TECHNICAL SPECIFICATIONS
1
3
Model
OLS1000E/EXL
OLS1500E/EXL
OLS2000E/EXL
OLS3000E/EXL
Configuration
Capacity (VA)
1000VA
1500VA
2000VA
3000VA
Capacity (Watts)
800W
1200W
1600W
2400W
Form Factor
Tower
Energy-saving Technology
Yes, ECO Mode
Efficiency
≧
95%
Input
Input Voltage Range
110~130Vac
5% for 1000 / 1500 / 2000 VA model
110~140Vac
5%
for 3000 VA only
@ 0~50% Load
5%
120~140Vac
5%
for 1000 / 1500 / 2000 VA model
140~160Vac
5%
for 3000 VA only
@ 0~60% Load
5%
140~160Vac
5%
for 1000 / 1500 / 2000 VA model
160~190Vac
5%
for 3000 VA only
@ 0~80% Load
5%
160~300Vac
5%
for 1000 / 1500 / 2000 VA model
190~300Vac
5%
for 3000 VA only
@ 0~100% Load
5%
Input Frequency Range
40~70Hz
Input Power Factor
0.98
Cold Start
Yes
Output
Output Waveform
Pure Sine Wave
Output Voltage
208, 220, 230, 240Vac ±1%
Output Frequency
50 / 60Hz (Auto-Sensing or Configurable) ±0. 5Hz
Transfer Time (Typically)
0ms
Rated Power Factor
0.8
Harmonic Distortion
THD < 3% at Linear Load, < 5% at Non-linear Load @ Nominal Input
Crest Factor
3 : 1
ECO Mode Voltage
Regulation
±10%, ±15% (Configurable)
UPS Outlets
(4) IEC C13
(2+2) IEC C13
(1) Terminal Block
(2+2) IEC C13
(1) IEC C19
(1) Terminal Block
Protection
Surge Protection
IEC 61000-4-5 Level 4
Phone / Network Protection
RJ11/RJ45 (One In/One Out)
Overload Protection
Line Mode
:
105~110%
Overload warning only (No shutdown)
,
110~120% Warning, transfer to bypass after 60s
>120% Transfer to bypass immediately
Battery Mode
:
105~110%
Overload warning only (No shutdown)
,
110~120% Warning, shutdown after 10s
>120% Shutdown immediately
Short Circuit Protection
UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
Battery
Specifications
(3) 12V/7AH
(3) 12V/8.5AH
(6) 12V/7AH
(6) 12V/8.5AH
For -EXL Models, NO Battery Inside.
Recharge Time (Typically)
4 Hours (inside batteries)
Sealed, Maintenance Free
Yes
Status Indicators
LCD Screen
Graphic LCD
Audible Alarms
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery, Bypass Mode
Charger Failure /Over Charged,
Fan failure,
EPO active
Environment
Operating Temperature
32
℉
to 104
℉
( 0
℃
to 40
℃
)
Operating Relative Humidity
20 to 90% Non-Condensing
Management
On-Device Features
Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
Connectivity Ports
(1) Serial Port (RS232), (1) USB Port,
SNMP/HTTP Capable
(1) Expansion Port (With optional RMCARD 302)