D+H RZN 4404-K V2 Instructions Manual Download Page 13

-

+

-

+

N– N+ Z

+ M

D1 D2

Cutout 
button

Magnetic 
clamps

RZN 4404-K

99.823.80 3.7/06/19

99.823.80 3.7/06/19

28

/

36

RZN 4404-K

 

13

/

1

7

Connection of magnetic clamps

Magnetic clamps 24V (max. 500 mA overall power)
No output voltage during power failure!

Group output:

While an alert, a possible group disturbance will 
not notified. Only after reset the alarm, a fault 
message will be indicated.

High-speed function (HS):

All D+H drives with SHEV high-speed function are 
supported. In daily ventilation operation, a consi-
derable noise reduction is achieved through the 
reduced drive speed. In case of SHEV the drives 
run with a very high speed to reach the OPEN 
position defined within 60 seconds at the most.

SHEV retriggering:

(When DIP switch S1.10 = ON)
The smoke vents will be triggered with an OPEN- 
impulse every 2 minutes for a duration of 30 
minutes according to VdS 2581. For this, the 
drives must be blockage safe. All D+H drives meet 
this precondition. Otherwise the DIP switches has 
to be switched on OFF. 

Mounting of the drives:

Please take mounting informations from the 
relevant instruction for use of the respective drive, 
because of varied possibilities for choosing drives.

Drives

Connection of fire detector

Max. 14 fire detectors connectable.
Only D+H approved detectors must be used.

*  Terminal resistors for line monitoring

 It is pinched in control panel for transport.

Take it off there and connect according to plan.
Terminal resistor must remain at terminal RM 1,2,

 when no fire detector or external control exists!

Connection of fire alarm system 

English

Information for starting

Carry out following sight and performance checks for switching-on the smoke and heat vent 
control panel.

All cables 

connected?

Factory set?

(DIP switch)

10kΩ resistor in 

smoke vent 

button?

End module 

2x47kΩ 

in junction box?

Connect mains. 

LED mains lightens? 

Connect battery 

lines. Control l

ightens?

Smoke vent flap opens 

and closes?

All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of 
control panel. The smoke vent opens self-acting and can be 
reset under special conditions only.

yes

yes

yes

yes

yes

yes

yes

Performance check alarm/reset and ventilation

yes

Partial or incomplete connection of 
components can cause malfunction. 
Check following connections: mains 230 V, 
drives, smoke vent buttons, when necessary 
fire detectors and vent buttons. 
See wiring an connection plans pages 26-28.

Delivery condition of DIP switch see page 24.

Resistor must be cramped in electric last 
button on terminal 3/8 (RT 45).
See connection plan pages 26-27.

Resistor must be cramped in last or only fire 
detector on terminal 3 and 5 (type SD-O/FD-T). 
Resistor remains in control panel between 
terminal RM "R" and "–", when no fire 
detector is connected.
See connection plan page28.

10kΩ resistor in fire 

detector?

yes

End module on last or only drive in junction 
box on wire 5 orange, 6 black, 7 black.
See connection plan page 26.

Check line safety fuse in distribution box and 
fuse mains in control panel.

Mains still not available or line switch on "0" 
or one of fuses faulty.

Possibly change poles in drive.

no

no

no

no

no

no

no

no

R

Operating contact

Alarm resistor
1k

W

BMZ / BMA 

Terminal resistor*
10k

W

RZN 4404-K V2

RM

RT

1

2

first to penultimate 

fire detector

last

fire detector

SD-O 371
or
FD-T 271

RZN 4404-K V2

RM

RT

1

2

R

EP

 6

EM 2

1

C 3

IN 4

OUT 5

EP

 6

EM 2

1

C 3

IN 4

OUT 5

< optional >

10 k

W

Summary of Contents for RZN 4404-K V2

Page 1: ...RZN 4404 K V2 RZN 4404 K V2 ZP RZN 4404 K V2 GEH KST 0786 CPD 50383 EN 12101 10 2005 AC 2007 conform RZN 4404 KS V2 ZP RZN 4404 K V2 GEH S RWA Original instructions...

Page 2: ...Mounting of SHEV control panel with housing GEH KST 6 View motherboard 7 DIP switch settings 8 Cables for D H smoke an heat vent systems Wiring plan Paragon 9 230 V supply 10 Connection overview 10 C...

Page 3: ...disposal to professionally install your system and commission it Our partner system guarantees that D H products are installed exclusively by trained and experienced fitters in compliance with the te...

Page 4: ...been authorized by the appliance manufacturer Servicetimer Inspection and maintenance has to be carried out according to D H maintenance notes Only original D H spare parts may be used Repair is to be...

Page 5: ...s protection IP30 IP54 Protection class II with fuctional ground I Dimensions WxHxD 310 x 310 x 100 mm 400 x 300 x 120 mm Technical data SHEV alarm Malfunction Mains existing Vent button function OPEN...

Page 6: ...RE FUM ROOKAFVOER R G L E M ODDYMIANIE EVACUACI N DE HUMOS DESENFUMAGE ODVOD KOU E ODVOD DYMU BRANDVENTILATION 2 x 1 2 A h 2 x 3 4 A h max 5 mm not included 4x Install batteries Position of the centra...

Page 7: ...gnal DIP switch S1 Fuse mains Battery charging voltage regulator Battery connection LED battery fault Fuse battery OPEN running time limitation Ventilation time limitation Line ON OFF RESET D1 D47 D42...

Page 8: ...ose SHEV in the smoke vent button is pressed OPEN display on vent button is no longer possible then The function power failure CLOSE will be ineffective see DIP switch 4 6 ON Drives OPEN up to final p...

Page 9: ...ne monitoring on which also the SHEV high speed HS signal is transmitted to the drive If group DIP switch 8 is ON the group will in case of a fault automatically triggered and opens Line cable control...

Page 10: ...l after mains cable has been connected L N PE 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 OK Line T R A K E A a Z b S RZN 4404 K V2 Line N Control Alarm CLOSE Mot b Mot a Monitoring OP...

Page 11: ...re 3 4 5 6 7 8 RZN 4404 K V2 Line Control Alarm CLOSE RM 10kW Alarm Control Line Line CLOSE Failure Shunt connection by customer Alarm Control Line CLOSE Failure n c RT 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6...

Page 12: ...minutes according to VdS 2581 For this the drives must be blockage safe All D H drives meet this precondition Otherwise the DIP switches has to be switched on OFF Mounting of the drives Please take m...

Page 13: ...lete connection of components can cause malfunction Check following connections mains 230 V drives smoke vent buttons when necessary fire detectors and vent buttons See wiring an connection plans page...

Page 14: ...ol Manual opening by smoke vent button Automatic opening by fire detector Automatic opening by external control e g fire alarm system OK SMOKE VENT OK Reset 0 I System Line D47 D42 D20 OK OK RT RZN Re...

Page 15: ...f non resettable alarm Reset OFF ON Reset 0 I System Line OK click OFF Reset 0 I System Line OK With manual release In case of automatic release by fire detector or external control External control o...

Page 16: ...n Do not ventilate via smoke vent button because otherwise there would be a danger of damage by wind or water The weather automatic can be switched off via an optional automatic switch if gap ventilat...

Page 17: ...units Functional testing of connected system components Record of competent carrying out of maintenance and designation according to directions Inspection Regular visual inspection between maintenance...

Reviews: