background image

2/8

3/8

English

English

DXD-BSY+ (-HS)

DXD-BSY+ (-HS)

99.831.05 1.1/10/15

99.831.05 1.1/10/15

! IMPORTANT ! Safety Notes

1.  Mounting of the drive should be carried out by a D+H distributor, whose qualification and experience is 

ensured by regular in-house training.

2.  All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3.  For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4.  Observe enclosed red safety slip!
5.  Danger of violent pressure in handaccessible area.
6.  The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7.  A suitable field wiring means should be provided in the end use application.
8.  The mounting and routing of external wiring should be determined in the end product.
9.  The mounting of each unit shall be evaluated in the end use.
10. The suitability of the leads for field wiring should be determined in the end-use application.
11. The drive must be mounted a min of 8 feet above the floor or any access level.
12. The drives were not evaluated for entrapment protection since they are to be installed at least 8 feet above 

the floor. Where entrapment is a consideration, the need for additional tests and evaluation should be 
determined during the end product investigation.

13. The drive shall be connected to a Class 2 power supply.

For North America:
14. The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.

Intended use

-   Rack  and  pinion  drive  for  electric  opening  and 

closing of heavy windows and flaps in the facade 
and roof area

-   Operating voltage 24 V DC
-   Usheable for smoke ventilation, D+H Euro-SHEV 

according  to  DIN  EN  12101-2  as  well  as  daily 
natural ventilation

-   Only for inside mounting

Performance features

-   Micro processor controlled  synchro electronics

   BSY + for a precise     synchronous run of  up to
   8 drives

-   Individually programmable (via software SCS)
-   SHEV-high speed function (fast-running   

   feature in OPEN-direction)

-   Protectionsystem for the main  closing edge
-   Especially silent in ventilation operation 

   because of reduced motor speed

Drive  unit  with  2,5  m  (97.5")  silicone  cable. 
Dependent on the type of window, different bracket 
sets are available separately.

Scope of supply

Mounting informations

-   Swivel radius of the drive must go free over entire

   range of stroke.  Otherwise, the toothed rack and
   the suspension can be damaged

-   The drive set will be full configured by factory

   The drives must be reconfigured in case of
   alterations (e.g. removing of drives from existing
   set or integrating a new drive) with SCS

-   Use only drives with the same force
-   Ensure evenly load distribution on all the drives

Type 

DXD1500-BSY+ 

DXD 1500-BSY+ HS  DXD 3000-BSY+ 

DXD 3000-BSY+

  

HS

 

Power supply 

24 V DC, ±15 % 

24 V DC, ±15 % 

24 V DC, ±15 % 

24 V DC, ±15 %

Nominal current  

1,4 A   

 

2,5 A    

 

2,5 A    

 

4,0 A 

Nominal force 

1500 N 

 

1500 N 

 

3000 N 

 

3000 N

 

Nominal locking force 

 

1100 N 

2200 N

Lifetime 

>10 000 double strokes

Duty cycle 

30 % (with cycle time 10 minutes)

Housing 

anodized aluminium / polycarbonate

Ingress protection 

IP 64

Temperature range 

-5 ... +75 °C (23 ... 167 °F)

Fire stability 

30 min / 300 °C (572 °F)

Nominal stroke length* 

see type plate

Additional functions * 

closing edge protection activated (3 stroke repeatings)

 

* programmable with software SCS

Technical data

All forces
+ approx. 20 %
switch-off reserve (temporary)

Normal  operation

  =

SHEV- fast running =

I

III

100 mm

4"

23 mm

0.9"

7,1 mm/s (0.28"/s)

5 mm/s 

(0.2"/s)

5 mm/s

(0.2"/s)

~8 mm/s (~0.31"/s) / ~17 mm/s (~0.67"/s)

DXD 3000-BSY+ HS ~ 1

1 mm/s (~0,43'‘/s)

II

Closure Ranges

OPEN

Forces

CR 

III

CR 

II

CR

 I

1500 N / 337 lbf

1000 N / 224,8 lbf
1000 N / 224,8 lbf

800 N / 179,8 lbf

3000 N / 674,4 lbf
2000 N / 449,6 lbf
1600 N / 359.7 lbf

800 N / 179.8 lbf

DXD 1500-BSY+ (-HS) DXD 3000-BSY+ (-HS)

CLOSE

~7,1 mm/s / ~0.28"/s

Running speed and forces

DXD 1500-BSY+ (-HS)

max. Load (N / lbf)

Stroke (mm / Inch)

0

500 mm

19.7"

1000 mm

39.4"

1500 mm

59"

2000 mm

78.8"

2500 mm

98.5"

0

500N/112,4 lbf

1000N/224,8 lbf

1500N/337,2 lbf

2000N/449,6 lbf

2500N/562 lbf

durable

temporary

DXD 3000-BSY+ (-HS)

0

500 mm

19.7"

1000 mm

39.4"

1500 mm

59"

2000 mm

78.8"

2500 mm

98.5"

0

500N/112,4 lbf

1000N/224,8 lbf

1500N/337,2 lbf

2000N/449,6 lbf

2500N/562 lbf

durable

temporary

3000N/674,5 lbf

max. Load (N / lbf)

Stroke (mm / Inch)

Pressure load diagram

At  the  DXD  1500-BSY+  (-HS)  loads  of  more  than 
1000  N  (224,8  lbf)  up  to  1500  N  (337,2  lbf)  are 
transient admissible only (e.g. prior to snow removal 
or in case of wind loads). These may occur up to a 
stroke of 1750 mm (69").

At  the  DXD  3000-BSY+  (-HS)  loads  of  more  than 
2000  N  (449,6  lbf)  up  to  3000  N  (674,4  lbf)  are 
transient admissible only (e.g. prior to snow removal 
or in case of wind loads). These may occur up to a 
stroke of 1500 mm (59").

Maximum pressure load of the toothed rack is not automatically identical with maximum pressure force of the drive!

Summary of Contents for 150-BSY+

Page 1: ...99 831 05 1 1 10 15 en Original instructions Page 2 Please order bracket sets separately Standard version without tube Version with tube E 222052 C US DXD 150 BSY HS DXD 300 BSY HS ...

Page 2: ...rved Intended use Rack and pinion drive for electric opening and closing of heavy windows and flaps in the facade and roof area Operating voltage 24 V DC Usheable for smoke ventilation D H Euro SHEV according to DIN EN 12101 2 as well as daily natural ventilation Only for inside mounting Performance features Microprocessor controlled synchro electronics BSY for a precise synchronous run of up to 8...

Page 3: ...Nominal force 1500 N 1500 N 3000 N 3000 N Nominal locking force 1100 N 2200 N Lifetime 10 000 double strokes Duty cycle 30 with cycle time 10 minutes Housing anodized aluminium polycarbonate Ingress protection IP64 Temperature range 5 75 C 23 167 F Fire stability 30 min 300 C 572 F Nominal stroke length see type plate Additional functions closing edge protection activated 3 stroke repeatings progr...

Page 4: ... n 5 m m 0 2 X OPEN magnet N S Stroke shortening Shift slotted pins and magnets into desired position using a suitable tool e g a screw driver for stroke shortening Observe minimum distances 60 mm and 5 mm 2 4 and 0 2 After shifting of the CLOSED magnet let the drive run closed In this process it will be automatically set on a new zero point View X slotted pin slotted pin 2 magnets Shifting of dri...

Page 5: ...rately and disposed of in an environmentally correct manner Disposal Guarantee You will get 2 years guarantee for all D H products from date of verified handing over of the system up to maximal 3 years after date of delivery when mounting and starting has been carried out by an authorized D H distributor D H guarantee is expired with connection of D H components with external systems or with mixin...

Page 6: ... Data A GN Data B GR SZ GN SZ PK SA YE SA WH n c BN n c OR n c Standard WH Mot a BN Mot b OR HS YE Data A GN Data B second connecting cable Connection 1 2 3 4 5 L 6 N 7 Z A E X a b LT Group Monitoring Mot a Mot b MOT BK BK OR 2x47kW En dm od ul Te rm ina l mo du le Mo du le ter mi na l EM 47 K WH BN OR YE GN Mot a Mot b HS Data a Data b DXD BSY Master 1 Junction box WH white BN brown OG orange YE ...

Page 7: ...e instructions for use of control panel Connection 1 2 3 4 5 L 6 N 7 Z A E X a b LT Group Monitoring Mot a Mot b MOT BK BK OR 2x47kW En dm od ul Te rm ina l mo du le Mo du le ter mi na l EM 47 K WH WH BN BN OR OR YE YE GN GN Mot a Mot a Mot b Mot b HS HS Data a Data a Data b Data b Slave 1 Master 2 Junction box to control panel DXD BSY DXD BSY Normal mode SHEV fast running High Speed High Speed Hi...

Page 8: ... 32 Germany 22949Ammersbek 49 239 Tel 40 605 65 49 Fax 40 605 65 254 E Mail info dh partner com www dh partner com 2012 D H Mechatronic AG Ammersbek Rights to technical modifications reserved 100 Recycled paper All sizes in millimetre inches without tube 187 mm 7 4 Stroke 206 mm 8 11 Stroke 226 mm 8 9 182 7 2 with tube Stroke 213 5 mm 8 4 Stroke 240 5 mm 9 47 ...