2/8
3/8
English
English
DXD-BSY+ (-HS)
DXD-BSY+ (-HS)
99.831.05 1.1/10/15
99.831.05 1.1/10/15
! IMPORTANT ! Safety Notes
1. Mounting of the drive should be carried out by a D+H distributor, whose qualification and experience is
ensured by regular in-house training.
2. All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3. For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4. Observe enclosed red safety slip!
5. Danger of violent pressure in handaccessible area.
6. The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7. A suitable field wiring means should be provided in the end use application.
8. The mounting and routing of external wiring should be determined in the end product.
9. The mounting of each unit shall be evaluated in the end use.
10. The suitability of the leads for field wiring should be determined in the end-use application.
11. The drive must be mounted a min of 8 feet above the floor or any access level.
12. The drives were not evaluated for entrapment protection since they are to be installed at least 8 feet above
the floor. Where entrapment is a consideration, the need for additional tests and evaluation should be
determined during the end product investigation.
13. The drive shall be connected to a Class 2 power supply.
For North America:
14. The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.
Intended use
- Rack and pinion drive for electric opening and
closing of heavy windows and flaps in the facade
and roof area
- Operating voltage 24 V DC
- Usheable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
Performance features
- Micro processor controlled synchro electronics
BSY + for a precise synchronous run of up to
8 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protectionsystem for the main closing edge
- Especially silent in ventilation operation
because of reduced motor speed
Drive unit with 2,5 m (97.5") silicone cable.
Dependent on the type of window, different bracket
sets are available separately.
Scope of supply
Mounting informations
- Swivel radius of the drive must go free over entire
range of stroke. Otherwise, the toothed rack and
the suspension can be damaged
- The drive set will be full configured by factory
The drives must be reconfigured in case of
alterations (e.g. removing of drives from existing
set or integrating a new drive) with SCS
- Use only drives with the same force
- Ensure evenly load distribution on all the drives
Type
DXD1500-BSY+
DXD 1500-BSY+ HS DXD 3000-BSY+
DXD 3000-BSY+
HS
Power supply
24 V DC, ±15 %
24 V DC, ±15 %
24 V DC, ±15 %
24 V DC, ±15 %
Nominal current
1,4 A
2,5 A
2,5 A
4,0 A
Nominal force
1500 N
1500 N
3000 N
3000 N
Nominal locking force
1100 N
2200 N
Lifetime
>10 000 double strokes
Duty cycle
30 % (with cycle time 10 minutes)
Housing
anodized aluminium / polycarbonate
Ingress protection
IP 64
Temperature range
-5 ... +75 °C (23 ... 167 °F)
Fire stability
30 min / 300 °C (572 °F)
Nominal stroke length*
see type plate
Additional functions *
closing edge protection activated (3 stroke repeatings)
* programmable with software SCS
Technical data
All forces
+ approx. 20 %
switch-off reserve (temporary)
Normal operation
=
SHEV- fast running =
I
III
100 mm
4"
23 mm
0.9"
7,1 mm/s (0.28"/s)
5 mm/s
(0.2"/s)
5 mm/s
(0.2"/s)
~8 mm/s (~0.31"/s) / ~17 mm/s (~0.67"/s)
DXD 3000-BSY+ HS ~ 1
1 mm/s (~0,43'‘/s)
II
Closure Ranges
OPEN
Forces
CR
III
CR
II
CR
I
1500 N / 337 lbf
1000 N / 224,8 lbf
1000 N / 224,8 lbf
800 N / 179,8 lbf
3000 N / 674,4 lbf
2000 N / 449,6 lbf
1600 N / 359.7 lbf
800 N / 179.8 lbf
DXD 1500-BSY+ (-HS) DXD 3000-BSY+ (-HS)
CLOSE
~7,1 mm/s / ~0.28"/s
Running speed and forces
DXD 1500-BSY+ (-HS)
max. Load (N / lbf)
Stroke (mm / Inch)
0
500 mm
19.7"
1000 mm
39.4"
1500 mm
59"
2000 mm
78.8"
2500 mm
98.5"
0
500N/112,4 lbf
1000N/224,8 lbf
1500N/337,2 lbf
2000N/449,6 lbf
2500N/562 lbf
durable
temporary
DXD 3000-BSY+ (-HS)
0
500 mm
19.7"
1000 mm
39.4"
1500 mm
59"
2000 mm
78.8"
2500 mm
98.5"
0
500N/112,4 lbf
1000N/224,8 lbf
1500N/337,2 lbf
2000N/449,6 lbf
2500N/562 lbf
durable
temporary
3000N/674,5 lbf
max. Load (N / lbf)
Stroke (mm / Inch)
Pressure load diagram
At the DXD 1500-BSY+ (-HS) loads of more than
1000 N (224,8 lbf) up to 1500 N (337,2 lbf) are
transient admissible only (e.g. prior to snow removal
or in case of wind loads). These may occur up to a
stroke of 1750 mm (69").
At the DXD 3000-BSY+ (-HS) loads of more than
2000 N (449,6 lbf) up to 3000 N (674,4 lbf) are
transient admissible only (e.g. prior to snow removal
or in case of wind loads). These may occur up to a
stroke of 1500 mm (59").
Maximum pressure load of the toothed rack is not automatically identical with maximum pressure force of the drive!