background image

GVL 8408-M

GVL 8408-M

99.824.66 1.6/03/16

99.824.66 1.6/03/16

2/8

3/8

English

English

Technical data

Type 

:  GVL 8408-M

Nominal voltage 

:  115 V AC ± 10%, 60 Hz

Rated power 

:  240 VA

Stand-by operating  :  2.5 W
Class of rating 

:  short-time duty, 20%

Protection class 

:  I

Ingress protection 

:  IP 30

Temperature range  :  -5...+40°C (23...104°F)
Output voltage 

:  24 V DC / res. ripple. <10%

Safe output: *
  Running current of drives   : 

6.4 A

  Rated current of drives 

8 A

Housing 

:  plastic, white

Dimensions 

:  12.1'' x 12.1'' x 3.9''

* Please observe:
The 

output current of the groups

 1 ... 6

amounts 

max. 4 Amp

.

The 

total output current

 of the control panel,

is limited 

up to 8 Amp

.

Intended use

-  ventilation control for small to medium sized
  building objects
-  for triggering of 24 V DC drives
-  5 ventilation groups, expandable to 6 groups
-  8 A total actuating current - stabilized
-  Only for indoor mounting

Performance features

-  Ventilation safety function (key operation
  OPEN/CLOSE), can be free encoded
-  Weather automatic for single groups,
  can be switched on and off
-  Entry for external control, e.g. timer
-  Possibility of connecting rain detector or wind/ rain
  detector without supplementary module
-  Plastic housing, surface mounted type with
  lockable steel sheet door

View motherboard

groups

window drives*

vent button*

room temp. control*

Control panel (GVL 8408-M)

rain sensor*

external control*

Example for Application

* optional function extension
(separate components, retrofitable!)

This  instruction  includes  descriptions  and 
connection plans of components which are not part 
of scope of supply of control panel. You can order 
these  parts  and  many  more  separately  from  your 
D+H  distributor.  Further  connecting  plans  are 
available there as well.

Safety notes:

When installing the Ventilation Control Panel (VCP-M 8408), basic safety precautions should 
always be followed to reduce risk of fire, electric shock, and personal injury.
Failure to follow these instructions could result in death or serious injury.
Operating voltage 115 VAC!
Connection has to be carried out only by an authorized electrical specialist.
Mounting of the control panel should be carried out by a D+H distributor, whose qualification and 
experience is ensured by regular in-house training.
All wiring must be installed by a qualified electrican according to e.g. National Electrical Codes, 
NFPA 70 and local codes.
For continued protection against fire, replace only with the same type and rating of fuse.
Only for indoor mounting.
Just use unchanged original D+H parts

For North America:
The International Building Codes have to be observed

For continued protection against fire,
replace only with the same type and rating of fuse.

WARNING

WARNING

fuse mains

Mulitpoint connector for 
further group plug-in unit

LED Power ON

28 - 14 AWG
max. 4.5 lb-in

22 - 12 AWG
max. 6 lb-in

mains connector

S1

F3.15A

T2.5A

S2

F3.15A

S3

F3.15A

S4

F3.15A

S5

F3.15A

Power

115 VAC

www.dh-partner.com

Ventilation control panel

GVL 8408-M

Group 1

Group 2

Group 3

Group 4

Group 5

WARNING

For continued protection against fire,

replace only with the

same type and rating of fuse.

fuse drive
group 1

DIP-switch S1

fuse drive
group 2

DIP-switch S2

fuse drive
group 3

DIP-switch S3

fuse drive
group 4

DIP-switch S4

fuse drive
group 5

DIP-switch S5

group 1-5: 22 - 12 AWG /       max. 4.5 lb-in

Summary of Contents for GVL 8408-M

Page 1: ...GVL 8408 M en Original instructions Page 2 99 824 66 1 6 03 16...

Page 2: ...recautions should always be followed to reduce risk of fire electric shock and personal injury Failure to follow these instructions could result in death or serious injury Operating voltage 115 VAC Co...

Page 3: ...tion key operation OPEN CLOSE can be free encoded Weather automatic for single groups can be switched on and off Entry for external control e g timer Possibility of connecting rain detector or wind ra...

Page 4: ...S1 S5 on motherboard of control panel and on group plug in unit if available The delivery state of all DIP switches is OFF 1 ON Drives CLOSE up to final position by single pressing on respective vent...

Page 5: ...al only LT 84 U SD LT MOT 1 2 3 Vent button e g LT 84 U SD L P Mot b Mot a 24 V DC Window Drives Mot b Mot a 4 GVL 8408 M G Az Zz X1 1 2 3 External contact for central closing e g rain detector Drive...

Page 6: ...ot b 1 2 3 4 5 6 7 GVL 8408 M LT MOT LT 84 U LT 84 U W close N open P P S VRS 10 rain 24V 2 1 3 4 5 6 R insert bridge insert bridge Connect lead directly when no automatic switch available In this cas...

Page 7: ...ation is not possible in case of bad weather if no vent button LT 84 U W available Operation Weather automatic ST OP ST OP ST OP Operation Day to day ventilation Open Close Stop Ventilation button req...

Page 8: ...Germany 22949Ammersbek 49 239 Tel 40 605 65 49 Fax 40 605 65 254 E Mail info dh partner com www dh partner com 2012 D H Mechatronic AG Ammersbek Technische nderungen vorbehalten Rights to technical mo...

Reviews: