7
Installation Specifications
You can increase the duct size over the duct run if
•
desired. To prevent a back draft, never decrease the
duct size over the run.
Do not rely on duct tape alone to seal duct joints.
•
Fasten all connections with sheet metal screws and
tape all joints with certified silver tape or duct tape.
Use sheet metal screws as required to support the duct
•
weight.
To prevent back-drafts, a damper at the duct outlet may
•
also be required.
Make sure duct work does not interfere with floor joists
•
or wall studs.
With concrete slab construction, “box-in” the duct work
•
and blower wiring to prevent collapsing or other dam-
age when the wet concrete is poured.
Cross-drafts or air currents from adjacent open win-
•
dows or doors, heating/air conditioning outlets, ceiling
fans and recessed ceiling lights reduce vent efficiency.
Duct Work Design Tips
Wherever possible, reduce the number of transitions
•
and turns to as few sharp angles as possible. Two
staggered 45° angles are better than one 90°. Keep
turns as far away from the hood exhaust as possible,
with as much space between each bend as possible.
For best performance, use round duct instead of rect-
•
angular when possible, especially when elbows are
required.
If multiple elbows are used, try to keep a minimum of
•
24” of straight duct between them. Avoid “S” or “back to
back” configurations of adjacent elbows.
Do not use flexible metal duct.
•
You must install one of the Dacor blower models listed
below for proper operation. For ILHSF or REMP series
blowers, see the blower installation instructions. For model
CABP3, see the instructions later in this manual. Only one
blower shall be installed.
APPROVED DACOR BLOwERS FOR USE wITH
RV SERIES RAISED VENTS
Model Number
Rating
CABP3
600 CFM
*
ILHSF8
600 CFM
**
ILHSF10
1100 CFM
**
REMP3
600 CFM
**
REMP16
1000 CFM
**
* Nominal rating at zero inches static pressure, see the
CABP3 Cabinet Blower Data
on page 15 for actual rating.
** Nominal rating at zero inches static pressure. See the
blower installation instructions for actual blower rating.
The raised vent can be configured to exhaust through
•
the bottom or either side:
On installations using the ILHSF or REMP series
►
blowers, the cover plate on the appropriate
side or on the bottom is removed to expose the
exhaust. See page 8 for locations and dimensions.
Configure the raised vent for bottom exhaust and
use an elbow to vent through the rear cabinet wall.
On installations using the CABP3 blower, the blow-
►
er assembly is mounted to the front of the raised
vent with the exhaust pointing in the desire direc-
tion. See page 8. Point the exhaust down and use
an elbow to vent through the rear cabinet wall.
When planning new duct work, always look for the
•
shortest, most direct route to the outside. See pages
5 and 6 for examples. Calculate the maximum duct
length (see page 9) to determine if the planned duct
route will work with the blower selected.
On bottom exhaust installations you may cut a hole in
•
the floor to allow the duct work to pass through.
All duct work materials (including screws and duct tape)
•
must be purchased separately by the customer.
Planning the Duct Work
wARNING
To reduce the risk of fire and to properly exhaust air, be sure to duct air outside the house or building. Do not vent
•
exhaust air into spaces within walls or ceilings or into attics, crawl spaces or garages.
Tape all duct joints securely to prevent combustion by-products, smoke or odors from entering the home. Doing so
•
will also improve system efficiency.
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCT WORK.
•
DO NOT
•
install more than one blower. Even small differences between blower air flow rates can greatly reduce the
air draw by the raised vent.
Summary of Contents for RV30
Page 18: ...16 Notes...
Page 19: ......