background image

6

I.B. 8926-1A

not be used for storage and should have
adequate lighting.

3.  Since control centers are assembled at the

factory on smooth and level surfaces to assure
correct alignment of all parts, control centers
should be securely mounted on a level surface.
The foundation furnished by the purchaser must
be true and level, or the bottom frames must be
shimmed to support the entire base in a true
plane. It is recommended  that  leveled channel
sills under both the front and rear of the control
center be used to provide this level base. Drill an
tap the channel sills for mounting bolts in
accordance with the applicable floor plan
drawing and then either install the MCC level
with, or on top of, the finished floor. If sills are
grouted in concrete, the mounting bolts should
be screwed in place and remain until the
concrete has hardened.

4.  For bottom entry, position the motor control

center so that the conduit stubs or floor
openings are located in the shaded areas shown
on the MCC floor plan drawings (refer to pages
31 to 32  for  floor plan dimensions). The shaded
areas represent the open space available for
conduit entry through the bottom of each
section. A shaded area may be restricted if large
controllers or  autotransformers are mounted in
the bottom of the sections. If optional bottom
plates are supplied, the plates may be removed
and drilled for conduit entry.

5.  Install the MCC in its final position, progressively

leveling each section and bolting the frames
together if they are separated. If necessary,
secure the MCC to walls or other supporting
surfaces. Do not depend on wooden plugs
driven into holes in masonry, concrete, plaster,
or similar materials. See NEC 110-13.

6.  If two or more shipping sections are to be joined

into an integral assembly or a shipping section is
to be joined to an existing section, refer to
paragraphs below before proceeding with the
installation.

7.  Ground and bond the motor control center as

follows:
a)  Motor control centers used as service

equipment for a grounded system or as an
incoming line section for a separately-
derived previously grounded system:
i)  Run a grounding electrode conductor

(ground wire) having a size in
accordance with NEC 250-94 from the
grounding electrode to the MCC ground
bus or ground terminal provided. See
also NEC 250-91(a) and 92(b).

ii)  If the system is grounded at any point

ahead of the MCC, the grounded

conductor must be run to the MCC in
accordance with NEC 250-23(b), and
connected to the ground bus terminal.

iii) Do not make any connections to ground

on the load side of any neutral
disconnecting line or any sensor used for
ground-fault protection. Do not connect
outgoing grounding conductors to the
neutral.

b)  Motor control centers used as service

equipment for an ungrounded system or as
an incoming line section for a separately-
derived previously ungrounded system:
i) Run a grounding electrode conductor

(ground wire) having a size in
accordance with NEC 250-94 from the
grounding electrode to the MCC ground
bus terminal. See NEC 250-91(a) and
92(b).

c)  Motor control centers not used as service

equipment nor as an incoming line section
for a separately-derived system, and used
on either a grounded or ungrounded system:
i)  Ground the MCC ground bus by means

of equipment grounding conductors
having a size in accordance with NEC
250-95 or by bonding to the raceway
enclosing the main supply conductors in
accordance with NEC 250-91(b).

8.  When all wiring and adjustments are complete,

close all unit and  wireway doors.

9.  In damp indoor locations, shield the MCC to

prevent moisture and water from entering and
accumulating.

10.  Unless the motor control center has been

designed for unusual service conditions, it
should not be located where it will be exposed to
ambient temperatures above 40

°

C (104

°

F),

corrosive or explosive fumes, dust, vapors,
dripping or standing water, abnormal vibration,
shock or tilting.

JOINING COMPATIBLE SECTIONS

If two more shipping blocks are to be joined into an
integral assembly, or a section added to an existing
installation, splicing or horizontal bus, ground bus,
neutral bus and joining of the adjacent vertical
sections must be planned with the installation.
1.  Remove the side sheets from adjacent vertical

sections to be joined. (These sheets will have
been removed from factory-assembled
sections.)

2.  The horizontal bus splice plates and connection

hardware will be shipped with the MCC attached
to one end of shipping section. Refer to Figure
4. This method provides the most convenient

Summary of Contents for Freedom 2100 Series

Page 1: ...Views 31 12 Related Instruction Leaflets 33 This electrical control equipment is designed to be installed operated and maintained by adequately trained workmen These instructions do not cover all det...

Page 2: ...10 which can be removed for installation and maintenance operations Adequate space is provided for control wiring and top cable entry At the bottom of each section a door 18 provides ready access to...

Page 3: ...on each handle The device panel 5 is mounted on the drawout unit It will accommodate up to six pilot devices The overload reset button 20 is mounted on the unit door 1 Unit Door 2 Drawout Unit 4 Turn...

Page 4: ...and after unloading the motor control center inspect each section and unit exterior for evidence of damage that may have been incurred during shipment If there is any indication that the control cent...

Page 5: ...rdance with both the National Electrical code NEC NFPA 70 and the National Electrical Safety Code NESC ANSI C2 Caution If work is involved in connecting the control center with existing equipment ensu...

Page 6: ...nd wire having a size in accordance with NEC 250 94 from the grounding electrode to the MCC ground bus or ground terminal provided See also NEC 250 91 a and 92 b ii If the system is grounded at any po...

Page 7: ...amp the rear upright channels together In front mounted only structures this will require removal of the adjacent back sheets In a back to back mounted structure remove the vertical wireway doors and...

Page 8: ...hrough 10 represents the backside of the MCC The top portion of each of these figures applies to 20 deep enclosures and the lower portion to 16 deep enclosures Note that for all but the single bar per...

Page 9: ...TROL Consult the assembly instruction supplied with every Freedom 2100 Motor Control Center set up for splice to Freedom Unitrol or F10 Unitrol Fig 11 Splice Plates Attached to Freedom 2100 Horizontal...

Page 10: ...oad be sure to have each conduit carry conductors from each phase and the same number of conductors per phase If the phase conductors are not distributed uniformly eddy currents will be generated in t...

Page 11: ...be wired outside of the vertical wireway To engage the terminal block align the fingers of the male connector with the slot at the back of the female portion of the terminal block Then rotate the mal...

Page 12: ...C and the 10 foot rule and the 25 foot rule of NEC 240 21 apply These latter exceptions to the general rule allow the disconnect means and Fig 17 Main Disconnect with Stab Load Connections overcurrent...

Page 13: ...metrical the installing electrician needs to anchor the cables at the incoming line connections sufficiently and tighten the lugs correctly Each incoming line compartment is equipped with a two piece...

Page 14: ...applications such as jogging Class 10 or 20 heater packs Fig 24 Use Class 10 heaters with fusible or thermal magnetic breaker disconnects only Bimetallic ambient compensated operated Trip free mechan...

Page 15: ...trip setting which does not exceed the calculated figure of Item 2 This is the maximum setting that should be used 4 Depress and turn the screwdriver adjustment counter clockwise one setting at a tim...

Page 16: ...used select the wire size as if the conductors had an insulation temperature rating of 75 C even if the conductors actually used have a temperature rating higher than 75 C Protect heater and starter a...

Page 17: ...TIC RESET The overload relay is factory set at M for manual reset operation as shown in the illustration For automatic reset operation turn the reset adjustment dial to the A position Automatic reset...

Page 18: ...MPERES 3 90 N 14 4 135 MAXIMUM RATINGS Minimum Wire Size 6 AWG l NOTES Part Winding Starters Select heater packs for 50 of the motor FLA Wye Delta Starters Select heater packs for 58 motor FLA u For m...

Page 19: ...shed 11 Set any adjustable current and voltage trip mechanisms to the proper values 12 Ensure that overload relay heater elements are installed and selected to the full load current shown on the namep...

Page 20: ...emoving the unit door the control unit is exposed With a screwdriver push in on the latch at the top center of the unit and rotate turn counterclockwise CAUTION Units 18 or more high have a retaining...

Page 21: ...is withdrawn free of the linkage a spring automatically moves the shutter to its closed position See Figure 31 and Figure 4 With the control unit removed the shutter should completely cover the stab...

Page 22: ...1 Remove the existing blank door 2 Position the new unit door over the open space to ensure the hinges and latches are aligned If the spaces differ the hinges and latches on the structure must be re l...

Page 23: ...g and adjusting the electrical equipment refer to the applicable drawings covering the specific motor control center MCC and any other related interconnection drawings Follow any instructions which ma...

Page 24: ...nts charred insulation discolored terminals etc Mechanically clean to a bright finish don t use emery paper or replace those terminations that have become discolored Determine the cause of the loose j...

Page 25: ...racket does not need field adjustment The interlock bracket will be adjusted to almost touch the side of the unit interlock rod when the operator is in the on position Fig 35 6 Inch Breaker Unit Slide...

Page 26: ...d to coil Correct any mechanical defects or misalignment Abrasive dust on contacts Do not use emery cloth to dress contacts Load current is too high Reduce load Use larger contactor Jogging cycle is t...

Page 27: ...er opening indicates deterioration beyond normal wear and tear such as overheating contact blade or jaw pitting insulation breakage or charring the switch must be replaced Fuse holders Deterioration o...

Page 28: ...ore quickly than the other three corners This wear is normally due to misalignment of the moving and stationary contacts Contacts should be replaced if it is apparent that one contact is nearly making...

Page 29: ...9 2756 13 9 1891 20 9 1891 20 380 415V 50 Hz L 9 2703 8 9 2703 8 380V 50 Hz L 9 2756 12 9 1891 14 9 1891 14 415V 50 Hz M 9 2756 8 9 1891 21 9 1891 21 550V 50 Hz N 9 2756 14 9 1891 8 9 1891 8 C306KN3 C...

Page 30: ...t Guides Included with Item 3 5 Quarter Turn Latch Included in Item 9 4 Freedom Starter 3 Unit Frame 2 Heater Mounts 1 8 Stab Assembly 9 Unit Drawout Handle 10 Unit Terminal Blocks 11 Control Power Tr...

Page 31: ...31 I B 8926 1A Part 11 PLAN VIEWS...

Page 32: ...e removed to provide maximum unrestricted conduit space at the bottom of the MCC 5 This conduit space is not recommended when a neutral bus is required Otherwise available See side View A far right fo...

Page 33: ...t height above floor line is 3 50 inches 3 Maximum conduit space with channel sills is 17 50 X 9 73 inches 4 For multiple structure assemblies either one or both of these members are removed to provid...

Page 34: ...g and Reversing vacuum I L 16999 Size 5 Non Reversing and Reversing vacuum I L 17088 Circuit Breakers Series C F frame I L 29C101 Series C J frame I L 29C103 Series C K frame I L 29C104 Series C L fra...

Reviews: