34. Extender Cable
An extender cable provides a means for extending the
distance between the power switching panel and the
logic panel. This allows for remote mounting of the logic
panel.
A. 48 inch (1.2 m)
B. 72 inch (1.8 m)
C. 96 inch (2.4 m)
D. 120 inch (3.0 m)
E. 144 inch (3.7 m)
Special lengths are available. Contact Cutler-Hammer.
37. Service Entrance
A. Provides transfer switch as suitable for service
equipment rating - A key operated selector switch
permits external, power operated service disconnec-
tion with external pilot light for disconnect indication,
also includes Option 16.
B. Same as A except includes ground fault protection.
41. Space Heater with Thermostat
A. 100 Watts
B. 200 Watts
C. 400 Watts
42. Seismic Withstand Capability
Provides transfer switch with seismic capability exceed-
ing the worst case Zone 4 required levels per both the
Uniform Building Code and the California Building
Code.
3.7 ENCLOSURE
The rugged steel switch enclosure is supplied with three
door hinges, regardless of enclosure size, to insure
proper support of the door and door mounted devices
(Figures 3-10, 4-1 and 4-2). The hinges have removable
hinge pins to facilitate door removal. The doors are sup-
plied as standard with a key lockable handle. Cable
entry holes are the customer’s responsibility.
The door is used to mount a variety of lights, switches
and pushbuttons, depending upon the options required
for a particular switch. All switch doors are supplied with
a heavy duty plastic accessory panel in place, whether
or not external devices are required. When lights, push-
buttons or switches are required, they are normally
mounted in the plastic door mounted panel. Models of
2500 amperes and higher have two doors (Figures 4-1
and 4-2).
Transfer switch enclosures and all internal steel mount-
ing plates, such as the power panel mounting plate, go
through a pre-treatment cleaning system prior to paint-
ing to insure a durable finish. Contact your local Cutler-
Hammer sales representative for touch-up paint infor-
mation.
The standard switch enclosure is NEMA Type 1 for gen-
eral indoor use (Table 3.1).
3.8 STANDARDS
Cutler-Hammer transfer switch equipment enclosed in a
NEMA 1 enclosure is listed for application by UL, and
are certified to meet Canadian Standards by
Underwriters Laboratories Inc. (CUL), except for Bypass
Isolation units. In addition, Cutler-Hammer Automatic
Transfer Switches are listed in File E38116 by
Underwriters Laboratories, Inc. under Standard UL
1008. This standard covers requirements for automatic
transfer switches intended for use in ordinary locations
to provide for lighting and power as follows:
a. In emergency systems, in accordance with articles
517 and 700 in the National Electrical Code,
ANSI/NFPA 70 and the National Fire Protection
Association No. 76A and/or
6.13 (156)
9.50 (241)
7.50 (191)
7.38 (187)
Figure 3-9 Charger Mounting Dimensions in Inches
(mm)