99.826.36 1.1/03/16
99.826.36 1.1/03/16
4/12
5/12
English
English
LDF 100/030-L/-R
LDF 100/030-L/-R
Technical Data
Running speed and forces*
CLOSED
Closure Ranges
Cable from
the top
Closing edge protection
In the "CLOSE" direction the drive has an
active protection for the main closing
edge. If there is an overload in the closing
range 3 and 2, the drive runs "OPEN" for
10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the
drive remains in this position.
In addition, the drive is equipped with
passive protection. The closing speed in
closing range 2 and 1 is reduced.
Significantly greater forces
can be exerted at the
secondary closing edges.
Danger of crushing hands
and fingers!
Intended use
®
- Drive for electric opening and closing for Fieger
louvre windows
- The louvre must be prepared by the louvre
manufacturer for the application of the drive
- Operating voltage 24 V DC
- Usable for smoke extraction as well as daily
ventilation
- Only for inside mounting
Type
LDF 100/030
LDF 100/030-IP 54
Power supply
24 V DC / ±15% / 0,8 A
24 V DC / ±15% / 0,8 A
Nominal force
900 N
900 N
Nominal stroke *
28 mm
28 mm
Running time (OPEN)
≤ 30 sec.
≤ 30 sec.
Ingress protection
IP 50
IP 54
Lifetime
>20 000 double strokes
Duty cycle
30 %, With cycle time 10 minutes
Housing
Stainless steel
Temperature range
-5 ... +75°C
Fire stability
30 min / 300°C
Emission sound pressure level
LpA ≤ 70 dB(A)
Additional functions *
Closing edge protection activated, 3 stroke repeatings
* Programmable with SCS software
2,1 mm/sec. / 900 N
OPEN
III
II
I
1 mm/sec.
900 N
0,6 mm/sec.
250 N
2,1 mm/sec.
900 N
2 mm
5 mm
Starting
Do not run the drive without the tappet driver,
otherwise the drive could be damaged.
A reference run must be carried out for the first
starting and after exchange of one of the drives. In
this process the drive will determine its zero point
(Closed-position). This single event is called null
balance.
- Connect drive
- Trigger drive in CLOSED-direction
(independent on the position of louvres)
After an overload cutoff has been effected in
running direction „CLOSED", the drive will have a
new zero point. During the reference run, no
obstacle must impair the running of the louvres.
The hand guard in arms's reach is
deactivated during the reference
run (danger of squeezing)!
- Cable entry must be carried out from the top
- The louvre must be prepared by the louvre
manufacturer for the application of the drive
Mounting notes
Drive unit with 2,5 m silicone cable and tappet driver.
Extent of supply
Safety notes
Safety extra low voltage 24 V DC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
- Just use unchanged original D+H parts
Observe enclosed r
ed safety slip!
Performance Features
- Microprocessor controlled synchro electronics
for a precise synchronous run of up to 2 drives
(Tandem programming required by SCS software)
- Individually programmable (via software SCS)
- Protection system for the main closing edge
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling. Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for
waste electrical and electronic equipment and its
implementation into national right, electrcal devices
that are no longer usable must be collected separa-
tely and disposed of in an environmentally correct
manner.
Disposal
Declaration of Conformity
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder
Maik Schmees
Member of the Board
Authorized signatory, Technical Director
24.02.2016
Maintenance and cleaning
Maintenance work is only allowed when the device is in
a de-energized condition! Inspection and maintenance
has to be carried out according to D+H maintenance
notes. Only original D+H spare parts may be used.
Repair is to be carried out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
Guarantee
You will get 2 years guarantee for all D+H products
from date of verified handing over of the system up to
maximal 3 years after date of delivery, when
mounting and starting has been carried out by an
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.
WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.