99.823.30 2.1/02/12
6/16
English
CDC 200/350
Technical data
Type
CDC 200/350
CDC 200/350 -SBD
Rated voltage
24 VDC, ±15%, 0,6 A
24 VDC, ±15%, 0,5 A
Chain type
Standard chain
Side bow chain
Nominal pressure
200 N + aprox. 20% cut-off reserve 150 N + aprox. 20% cut-off reserve
(temporary)
(temporary)
Nominal tractive force
150 N safety cut-off force
Nominal locking force
aprox. 1500 N
Runtime-OPEN
aprox. 6,7 mm/s
Runtime-CLOSED
aprox. 5 mm/s
Service life
>10.000 double strokes
Housing
Aluminium pressure die casting, -RAL 9006 (White aluminium)
Protective system
IP 50
Temp.range
-5 ... +75°C
Fire stability
30 min / 300°C
Connection
2,5 m silicone cable
Closing edge protection = deactivated
Locking relief = activated (retraction lift max. 0.2 mm)
CDC-PC xxxx-T01
* TMS line must
be disconnected!
CDC-PC xxxx-T01
*
*
Tandem Safety Function
For the operation of 2-3 drives on separate vents the
tandem safety function (TMS) may not be used! For
this the TMS line (yellow) of the connection cable
CDC-PC xxxx of the drives is disconnected, so that
the remaining drive(s) are still opened in case of fire
in the event of a failure, under voltage or overload
cut-out.
Whenever two drives are operated on a single sash,
the tandem safety function can be used. This
function connects the cut-offs of the two drives in
such a way that if one drive is cut off due to overload,
the other drive will also be cut off.
In this case active jamming protection may not
activated!