background image

RZN 4404-K

99.823.80 3.7/06/19

99.823.80 3.7/06/19

10

/

1

7

 

RZN 4404-K

27

/

36

Connection overview

230 V, 50 Hz

Seperate electric circuit..
Mark fuse.

230 V supply

Protective earth (PE)

Only with KS-Version.

Protection cap:

Place enclosed protection cap 
over supply terminal after mains 
cable has been connected.

L
N
PE

2

8

3

1

6

4

7

5

R

T

 45

2

8

3

1

6

4

7

5

RT 45

2

8

3

1

6

4

7

5

OK

Line 

T

R

A

K

E

A

a

Z

b

S

RZN 4404-K V2

Line

N–

Control

Alarm

CLOSE

Mot.b

Mot.a

Monitoring

OPEN

CLOSE

Open signal (only with L

T

 43U-SD)

RM

LT

10k

W

Failure

Alarm

Control

Line 

CLOSE

Failure

n.c.

RT

MOT

10k

W

OK

L

N–

Z

LT 84-U (-SD)

L

P

EM 47 K

2x47k

W

(BK)

(BK)

(OG)

Mot.b

Mot.a

HS

Drive

Mot.b

Mot.a

HS

Connection of smoke vent buttons

Max. 8 buttons per line connectable.

Standard connection

Parallel connection

Parallel connection of 2x 2 buttons

2

8

3

1

6

4

7

5

R

T

 45

first to penultimate

 button

2

8

3

1

6

4

7

5

RT 45

2

8

3

1

6

4

7

5

OK

last button

Line 

3

4

5

6

7

8

RZN 4404-K V2

Line

Control

Alarm

CLSOE

RM

10k

W

Failure

Alarm

Control

Line 

CLOSE

Failure

n.c.

RT

Line 

n.c.

Failure

3

4

5

6

7

8

RZN  4404-K V2

Line

Control

Alarm

CLOSE

RM

10k

W

Alarm

Control

Line

Line

CLOSE

Failure

*

*

* Shunt connection by customer

Alarm

Control

Line 

CLOSE

Failure

n.c.

RT

2

8

3

1

6

4

7

5

RT 45

2

8

3

1

6

4

7

5

OK

2

8

3

1

6

4

7

5

RT 45

2

8

3

1

6

4

7

5

OK

2

8

3

1

6

4

7

5

R

T

 45

2

8

3

1

6

4

7

5

R

T

 45

first to penultimate 

button each

last button each

Line 

n.c.

Failure

3

4

5

6

7

8

RZN 4404-K V2

Line

Control

Alarm

CLOSE

RM

Alarm

Control

Line

Line

CLOSE

Failure

*

*

Alarm

Control

Line 

CLOSE

Failure

n.c.

RT

* Shunt connection by customer

10k

W

2

8

3

1

6

4

7

5

RT 45

2

8

3

1

6

4

7

5

OK

2

8

3

1

6

4

7

5

RT 45

2

8

3

1

6

4

7

5

OK

English

3

2

5

SD-O 371

3

2

SD-O 371

5

Summary of Contents for RZN 4404-K V2

Page 1: ...RZN 4404 K V2 RZN 4404 K V2 ZP RZN 4404 K V2 GEH KST 0786 CPD 50383 EN 12101 10 2005 AC 2007 conform RZN 4404 KS V2 ZP RZN 4404 K V2 GEH S RWA Original instructions...

Page 2: ...Mounting of SHEV control panel with housing GEH KST 6 View motherboard 7 DIP switch settings 8 Cables for D H smoke an heat vent systems Wiring plan Paragon 9 230 V supply 10 Connection overview 10 C...

Page 3: ...disposal to professionally install your system and commission it Our partner system guarantees that D H products are installed exclusively by trained and experienced fitters in compliance with the te...

Page 4: ...been authorized by the appliance manufacturer Servicetimer Inspection and maintenance has to be carried out according to D H maintenance notes Only original D H spare parts may be used Repair is to be...

Page 5: ...s protection IP30 IP54 Protection class II with fuctional ground I Dimensions WxHxD 310 x 310 x 100 mm 400 x 300 x 120 mm Technical data SHEV alarm Malfunction Mains existing Vent button function OPEN...

Page 6: ...RE FUM ROOKAFVOER R G L E M ODDYMIANIE EVACUACI N DE HUMOS DESENFUMAGE ODVOD KOU E ODVOD DYMU BRANDVENTILATION 2 x 1 2 A h 2 x 3 4 A h max 5 mm not included 4x Install batteries Position of the centra...

Page 7: ...gnal DIP switch S1 Fuse mains Battery charging voltage regulator Battery connection LED battery fault Fuse battery OPEN running time limitation Ventilation time limitation Line ON OFF RESET D1 D47 D42...

Page 8: ...ose SHEV in the smoke vent button is pressed OPEN display on vent button is no longer possible then The function power failure CLOSE will be ineffective see DIP switch 4 6 ON Drives OPEN up to final p...

Page 9: ...ne monitoring on which also the SHEV high speed HS signal is transmitted to the drive If group DIP switch 8 is ON the group will in case of a fault automatically triggered and opens Line cable control...

Page 10: ...l after mains cable has been connected L N PE 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 OK Line T R A K E A a Z b S RZN 4404 K V2 Line N Control Alarm CLOSE Mot b Mot a Monitoring OP...

Page 11: ...re 3 4 5 6 7 8 RZN 4404 K V2 Line Control Alarm CLOSE RM 10kW Alarm Control Line Line CLOSE Failure Shunt connection by customer Alarm Control Line CLOSE Failure n c RT 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6...

Page 12: ...minutes according to VdS 2581 For this the drives must be blockage safe All D H drives meet this precondition Otherwise the DIP switches has to be switched on OFF Mounting of the drives Please take m...

Page 13: ...lete connection of components can cause malfunction Check following connections mains 230 V drives smoke vent buttons when necessary fire detectors and vent buttons See wiring an connection plans page...

Page 14: ...ol Manual opening by smoke vent button Automatic opening by fire detector Automatic opening by external control e g fire alarm system OK SMOKE VENT OK Reset 0 I System Line D47 D42 D20 OK OK RT RZN Re...

Page 15: ...f non resettable alarm Reset OFF ON Reset 0 I System Line OK click OFF Reset 0 I System Line OK With manual release In case of automatic release by fire detector or external control External control o...

Page 16: ...n Do not ventilate via smoke vent button because otherwise there would be a danger of damage by wind or water The weather automatic can be switched off via an optional automatic switch if gap ventilat...

Page 17: ...units Functional testing of connected system components Record of competent carrying out of maintenance and designation according to directions Inspection Regular visual inspection between maintenance...

Reviews: