IMPORTANT SAFETY INSTRUCTIONS

 

 

1

 

 

 

This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual 
thoroughly before attempting to unpack, install, or operate the UPS. 

 

CAUTION!   

The  UPS  must  be  connected  to  a  grounded  AC  power 

outlet with fuse or circuit breaker protection. DO NOT plug the UPS into 
an outlet that is not grounded. If you need to power-drain this equipment, 
turn off and unplug the unit.

 

CAUTION!   

The  battery  can  power  hazardous  components  inside  the 

unit, even when the AC input power is disconnected.

 

CAUTION!   

The UPS should be placed near the connected equipment 

and easily accessible. 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a 

temperature  and  humidity  controlled  indoor  area,  free  of  conductive 
contaminants. (Please see specifications for acceptable temperature and 
humidity range).

 

CAUTION!    (No  User  Serviceable  Parts):

  Risk  of  electric  shock,  do 

not  remove  cover.  No  user  serviceable  parts  inside.  Refer  servicing  to 
qualified service personnel.

 

CAUTION!    (Non-Isolated  Battery  Supply): 

Risk  of  electric  shock, 

battery circuit is not isolated from AC power source; hazardous voltage 
may exist between battery terminals and ground. Test before touching.

 

CAUTION!   

To  reduce  the  risk  of  fire,  connect  the  UPS  to  a  branch 

circuit  with  10  amperes  (OL1000  /  OL1500  /  OL2000)  /  16  amperes 
(OL3000)  maximum  over-current  protection  in  accordance  to  CE 
requirement.

 

CAUTION!   

The AC outlet where the UPS is connected should be close 

to the unit and easily accessible. 

CAUTION!   

Please use only VDE-tested, CE-marked mains cable, (e.g. 

the mains cable of your equipment), to connect the UPS to the AC outlet.

 

CAUTION!   

Please  use  only  VDE-tested,  CE-marked  power  cables  to 

connect any equipment to the UPS. 

CAUTION!   

When installing the equipment, ensure that the sum of the 

leakage  current  of  the  UPS  and  the  connected  equipment  does  not 
exceed 3.5mA.

 

CAUTION! 

The OL1000 / OL1500 / OL2000 / OL3000 models are only 

qualified maintenance personnel may carry out installations.

 

CAUTION!   

Do not unplug the unit from AC Power during operation, as 

this will invalidate the protective ground insulation. 

CAUTION!   

To avoid electric shock, turn off and unplug the unit before 

installing  the  input/output  power  cord  with  a  ground  wire.  Connect  the 
ground wire prior to connecting the line wires! 

CAUTION!   

Do not  use an improper size power cord  as it may cause 

damage to your equipment and cause fire hazards. 

CAUTION!   

Wiring must be done by qualified personnel.

 

CAUTION!    DO  NOT  USE  FOR  MEDICAL  OR  LIFE  SUPPORT 
EQUIPMENT!

    Under  no  circumstances  this  unit  should  be  used  for 

medical applications involving life support equipment and/or patient care.

 

CAUTION!    DO NOT USE WITH OR NEAR AQUARIUMS!

    To reduce 

the risk of fire, do not use with or near aquariums.    Condensation from 
the  aquarium  can  come  in  contact  with  metal  electrical  contacts  and 
cause the machine to short out. 

CAUTION!   

Do  not  dispose  of  batteries  in  fire  as  the  battery  may 

explode. 

CAUTION!   

Do not open or mutilate the battery, released electrolyte is 

harmful to the skin and eyes. 

CAUTION!   

A battery can present a risk of electric shock and high short 

circuit  current.  The  following  precaution  should  be  observed  when 
working on batteries 
1.

 

Remove watches, rings or other metal objects. 

2.

 

Use tools with insulated handles. 

CAUTION!   

The  unit  has  a  dangerous  amount  of  voltage.  When  the 

UPS  indicators  is  on,  the  units  may  continue  to  supply  power  thus  the 
unit’s outlets may have a dangerous amount of voltage even when it’s not 
plugged in to the wall outlet. 

CAUTION!   

Make  sure  everything  is  turned  off  and  disconnected 

completely before conducting any maintenance, repairs or shipment. 

CAUTION!   

Connect the Protection Earth (PE) safety conductor before 

any other cables are connected. 

WARNING!    (Fuses): 

To  reduce  the  risk  of  fire,  replace  only  with  the 

same type and rating of fuse. 

 

 

DO  NOT  INSTALL  THE  UPS  WHERE  IT  WOULD  BE  EXPOSED  TO 
DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE! 

DO  NOT  BLOCK  OFF  VENTILATION  OPENINGS  AROUND  THE 
HOUSING! 

DO  NOT  CONNECT  DOMESTIC  APPLIANCES  SUCH  AS  HAIR 
DRYERS TO UPS OUTPUT SOCKETS! 

SERVICING  OF  BATTERIES  SHOULD  BE  PERFORMED  OR 
SUPERVISED  BY  PERSONNEL  KNOWLEDGE  OF  BATTERIES  AND 
THE 

REQUIRED 

PRECAUTIONS. 

KEEP 

UNAUTHORIZED 

PERSONNEL AWAY FROM BATTERIES!

 

Summary of Contents for OL1000EXL

Page 1: ...User s Manual OL1000EXL OL1500EXL OL2000EXL OL3000EXL CyberPower Systems Inc www cpsww com K01 0000358 00 ...

Page 2: ... carry out installations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage t...

Page 3: ...lled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity range CAUTION Never install a UPS or associated wiring or equipment during a lightning storm CAUTION Do not work alone under hazardous conditions CAUTION In case of the risk of electric shock do not remove the top cov...

Page 4: ...ephone fax machine or network device 5 Press the ON OFF switch to turn the UPS on The Power On indicator light will display when activated If an overload is detected an audible alarm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to th...

Page 5: ...he power supply to equipment connected to NONCRITICAL outlets after a designated period of time 7 Serial Port Serial port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters 8 USB port This is a connectivity port which all...

Page 6: ...Copyright 2014 CyberPower Systems Inc BASIC OPERATION 5 OL1000EXL OL1500EXL OL2000EXL OL3000EXL ...

Page 7: ...Y Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description ON...

Page 8: ... XXX XV Displays the Output Voltage O P Freq XX XHz Displays the Output Frequency I P Volt XXX XV Displays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load as a Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Displays the Output VA BAT Volt XXX XV Displays the Battery ...

Page 9: ... to select the Language submenu 6 Press the and buttons to scroll to the language that you want to select You may be prompted to save the selection if so press the ENTER button to save the setting 7 Press the ESC button to cancel or return to previous LCD menu LCD SETTINGS CONFIGURATION There are 22 UPS settings that can be configured by the user 1 Press the ENTER button to activate the MAIN MENU ...

Page 10: ... Français French Deutsch German English Generator Mode Disable Enable Disable Communication Disable Enable Enable Dry Relay Set I P Power Fail Battery Low Summary Alarm UPS On Bypass UPS Fail I P Power Fail Converter Mode Converter Off O P Freq 50Hz O P Freq 60Hz Converter OFF Screen Saver Disable 1 Minutes 5 Minutes 5 minutes Clear Event Log Activate None Button OFF LOCK Disable Enable Disable Ch...

Page 11: ...st portion of the LCD screen and the unit will perform a manual battery test GRAPHICAL LOAD BATTERY CAPACITY DISPLAY 1 Press the ESC button to return to UPS Status 2 Press the and buttons to scroll to the LOAD and BAT Capacity 3 Press the and buttons to scroll to the Charging or Discharging Capacity Discharging Capacity The LCD screen displays the remaining battery capacity with a graphical icon w...

Page 12: ...s and may be toxic CAUTION To avoid electric shock turn off and unplug the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please refer to the front side of the UPS for the model number of the correct replacement batteries For battery procurement log ...

Page 13: ...e Mode 105 125 Load for 1 min 126 150 Load for 10 sec Battery Mode 105 130 Load for 10 sec 131 150 Load for 2 sec Short Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 3 12V 9AH 6 12V 9AH Recharge Time Typically 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that Support...

Page 14: ...he EPO connection Wiring Fault Line and neutral wires are reversed Exchange line and neutral wires Missing ground wire Connect ground wire No ground wire Disable Wiring Fault alarm on LCD panel Line Abnormal Wrong utility power backed up during UPS auto restart Check whether voltage or frequency of utility power is out of range Output Short Output short circuit Your attached equipment may have pro...