Copyright © 2014 CyberPower Systems, Inc.
HARDWIRING THE INPUT/ OUTPUT TERMINALS
6
TERMINAL BLOCK IDENTIFICATION
ISOLATION TERMINAL BLOCK CONFIGURATION
Input Voltage
AC Output Connection
Output Voltage
L1 → L2 = 200Vac
L1
→ N
←
L2
100Vac
→ 0
←
100Vac
L1
→ L2
200Vac
L1 → L2 = 220Vac
L1
→ N
←
L2
110Vac
→ 0
←
110Vac
L1
→ L2
220Vac
L1 → L2 = 230Vac
L1
→ N
←
L2
115Vac
→ 0
←
115Vac
L1
→ L2
230Vac
Input Voltage
AC Output Connection
Output Voltage
L1T
→ L2 = 208Vac
L1
→ N
←
L2
120Vac
→ 0
←
120Vac
L1
→ L2
240Vac
L1
→ L2T
208Vac
Input Voltage
AC Output Connection
Output Voltage
L1 → L2 = 240Vac
L1
→ N
←
L2
120Vac
→ 0
←
120Vac
L1
→ L2
240Vac
L1
→ L2T
208Vac