrap the indoor outdoor wire copper tubing and drain hose together MOUNTING THE INDOOR UNIT The Indoor unit must be mounted before connecting the indoor outdoor wire drain hose and copper tubing To mount follow the procedures below 1 The tubing can be extended in 4 directions as shown below No cutting is necessary for left rear and right ...

Page 10: ... copper tubing and drain hose through the hole in the wall angling downward Situate the indoor unit on the wall bracket by lifting the indoor unit slightly above the wall bracket and then down so it is securely locked in place 1 Remove the flare nut stoppers from the inside unit Determine the location of the copper tubing and where the bends will be Gently bend the copper tub ing making sure to us...

Page 11: ...rapping foam rubber or equivalent around the connection approxi mately 8mm thick so no copper tubing is exposed NOTES As with all wiring and hookups on this unit make sure the AC plug on the indoor unit is unplugged Be very careful not to strip the threads or flare nut When insulating the connections use foam rubber or equivalent 1 Connect the drain hose extension to the drain hose coming from the...

Page 12: ... 1 L 2 Terminals Housing Terminals on the indoor unit Main PCB Terminals Y 1 L 2 4 To connect wires loosen the screw in the Terminal Block and insert the correct wires like following fig ure Connect the Brown wire to the L connection Yellow Green wire to the connection the Blue wire to Y connection the Blue wire to 1 connec tion and the Black wire to 2 connection Insert Housing A and Housing B to ...

Page 13: ...p the previ ous turn by half the width of the tape TAPING UP THE WIRE TUBES HOSE After running the wire hose and tubing outside tape them up as shown below to insulate 3 Wrap the piping joints with the insulator plate and fasten it with vinyl tape pipe insulator plete vinyl tape 4 After wrapping the connection pipe with tape fasten it to the outside wall with saddles etc Saddle Not supplied Wall c...

Page 14: ...Save for reuse 2 Attach a manifold valve with pressure gauge and dry nitro gen gas cylinder to this service port with charge hoses CAUTION Be sure to use a manifold valve for air purging If it is not avail able use a stop valve for this purpose The Hi knob of the man ifold valve must always be kept closed 3 Pressurize the system to no more than 150 P S I G with dry nitrogen gas and close the cylin...

Page 15: ...n the valve CAUTION To avoid gas from leaking when removing the charge hose make sure the wide tube service valve is fully open and turned all the way out 3 Loosen the charge hose connected to the wide tube ser vice port slightly to release the pressure then remove the hose 4 Replace the threaded cover on the wide tube service port and fasten it securely This process is very important to prevent g...

Page 16: ...ION When opening or closing the service valve stem be sure to use a hex wrench PUMP DOWN Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas This is performed when the unit is to be relocated or the refrigerant circuit is serviced CAUTION Be sure to perform Pump Down procedure with the unit cooling mode Pump Down Procedure 1 Connect a low pressure gauge m...

Page 17: ...Cover Power Plug Cold Air Air In O N O F F E N T E R C A N C E L T I M E R R E S E T F A N D I R F A N S P E E D M O D E S L E E P O N O F F T E M P Remote Sensor LCD Remote Controller Deodorizing Filter Option Removes bad smells from the air INDOOR UNIT Connection Cover Remove cover to access the AC connection from this unit to the indoor unit Service Valves The indoor and outdoor units are conne...

Page 18: ... at inside of Front Panel At the time of operating open the Front Panel Emergency switch can be used when the remote controller is lost or Testing Remote switch is usually used by remote controller Indoor Unit Display Switch Panel Timer Yellow Lights during the time reservation mode Quick Red Lights during the Quick Mode ON Red Lights when the operation is going on Air clean Green EMR REMOCON ...

Page 19: ...ss to turn the unit on or off TEMPERATURE Buttons Press to raise or lower the desired temperature FAN SPEED Button Press to select the fan speed High Middle Llow COVER Slide down to access most of the remote buttons Slide down further to access the battery compartment AUTO FAN DIR REMOTE CONTROLLER MODE Indicators Auto Quick Cool Fan Dehumidifier Heat Lights to indicate the mode selected TIMER Ind...

Page 20: ...E switch is set to the RE MOTE position this will allow the unit to operate with the remote controller SETTING THE UNIT FOR REMOTE OPERATION After the unit is fully connected and plugged in it can be turned on To turn the unit on and set it for remote operation follow the procedures below 2 Press the ON OFF button on the remote controller to turn on the unit The On LED will light on the indoor uni...

Page 21: ...arity diagram below ON OFF TIMER ENTER CANCEL TURBO MILD BATTERY PRECAUTIONS The precautions below should be followed when using batteries in this device 1 Use only the size and type of batteries specified 2 Be sure to follow the correct polarity when installing the batteries as indicated in the battery compartment Reversed batteries may cause damage to the device 3 Do not mix different types of b...

Page 22: ...rn the unit on the On LED will light on the indoor unit and ON will light in the remote display 2 Press the MODE button until the Quick indicator appears in the dis play 3 The unit will then start cooling the room at the highest power AUTO 1 Press the ON OFF button on the re mote control to turn the unit on the On LED will light on the indoor unit and ON willlightintheremotedisplay 2 Press the MOD...

Page 23: ...ll light in the remote display 2 Press the MODE button until the Fan indicator appears in the display No allowance setting temperature TO OPERATE FAN ONLY To operate only the fan so the unit will circulate the air proceed as follows 1 Press the ON OFF button on the remote control to turn the unit on the On LED will light on the indoor unit and ON will light in the remote display 2 Press the MODE b...

Page 24: ...ally select the fan speed The fan will operate on low speed The fan will operate on medium speed The fan will operate on high speed NATURAL The fan will randomly cycle through the speeds simulating a cool breeze NOTE When the heating orperation is started hot air delivery might be delayed due to warm up period 1 Press the ON OFF button on the remote control to turn the unit on the On LED will ligh...

Page 25: ...button within 5 seconds of selecting the desired time If mote than 5 sec onds elapse steps 3 and 4 must be repeated 2 Press the TIMER OFF button once to enter the Timer screen 3 Repeatedly press the TIMER OFF but ton until the desired hour that you want the unit to shut off appears on the dis play For example if it is 8 00 P M and you want the unit to turn off at 10 00 P M select 2 hours 4 Press t...

Page 26: ...mpera ture using the TEMP or buttons 3 Press the SLEEP button on the remote con troller The unit will then be in the sleep mode and will cool the room to the desired tempera ture After a while the unit will increase the tem perature again This process will then repeat 4 Press the TURBO MILD button to select powerful cooling if this button is selected one more time it is become normal power TURBO M...

Page 27: ...lectrostatic back into the unit NOTES The filters should be changed every 6 months If in a climate with cold winters once a year is adequate After getting rid of vinyl in the filter Deodorizing and Electrostatic use it CLEANING THE INDOOR COVER To clean the indoor cover follow the procedures below 1 Remove the left and right side to open the indoor cover upward by two hands NOTE Please remove and ...

Page 28: ...off the indoor unit and then unplug it from the wall Clean the air filters Cover the outdoor unit with the supplied cover this is very important to protect this unit BEFORE THE SEASON Make sure the air filters are clean Make sure the inlet and outlet on the indoor and outdoor units are not blocked by obstructions Make sure the unit is grounded Consult a serviceman for help PRECAUTIONS Do not use t...

Page 29: ...for the unit to operate immediately back on the compressor will delay for 3 minutes The air filter s is dirty or clogged Clean or replace filter s Unit is located near a heat When locating unit for the first time source heater stove etc make sure it is in a desirable location A door or window is open Shut door or window There is an obstacle in front of Remove obstacle intake or indoor unit Thermos...

Page 30: ...mm Outdoor Unit Dimensions W 654 x H 549 x D 256 mm Net Weight Indoor 7 0 kg Outdoor 34 kg Connection Type Flare the piping Gas 1 2 12 7 mm Liquid 1 4 6 35 mm Air Cleaning Anti bacteria Filter Electrostatic Filter Deodorizing Filter Option Operating Indoor side Heating Mode min 21 C max 32 C min 15 C max 27 C Condition Outdoor side Heating Mode min 21 C max 43 C min 5 C max 24 C Design and specifi...

Reviews: