background image

I.B. 48008

Page 2

Effective 11/97

SYNCHRONOUS MOTORS (Continued)

changing the field current can change the power factor at
which the synchronous motor runs or the reactive current
drawn from the AC line.

A synchronous motor cannot start with its DC pole
windings excited.  Voltage is applied to the DC winding
only after the motor has been accelerated to a speed
which is over 90 percent of synchronous speed.  With a
slip of less than ten percent, the DC poles will jump to
synchronous speed when DC voltage is applied and will
lock onto the rotating magnetic field produced by the
three-phase alternating current in the stator.

Applying DC at the most advantageous time is the job of
the motor controller which uses feedback signals to opti-
mize the transition and thereby minimize the disturbance to
the power system at the time of synchronization.

MOTOR FIELD EXCITATION

In this controller, the DC power for the excitation of a
synchronous motor field is obtained from a solid-state
power supply (exciter).  Provisions are made for field
current adjustments.  Usually, field current is set to
optimum values only after the motor field has reached
maximum operating temperatures.  On cold start-ups, the
field current may be 20 to 40% high initially but will
decrease to normal as operating temperatures are
reached.  The field current is usually maintained as set
during motor operation except where the field current
regulator option is included for those applications in which
VAR, power factor, or the field current itself is being
automatically adjusted.

THE MOTOR CONTROLLER

As explained in the companion instruction material, each
Ampgard

®

 full-voltage motor starter (controller) consists of

one nonload-break isolating switch, one contactor, current-
limiting fuses, a set of current transformers, and some
form of overload protection.  A reduced-voltage starter
includes all of the components of a full-voltage starter plus
one or two additional contactors and related control
components.  A synchronous motor controller is either a
full-voltage starter or a reduced-voltage starter which
includes a source of DC and the additional controls
needed to start a synchronous motor, operate it at syn-
chronous speed, and protect it.

THE MARK V CONTROLLER

The Mark V is a field power supply and controller that
blocks the field voltage during subsynchronous operation
and applies the field voltage during synchronous operation.
The field voltage is adjusted by a potentiometer during
operation.

Fig. 1  Synchronous Motor Components

This solid-state field power source functions without
regard to the phase sequence of the three-phase power
supply, which may be at either 50 or 60 hertz.  The field
power supply and controller contains synchronizing
circuitry with means to adjust the synchronizing slip-
frequency from 1 to 9 percent (SW1) and the permissible
stalled-rotor time from 0 to 9 seconds (SW2).  It has pole
slippage sensing, incomplete sequence detection and
shutdown in the case of exciter low voltage or phase loss.

Figure 2 shows the solid-state field power supply panel
designed to control the application of either 125 VDC or
250 VDC to the field of a synchronous motor.  The panel
consists of a printed circuit board (synchronizing control
board), protective fuses, and an assembly of power
thyristors (silicon controlled rectifiers, SCR’s) arranged to
convert 120 or 240 VAC, three-phase, to 125 or 250 VDC,
respectively.  The direct current (DC) is supplied directly to
the field of the synchronous motor.  The synchronizing
control board shown in the lower portion of Figure 2
appears enlarged in Figure 3.

Characteristics

Each Mark V controller has a maximum DC current
capability (50, 100, or 200 amperes), a rated field supply
voltage of 125 or 250 VDC, and the ability to withstand a
field output (induced) voltage of up to 1500 volts during
the time that the motor is coming up to rated speed, i.e.,

Summary of Contents for EATON Ampgard Mark V

Page 1: ...squirrel cage induction bars located in the faces TABLE I REFERENCE MATERIAL Contactor Ampere Instruction Type Rating I L or I B Type SJA 360A I B 48002 Type SJA 720A I B 48005 Type SJD 360A I B 48004...

Page 2: ...oltage starter includes all of the components of a full voltage starter plus one or two additional contactors and related control components A synchronous motor controller is either a full voltage sta...

Page 3: ...short out the reactor or to connect and disconnect the autotransformer in the circuit The overload protection relay e g IQ1000 II protects the motor from damage by overcurrent conditions single phasi...

Page 4: ...erminals KA2 KB2 or KC2 RLY1 will drop out to open the control circuit RLY1 and RLY3 may pulse open and closed during certain types of faults causing the interposing relay MX to drop out insuring that...

Page 5: ...ower supply cabinet The range of local voltage control adjustment is coordinated with the minimum output voltage adjustment P1 to produce the desired minimum and maximum output voltages Fig 4 Mark V C...

Page 6: ...terminal located with the TO terminal near T4 Remove jumpers from the two 120V terminals located near T4 See Figure 5 and Table II ADJUSTINGTHE MOTOR FIELDVOLTAGE To adjust the motor field voltage use...

Page 7: ...N When voltage is applied to terminals 115 and IN the Mark V will go into the synchronizing mode SYSTEM PROTECTION This controller includes circuits that provide a means of shutting down in the event...

Page 8: ...ed on motor start up while ensuring that proper sequential synchronizing occurs and that motors will operate continu ously in synchronism The protection system must detect and operate for a condition...

Page 9: ...ith motor voltage HP and FLA Check the torque tightness of all connections Study all applicable instruction material and diagrams Have available the schematic and connection diagrams fur nished with t...

Page 10: ...use 2 With the motor field disconnected verify that the resistance between F1 and F2 on the terminal strip is 250 ohms 15 ohms 3 Measure the resistance of the starting and discharge resistor S D RES o...

Page 11: ...th power available on the Ampgard bus system close the controller isolating switch and close the line contactor M 7 Plan to keep the motor field energized with the motor still for not more than two mi...

Page 12: ...on 4 External Inhibit 7 Field Excitation 2 Frequency Option 6 Full Operation 11 Fuse and Contactor Check 9 Incomplete Sequence 6 Mark V Controller 3 Motor Controller 2 Motor Field Excitation 2 Page Op...

Reviews: