USER'S MANUAL

DDAE

8000

SE

Diesel generator

The following manual is only a guide to assist you and is not a complete or comprehensive manual 
of ali aspects of maintaining and repairing your generator. The equipment you have purchas d is a 
complex piece of machinery. We recommend that you consult with a dealer if you have doubts or 
concerns as to your experience or ability to properly maintain or repair your equipment. You will 
save time and the inconvenience of having to go back to the store if you choose to write or call us 
concerning missing parts, service question ,operating ad vice, and/or assembly questions. 
Our air-cooled diese) generators have sorne of the following feature:

• Lightweight construction
• Air cooled
• Four-stroke diesel internal combustion engine
• Direct fuel injection system
• Recoil starter or an optional electric starter
• Large fuel tank
• Automatic voltage stabilizer
• NFB circuit protector
• AC and DC outputs
• Low oil pressure sensor

The air-cooled diese! generators are widely used when electrical power is scarce. Our generators 
provide a portable mobile solution in supplying power for field operations during project construc-
tion. Sorne other known applications include pipeline construction and metal welding when electri-
cal power is not available. 
This manual will explain how to operate and service your generator set. 
lf you have any questions or suggestions about this manual. please contact your local dealer or us 
directly. Consumers should notice that this manual might differ slightly from the actual product as 
more improvements are made to our products. Some of the pictures in this manual may differ slight-
ly Jrom the actual product as well. We reserves the right to make changes at any time without notice 
and without incurring any obligation.

1. TECHNICAL SPECIFICATIONS AND DATA

Engine type: Single cylinder, Vertical, 4 Stroke, Direct injection, Air-cooled
Displacement: 418 cc
Max power: 5.5 kw
Rated power: 5.0 kw
Engine power: 10 hp / 3000 rpm
Bore×stroke: 86×72 mm
Fuel tank capacity: 15 L
Fuel tank capacity: 1.65 L
Compression ratio: 19:01
Starting system: Electric start
Starting motor capacity: 12 V - 0.8 kW
Charging generator capacity: 12 V - 8.3 A
Battery capacity: 12V - 30 Ah
Fuel consumption: 

370 g/kW.h

Insulation Grade: F
Power factor: 1
Noise level at 7M: 72 dBA
Phase NO.: Single phase
Continuous running time: 6 hr

2. OPERATING THE DIESEL GENERATOR

 
2-1 General main points of safety during operation of the generator set.

In order to operate the generator set safely,please follow all the instructions provided in this manual 
carefully . Doing so otherwise may lead to accidents and or equipment damage. 

2-1.1 Fire prevention 

The proper fuel for the diesel generator set is light diese! fuel . Do not use gasoline, kerosene and or 
other fuels other than light diesel fuel. Keep all flammable fuels away from the generator as the 
generator may spark and ignite these gases. In order to prevent fires from occurring and to provide 
enough ventilation for people and the machine ,keep the diesel generator at least 1.5meters or 5 feet 
away from buildings and or other equipment.Always operate your diesel generator on a level site .lf 
the generator is operated on an incline , the lubricating system within the engine will not perform 
well and may lead to failure of the engine. 

2-1.2 Prevention from inhaling exhaust gases

Never inhale exhaust gases emitted by the engine. The exhaust gases contain toxic carbon monoxi-
de.Never operate your generator in places with poor ventilation.ln order to operate this machinery 
indoors , a suitable ventilation system for the building is required to draw the poisonous exhaust 
gases out. 

2-1.3 Prevention from accidental bums

Never touch the muffler and its cover when the diesel engine is running .Never touch the muffler and 
cover after the diesel engine has been used, as the muffler remains hot for a good period of time. 

2-1.4 Electris shock and short circuits

Never touch the generator if the generator is wet.Also never touch the generator if your hand is 
wet.Never operate your generator if the weather conditions call for any type of precipitation such as 
rain ,snow or fog .To prevent electrical shocks,the generator should be grounded. U se a lead to 
connect the grounding end of the generator to the grounding surface of choice.

NOTE:

 When connection devices to the generator, make sure all other devices are rated lower than 

the generators output. Any generator socket should not be overloaded over its regulated limit.

2-1.5 Other safety points

Before operating this generator, all operators should have a good knowledge of how to break the 
circuit if any accidents occur .Also,all operators should be familiar with all the switches and func-
tions of the generator before using tkis machine .While operating the generator , wear safe shoes 
and suitable clothes during operation.Always keep children and animals away from the generator. 

2-1.6 Battery

The electrolytic liquid of the battery contains sulfuric acid .In order to protect your eyes,skin and 
clothing ,wear protective gear when working with the battery.lf you come in contact with the elec-
trolytic liquid, wash it immediately with clean water.Also, if the electrolytic liquid comes in contact 
with your eyes,see a doctor immediately. 

2-2 Preparation before operation 
2-2. l Fuel choices and fuel treatment

Fuel tank 

Use only light diesel fue l. The fuel should be filtered clean. Never Jet dust and water mix with fuel in 
the fuel tank. Otherwi se it will clog the fuel lines and oil nozzles. It may also damage your pressure 
pump. 

NOTE:

 lt is dangerous to overfill the fuel tank. Never exceed the red piston in the filter. 

a. After purchasing fuel, put it into a drum and let it sit for 3-4 days.
b. 3-4 days later, insert half of the fuel sucker into the drum (water and impurities stay in the lower 
portion of the drum).

Air filter element

Do not wash the air filter. The element is made of dry material, which does not permit washing. 
When the output of the diesel engine is bad or the color of the exhaust gas is abnormal, replace the 
air filter element. Never start the diesel engine without the air filter.

NOTE:

 Never smoke near the opening of the fuel tank. Do not let sparks get near the fuel or fuel tank 

and do not overfill tank. After filling, tighten the fuel cap.

2-2.2 Fill engine oil
Fubrication Oil Filling Inlet 

Put the generator set in level state. Fill the oil into the oilfilling inlet. At the time of checking the oil 
level, it is necessary only to lightly insert the oil ruler. Please pay attention to that you should not 
rotate the oil ruler. 

Engine oil is the most important factor in deterrnining the life of your generator engine.If you
use poor engine oil or if you don't change the oil regularly,the piston and cylinder will wear
easily or seize up.Also,the life of the other parts in your engine such as bearings,and other
rotating parts will shorten considerably.

Although there is an alarm system to check for low oil pressure, it is always a good idea to check 
the amount of oil inside the engine. lf the oil level is low, fill it before starting the engine. A good time 
to drain the oil from the engine is when the diese! engine is still hot. If the engine is fully cooled, it is 
more difficult to drain all the oil out or sorne impurities will remain in the engine.

WARNING:

 Don't fill engine oil when diesel is operating.

2-2.3 Check air filter

(1) Loosen the butterfly nut, take the cover of the air filter off and take the air filter element out. 

Do not use detergent to wash the air filter element. When the performance of the engine decreases 
or when the color of the exhaust gases is bad,exchange the filter element. Never start the engine 
without the air filter as foreign objects may enter the intake and damage the engine.

Summary of Contents for DDAE8000SE

Page 1: ...Manufactured under license of Daewoo International Corporation Korea www daewoopowerproducts com USER S MANUAL DDAE8000SE Diesel generator...

Page 2: ...INDEX 1 TECHNICAL SPECIFICATIONS AND DATA 3 2 OPERATING THE DIESEL GENERATOR 3 3 MAINTENANCE 12 4 OVERHAULING AND TROUBLESHOOTING 16 5 PART LISTINGS 17 6 REMOTE CONTROL INSTRUCTIONS 22 WARRANTY 23 1...

Page 3: ...r or an optional electric starter Large fuel tank Automatic voltage stabilizer NFB circuit protector AC and DC outputs Low oil pressure sensor The air cooled diese generators are widely used when elec...

Page 4: ...asoline kerosene and or other fuels other than light diesel fuel Keep all flammable fuels away from the generator as the generator may spark and ignite these gases In order to prevent fires from occur...

Page 5: ...While operating the generator wear safe shoes and suitable clothes during operation Always keep children and animals away from the generator 2 1 6 Battery The electrolytic liquid of the battery conta...

Page 6: ...ap 2 2 2 Fill engine oil Fubrication Oil Filling Inlet Put the generator set in level state Fill the oil into the oilfilling inlet At the time of checking the oil level it is necessary only to lightly...

Page 7: ...to drain all the oil out or sorne impurities will remain in the engine WARNING Don t fill engine oil when diesel is operating 2 2 3 Check air filter 1 Loosen the butterfly nut take the cover of the ai...

Page 8: ...the capacitor is turned off Otherwise it will burn tpe capacitor For silent set the inspection may not be carried out 2 2 5 The fuel and oil in a new engine is drained before sold Before you start the...

Page 9: ...ine the engine must be properly broken in The break in period is about 20 hours l Avoid overloading the engine when brand new 2 Change the engine oil according to specifications An oil change for a br...

Page 10: ...ne failure 2 4 2 Electric starting The procedures for preparing to start eh engine are the same as the manual starting engine 2 4 3 Battery 1 Insert key into ignition and put it in the off position 2...

Page 11: ...Operating the diesel engine 1 Pre heat the diesel engine for 3 minutes under no load conditions 2 First check the height of the lubricating oil level if it is low refill it Our diesel engines are equi...

Page 12: ...too low adjust the speed accordingly If there are problems stop the generator immediately and fix the issue 5 Make sure you are operating your generator in a well ventilated area The generator should...

Page 13: ...u feel resistance this is when the piston is on the compression stroke where the intake and exhaust valves are closed What this does is prevent the engine from rustiong when not in use 3 MAINTENANCE 3...

Page 14: ...anging the engine oil every 100 hours Take the oil cover out Take off the oil drain plug when the diese engine is still hot Be careful of hot oil and hot engine as you may get burned The bolt is locat...

Page 15: ...mmended time period for cleaning the fuel filter is 6 months or 500 hours of operation a To do this first drain the fule from the fuel tank b Loosen the small screws on the fuel switch and remove the...

Page 16: ...ting oil in it ten cover the plughole up again 4 For manual starting generators press the decompression handle down and pull the recoil handle 2 or 3 times This pushes the intake out Do not start the...

Page 17: ...g or have any questions please feel free to contact your local dealer or with our company directly Below is a list of sorne information you should have ready before contacting your local dealer or us...

Page 18: ...s diesel engine 1 2 Starter Motor 1 3 Flywheel generator 1 4 Bolt 2 5 Voltage Regulator 1 6 Battery Cable red black 2 7 Battery 1 8 Oil level sensor 1 9 Generator 1 10 Output panel assembly 1 11 Throt...

Page 19: ...elbow 1 3 Left outer cover 1 4 Fuel gauge 1 5 Fuel tank sleeve 1 6 Main cover 1 7 Door knob 1 8 Right outer cover 1 9 Output panel assembly 1 10 Air cleaner cover 1 11 Lower chassis 1 12 Engine tray...

Page 20: ...ntity 1 Positive DC port 1 2 Negative DC port 1 3 Grounded bolt 1 4 Bolt 2 5 Large nut 1 6 Bolt 2 7 Boly 2 8 Large nut 1 9 Current adjusting switch 1 10 3 Prong socket 6 11 Bolt 6 12 Electric panel bo...

Page 21: ...Nut 2 25 Breaker 1 26 Wiring hamess 1 27 Electrical box 1 Generator head assembly Number Part Description Quantity 1 Front end cover 1 2 Diode 2 3 M4 x 8 Bolt 2 4 Fan Blade 1 5 Bearing 1 6 Rotor Unit...

Page 22: ...7 Large flat washer 6 4 8 Fuel tank lining 4 9 Shock absorbing gasket 4 10 Fuel tank 1 11 M6 Nut 4 12 O ring seal 1 13 Fuel tank filter 1 14 O ring gasket 1 15 Fuel filter cover 1 16 Cover 1 17 Wing n...

Page 23: ...tery in the remote contro1 23A 12V 2 Operation procedures I Remote control starting DO NOT USE THE STARTING SWITCH The generator will automatically start when you press the l key twice If starting in...

Page 24: ...r more nodes teaser on the surfaces of the cylinder and the piston or destruction of piston rings Also the warranty does not cover failure of the automatic voltage regulator due to incorrect operation...

Page 25: ...www daewoopowerproducts com Manufactured under license of Daewoo International Corporation Korea...

Reviews: