A synchron-group DXD-BSY+ (-HS) can be count up
to 4 drives, which communicate by a bus. Each drive
has it’s own adress. This adress is configurable with
SCS.
The last drive of a synchron-group is the master,
which controls the other drives, the slaves. Different
forces between the drives of a group will balanced
with intelligent force- and position control. In case of
malfunction respective cutoff of a drive, all drives will
shut down from the master-drive.
Functional description
Maintenance and cleaning
Inspection and maintenance has to be carried out
according to D+H maintenance notes. Only original
D+H spare parts may be used. Repair is to be carried
out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
Declaration of Conformity
Electrical devices, accessories and packaging
should be sorted for environmental-friendly recycling.
Only for EC countries:
Do not dispose electrical
devices into household waste!
According the European Guideline
2012/19/EU for waste electrical and
electronic equipment and its implemen-
tation into national right, electrcal devices that are no
longer usable must be collected separately and
disposed of in an environmentally correct manner.
Disposal
Guarantee
You will get
2 years guarantee
for all D+H products
from date of verified handing over of the system up to
maximal 3 years after date of delivery, when
mounting and starting has been carried out by
an
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.
Visual inspection:
Only one master-drive allowed.
The master has, according to common drives,
the last adress.
The adress is sticked on the drive. Slaves are
nubered downwards.
Example: In a group, composed of 3 drives,
there is a master 3, a slave 2 and a slave 1drive.
Attention: only applies by factory set. as soon as
the drives were reprogramized with SCS
he factory set adressing does not apply any
longer.
Wiring:
Is the group wired correctly?
Therefore look connection diagrams.
Null balance:
It should be null balanced.
Software SCS or the special magnet
MAG 502 is required.
Call D+H Service:
Drives must be configured.
Software SCS is required.
Trouble shooting
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Thomas Kern
Maik Schmees
Member of the Board
Authorized signatory, Technical Director
12.10.2015
In case of stroke shortening in one drive
group (2 - 4 drives), all magnets must be
shifted always to the same proportion
(tolerance ±2,5 mm (0.1") for all drives
together) !
min. 60 mm / 2.4"
X
CLOSED
-magnet
N
S
min. 5 mm / 0.2"
X
OPEN
-magnet
N
S
Stroke shortening
Shift slotted pins and magnets into desired position,
using a suitable tool e.g. a screw driver for stroke
shortening. Observe minimum distances (60 mm
and 5 mm / 2.4" and 0.2")!
After shifting of the “CLOSED-magnet” let the
drive run closed.
In this process, it will be automatically set on a
new zero point!
View X
slotted pin
slotted pin
2 magnets
Shifting of drive cable
Disconnect drive from electric voltage!