ELECTRICAL INSTALLATION CONT.
(1)OL5KRTHD/OL6KRTHD models :
Set up communication Signal input Manual Bypass Save Change?
(2)OL6KRT/OL8KRT/OL10KRT/OL6KRTF/OL8KRTF/OL10KRTF models :
Configure Signal input Manual Bypass Save ?
[NOTE] If not follow the step to set the UPS Signal input to Manual bypass function enable and
correctly connected MBP detection cable, it will be caused UPS damage.
5. Press the UPS
“ON/OFF”
power button for 3 seconds to turn to start the UPS.
6. UPS will be automatically turning to Bypass mode
If not, please check MBP detection cable is correctly connected.
7. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user
manual).
8. Verify that the
“Normal”
green light of the MBP goes On, indicating that the UPS output power is
available on the MBP.
Important !
do not continue to next step if the
“Normal”
green light of the MBP is still Off (the
load will be lost).
9. Release two screws by screw driver and open the Cover of MBP switch and the MBP manual
Bypass switch is to the
“Bypass”
position now.
10. Set the MBP manual Bypass switch to the
“UPS”
position, indicating that the load is now powered
by the UPS.
11. Replace the Cover of MBP switch and tighten 2 screws by screw driver, UPS will be automatically
turning to Line mode.
12. Check that the UPS is in Online mode by checking UPS display panel (refer to the UPS user
manual)
the load is now protected by the UPS.
RETURN TO NORMAL OPERATION CONT. :
9