HARDWARE INSTALLATION

 

 

 

2

 

 

 

HARDWARE INSTALLATION 

These versatile Step-Down Transformers can be mounted in a rackmount 
or  vertical  tower  orientation.  This  versatility  is  especially  important  to 
growing organizations with changing needs that value having the option 
to position a Step-Down Transformer on a floor or in a rackmount system. 
Please follow the instructions below for the respective mounting methods.

 

 

SAFETY PRECAUTIONS

 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  only  use  the 

supplied hardware to attach the mounting brackets.

 

 

RACKMOUNT INSTALLATION 

Step 1: Rackmount ears installation 

Attach the two rackmount ears to the Step-Down Transformer using the 
provided screws M5X8L*8pcs. 

 

Step 2: Rackmount rail Installation 

The  rails  adjust  to  mount  in  48-cm  (19-inch)  panel  racks  from  52  to 
91.5cm (20.5 to 36 inches) deep. Select the proper holes in the rack for 
positioning the Step-Down Transformer in the  rack. The 2U Step-Down 
Transformer takes up position 1 through position 6. The 3U Step-Down 
Transformer takes up position 1 through position 9.

 

 

Step 3: Adjust rackmount rails to fit your rack 

Attach the rackmount rail to your rack with two M5X12L screws and two 
plastic washers at the front of the rack. (Located in position 1 & position 6) 
Do not tighten the screws. Adjust the rail size on the rail assembly of your 
rack. Secure the rail to the rear of the rack with two M5X12L screws and 
two plastic washers. Tighten all screws at the front and rear of the rail. 

 

Place the Step-Down Transformer on a flat stable surface with the front of 
the  unit  facing  toward  you.  Secure  the  Step-Down  Transformer  to  your 
rack with four M5X12L screws at the front of the rack. The 2U Step-Down 
Transformer takes up position  2 through position 5. The 3U Step-Down 
Transformer takes up position 2 through position 8.

 

 

CAUTION!   

The  Step-Down  Transformer  must  be  installed  above  the 

power module.

 

Summary of Contents for OL10KRT2UTFHWIORTAA

Page 1: ...Down Transformer OL6KRT2UTFHWIOTAA OL10KRT2UTFHWIOTAA OL6KRT2UTFHWIORTAA OL10KRT2UTFHWIORTAA CyberPower Systems USA Inc 4241 12th Avenue East Suite 400 Shakopee MN 55379 Phone 877 297 6937 Fax 952 403...

Page 2: ...des the UPS and connected equipment from any outside utility line fluctuations or interference 2U Step Down and Isolation Transformer User s manual Registration card Rackmount left rail Rackmount righ...

Page 3: ...hes deep Select the proper holes in the rack for positioning the Step Down Transformer in the rack The 2U Step Down Transformer takes up position 1 through position 6 The 3U Step Down Transformer take...

Page 4: ...odule Step 3 Attach dust covers Insert dust covers into the rackmount ear screw holes that are not being used SAFETY PRECAUTIONS CAUTION Installation environment should be in a temperature and humidit...

Page 5: ...eck wiring dimensions with the following table Step Down and Isolation Transformers with hardwire Wiring AWG Wiring mm 2 OL6KRT2UTFHWIOTAA OL6KRT2UTFHWIORTAA 10 AWG 5 5 mm 2 OL10KRT2UTFHWIOTAA OL10KRT...

Page 6: ...iguration Insert the input output cables through the appropriate cable gland Hardwire the input output terminals as shown in the following terminal block identification and configuration table Step 4...

Page 7: ...Voltage L1 L2 200Vac L1 N L2 100Vac 0 100Vac L1 L2 200Vac L1 L2 220Vac L1 N L2 110Vac 0 110Vac L1 L2 220Vac L1 L2 230Vac L1 N L2 115Vac 0 115Vac L1 L2 230Vac Input Voltage AC Output Connection Output...

Page 8: ...pyright 2014 CyberPower Systems Inc HARDWIRING THE INPUT OUTPUT TERMINALS 7 POWER CABLE CONNECTION OL6000RT3UTFTAA OL6000RT3UPDUTFTAA OL8000RT3UTFTAA OL10000RT3UTFTAA OL8000RT3UPDUTF OL10000RT3UPDUTFT...

Page 9: ...output terminal block 3 Battery Backup Surge Protected Outlets 120Vac Provides battery backup and surge protection They ensure power is provided to connected equipment over a period of time during a p...

Page 10: ...OL6KRT2UTFHWIOR TAA OL6KRT2UTFHWIO TAA OL10KRT2UTFHWIOR TAA OL10KRT2UTFHWIO TAA Configuration Maximum Output Power VA 6000VA 10000VA Maximum Output Power W 6000W 10000W Form Factor Rackmount Tower In...

Page 11: ...ber the Purchase Date and each item of Connected Equipment 2 Email us at tech cpsww com or Call us at 877 297 6937 3 If your product requires warranty service you must provide a copy of your dated pur...

Page 12: ...1 Loss of or damage to data records or software or the restoration of data or records or the reinstallation of software 2 Damage from causes other than AC Power Line Transients spikes or surges on pro...

Page 13: ...interference in which case the user will be required to correct the interference at his own expense Shielded signal cables must be used with this product to ensure compliance with the Class A FCC lim...

Reviews: