Mounting of drive:
Because of varied possiblilties for choosing drives,
Please take mounting informations from relevant
instructions for use of the respective drive.
Moving direction of drives:
Change poles of wires of the drive supply („Mot.a"
and „Mot.b"), when moving direction is wrong.
Window drives (Accessories)
Connection – Rain sensor and Room temperature control
<
optional
>
rain
Wind
Wind
–
+
1
2
4
3
5
7
6
8
9
R
W
WRG 82
S 1/1
S 1/2
P3
P4
+G
–
Zz
Az
1
2
3
4
GVL 8408-M
L
N–
Z
A
X
Mot.a
Mot.b
1
2
3
4
5
6
7
GVL 8408-M
LT
MOT
LT 84-U +
LT 84-U-W
close
–N
open
P
P
S
VRS 10
rain
–
–
+24V
2
1
3
4
5
6
R
insert bridge!
insert bridge!
* Connect lead directly when no automatic switch available.
In this case the manual operation is out of function.
Mot.a
Mot.b
Mot.a
Mot.b
Line lengths and
cross sections
see page 4
branch box
branch box
Only if wind detector or rain detector available:
If the weather automatic is switched on via vent button LT 84-U-W
(optional), the system will automatically close in case of wind or rain.
The system will not automatically open again, if wind or rain has stopped.
Opening of the system for ventilation via vent button.
The weather automatic can be switched-off at vent button LT 84-U-W
(optional), if gap ventilation is required in case of bad weather.
Gap ventilation is not possible in case of bad weather, if no vent button
LT 84-U-W available.
Operation - Weather automatic
The input current of the
connected window drives
shall not exceed 4 Amp.
WARNING
ST OP
ST OP
ST OP
Operation - Day-to-day ventilation
Open:
Close:
Stop:
Ventilation button required.
ST
OP
Automatic
on/off
LT 84-U-W
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling. Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for
waste electrical and electronic equipment and its
implementation into national right, electrcal devices
that are no longer usable must be collected separa-
tely and disposed of in an environmentally correct
manner.
Disposal
Maintenance and cleaning
Inspection and maintenance has to be carried out
according to D+H maintenance notes. Only original
D+H spare parts may be used. Repair is to be carried
out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.