GVL 8408-M
GVL 8408-M
99.824.66 1.6/03/16
99.824.66 1.6/03/16
2/8
3/8
English
English
Technical data
Type
: GVL 8408-M
Nominal voltage
: 115 V AC ± 10%, 60 Hz
Rated power
: 240 VA
Stand-by operating : 2.5 W
Class of rating
: short-time duty, 20%
Protection class
: I
Ingress protection
: IP 30
Temperature range : -5...+40°C (23...104°F)
Output voltage
: 24 V DC / res. ripple. <10%
Safe output: *
Running current of drives :
6.4 A
Rated current of drives
:
8 A
Housing
: plastic, white
Dimensions
: 12.1'' x 12.1'' x 3.9''
* Please observe:
The
output current of the groups
1 ... 6
amounts
max. 4 Amp
.
The
total output current
of the control panel,
is limited
up to 8 Amp
.
Intended use
- ventilation control for small to medium sized
building objects
- for triggering of 24 V DC drives
- 5 ventilation groups, expandable to 6 groups
- 8 A total actuating current - stabilized
- Only for indoor mounting
Performance features
- Ventilation safety function (key operation
OPEN/CLOSE), can be free encoded
- Weather automatic for single groups,
can be switched on and off
- Entry for external control, e.g. timer
- Possibility of connecting rain detector or wind/ rain
detector without supplementary module
- Plastic housing, surface mounted type with
lockable steel sheet door
View motherboard
groups
window drives*
vent button*
room temp. control*
Control panel (GVL 8408-M)
rain sensor*
external control*
Example for Application
* optional function extension
(separate components, retrofitable!)
This instruction includes descriptions and
connection plans of components which are not part
of scope of supply of control panel. You can order
these parts and many more separately from your
D+H distributor. Further connecting plans are
available there as well.
Safety notes:
When installing the Ventilation Control Panel (VCP-M 8408), basic safety precautions should
always be followed to reduce risk of fire, electric shock, and personal injury.
Failure to follow these instructions could result in death or serious injury.
Operating voltage 115 VAC!
Connection has to be carried out only by an authorized electrical specialist.
Mounting of the control panel should be carried out by a D+H distributor, whose qualification and
experience is ensured by regular in-house training.
All wiring must be installed by a qualified electrican according to e.g. National Electrical Codes,
NFPA 70 and local codes.
For continued protection against fire, replace only with the same type and rating of fuse.
Only for indoor mounting.
Just use unchanged original D+H parts
For North America:
The International Building Codes have to be observed
For continued protection against fire,
replace only with the same type and rating of fuse.
WARNING
WARNING
fuse mains
Mulitpoint connector for
further group plug-in unit
LED Power ON
28 - 14 AWG
max. 4.5 lb-in
22 - 12 AWG
max. 6 lb-in
mains connector
S1
F3.15A
T2.5A
S2
F3.15A
S3
F3.15A
S4
F3.15A
S5
F3.15A
Power
115 VAC
www.dh-partner.com
Ventilation control panel
GVL 8408-M
Group 1
Group 2
Group 3
Group 4
Group 5
WARNING
For continued protection against fire,
replace only with the
same type and rating of fuse.
fuse drive
group 1
DIP-switch S1
fuse drive
group 2
DIP-switch S2
fuse drive
group 3
DIP-switch S3
fuse drive
group 4
DIP-switch S4
fuse drive
group 5
DIP-switch S5
group 1-5: 22 - 12 AWG / max. 4.5 lb-in