18
10) It is requested to use the accessorial terminal splices which can be compacted
on the wires tightly, to ensure the connection between the wires and the
terminal block is reliable.
Fig.6-2 Input and output terminal block wiring diagram
Important notes:
If the Power module is used in single mode, the output must be connected to sL and
sN.
If the Power module is used in parallel mode, the output must be connected to pL
and pN.
11) Install an output breaker between the output terminal of Power module and the
load, and the breaker should with leakage current protective function if
necessary.
12) Turn off all the loads first before connecting the load with the Power module,
then perform the connection and finally turn on the loads one by one.
13) After completing the installation, please check the wires to make sure all were
connected correctly and tightly.
14) Suggest charging the batteries for 8 hours before use. After Installation, turn
on the mains power switch and turn the input breaker in the
"
ON
"
position, the
Power module will charge the batteries automatically. It can also use the
Power module immediately without charging the batteries, but the backup time
may be less than the standard value.
15) If it is necessary to connect the inductance load such as a monitor or a laser
Input Ground
Input N
Input L
B
Battery -
Battery Ground
Parallel Mode Output L
Output Ground
Single Mode Output L
Parallel Mode Output N
Single Mode Output N