BASIC OPERATION

 

 

 

9

 

 

REPLACE: 

This  icon  appears  if  the  batteries  need  to  be 

replaced. 

 

 

Event ID Descriptions

 

Event ID 

Description of Cause 

Bus Start Fail: 

DC-DC converter or bus sensing circuit failed.

 

Bus Volt High:

 DC-DC converter failed. 

Bus Volt Low: 

DC-DC converter failed. 

Bus Unbalanced: 

DC-DC converter failed. 

INV Start Fail: 

Inverter circuit failed. 

INV  Volt  High:

  Inverter  circuit  or  output  voltage  sensing 

circuit failed. 

INV Volt Low:

 The load may be too heavy or inverter circuit 

failed. 

INV Short: 

The inverter circuit failed. 

Bat Volt  High:

  The  external  battery  module  connection  is 

wrong, or the charger failed. 

10 

Bat Volt Low: 

Batteries failed. 

11 

Over  Temperature:

  High  ambient  temperature,  or  the 

ventilation hole has been covered. 

12 

Over Load: 

UPS is overloaded. 

54 

High  Temperature:

  High  ambient  temperature,  or  the 

ventilation hole  has  been  covered.  This is shown  only  when 
start up UPS. 

 

55 

Bat Low: 

Battery voltage is too low to DC start UPS.

 

57 

EPO Off:

 Missing the EPO connection

 

58 

Fan Fail: 

The ventilation hole has been covered, or the fans 

can’t work.

 

 

BUTTON OPERATION

 

Button 

Operation Description 

ON 

Press this button to turn on UPS.

 

OFF 

Press this button to turn off UPS.* 

ENTER/

▲ 

Press this button to scroll up in the LCD menu. 
Press  this  button  simultaneously  for  5  seconds  to  disable  or 
enable the alarm system while in battery mode. 
Press this button simultaneously for 5 seconds to enter UPS 
self-testing while in AC mode, ECO mode, or converter mode. 
In  setting  mode,  press  this  button  to  confirm  selection,  or 
press this button for long time to exit setting mode and saving 
changes. 

ESC/

▼ 

Press this button to scroll down in the LCD menu. 
Press this button for long time to get into setting mode 
In setting mode, press this button to display next selection, or 
press  this  button  for  long  time  to  exit  setting  mode  without 
saving changes. 

ENTER/

▲ + ESC/▼ 

Switch  to  bypass  mode:  When  the  main  power  is  normal, 
press  these  two  buttons  simultaneously  for  5  seconds,  then 
UPS will enter to bypass mode. 

 

*) If utility power is connected

UPS will keep charging but cut off output. 

 

 

Summary of Contents for OLS1000E

Page 1: ...User s Manual OLS1000E EXL OLS1500E EXL OLS2000E EXL OLS3000E EXL CyberPower Systems Inc www cpsww com K01 C000036 00 ...

Page 2: ...rsonnel may carry out installations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cau...

Page 3: ...Copyright 2012 CyberPower Systems Inc UNPACKING 2 UPS User s manual Phone line USB communication cable Input power cord Output power cords x2pcs PowerPanel Business Edition software CD ...

Page 4: ...quipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to the technical specifications 6 This UPS is equipped with an auto charge feature When the UPS is plugged into an AC outlet the battery will automatically charge even when the unit is switched off 7 To maintain an optimal battery charge leave the UPS plugged into an AC outlet at all times ...

Page 5: ...us programmable parameters 7 USB port This is a connectivity port which allows communication and control between the UPS and the connected computer It is recommended to install the PowerPanel Business Edition Agent software on the PC Server connected with the USB cord 8 Surge Protected Communication Ports RJ 45 RJ 11 These ports are used to protect standard RJ 45 RJ 11 based products ADSL LAN Phon...

Page 6: ...o daisy chain the next Battery module Remove the connector cover for access 2 On board Replaceable Fuse Cover Replaceable fuse is accessible from the rear panel It must be done by qualified personnel 3 Output Connector Use this output Connector to connect the Battery module to the Power module or to the next Battery module BPSE36V45A BPSE72V45A ...

Page 7: ...MODULE Step 1 Loosen the two screws to remove the battery cable retention bracket of the power module Step 2 Use the battery cable of the Battery module to connect the Battery module to the Power module Step 3 Rotate the battery cable retention bracket and tighten the two screws to fix battery cable ...

Page 8: ...ery module to the Power module using battery cable Step 2 Loosen the two screws to remove the battery cable retention bracket of the 1 st battery module Step 3 Use the battery cable to connect the 2 nd Battery module to the 1 st Battery module Step 4 Rotate the battery cable retention bracket and tighten the two screws to fix battery cable ...

Page 9: ...capacity This meter displays the approximate charge level in 20 increments of the UPS s internal battery During a blackout or severe brownout the UPS switches to battery power the BATTERY icon appears and the charge level decreases MUTE This icon appears whenever the UPS is in silent mode The alarm does not beep during silent mode until the battery reaches low capacity SCHEDULE Users can setup the...

Page 10: ...tery voltage is too low to DC start UPS 57 EPO Off Missing the EPO connection 58 Fan Fail The ventilation hole has been covered or the fans can t work BUTTON OPERATION Button Operation Description ON Press this button to turn on UPS OFF Press this button to turn off UPS ENTER Press this button to scroll up in the LCD menu Press this button simultaneously for 5 seconds to disable or enable the alar...

Page 11: ...Displays the Estimated Percentage of Battery Capacity ESTIMATED RUN TIME XX X Min Hr Displays the Estimated Run Time with battery TIME TO SHUT DOWN XX X Min Hr Displays the Time Delay to Shutdown UPS TIME TO TURN ON XX X Min Hr Displays the Time Delay to Restart UPS LCD SETTINGS CONFIGURATION There are 7 UPS settings that can be configured by the user 1 Press the ESC button to activate the setting...

Page 12: ...rn on off by the ROO port If ROO port is disconnected UPS will be turned off If ROO port is connected UPS will be turned on when the utility is normal UPS cannot detect the numbers of external battery automatically so manual input from user is necessary Note The manual settings programming mode can ONLY be invoked while UPS is in Bypass mode or Standby mode To make UPS on Standby mode connect util...

Page 13: ...chains wrist watches and rings CAUTION Do not open or mutilate the batteries Electrolyte fluid is harmful to the skin eyes and may be toxic CAUTION To avoid electric shock turn off and unplug the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please ...

Page 14: ...5 Configurable UPS Outlets 4 IEC C13 2 2 IEC C13 1 Terminal Block 2 2 IEC C13 1 IEC C19 1 Terminal Block Protection Surge Protection IEC 61000 4 5 Level 4 Phone Network Protection RJ11 RJ45 One In One Out Overload Protection Line Mode 105 110 Overload warning only No shutdown 110 120 Warning transfer to bypass after 60s 120 Transfer to bypass immediately Battery Mode 105 110 Overload warning only ...

Page 15: ...ment Software PowerPanel Business Edition Physical Dimensions D W H 15 51 x 5 94 x 8 86in 394 151 225 mm D W H 16 38 x 7 72 x 13 28in 416 196 337 mm Net Weight 28 9 17 0lbs 13 1 7 7Kg 33 7 17 2lbs 15 3 7 8Kg 52 5 26 9lbs 23 8 12 2Kg 62 2 27 8lbs 28 2 12 6Kg Safety Conformance Approvals CE ...

Page 16: ...down UPS and turn off AC input 2 Contact CyberPower for repair EPO OFF Missing the EPO connection Check the EPO connection Fault Over Temperature High ambient temperature 1 Shut down UPS Restart UPS to Check the fan for operation and if the ventilation hole has been covered 2 Contact CyberPower for repair Output Short Output short circuit 1 Shut down UPS 2 Your attached equipment may have problems...

Reviews: