background image

PROBLEM: WATER OVERFLOWING.

POSSIBLE CAUSE

SOLUTION

Turn power off and observe water level. If water continues to flow into the heating tank, 

clean or replace leaky valve.

Disconnect wire from probe terminal. Touch the body of the heating tank with the terminal 

at the end of this wire. If the flow of water stops, try cleaning the probe. The probe may 

have to be replaced.

Liquid level control board must be securely grounded through the back of the board and 

the mounting bracket. Check for loose connections at the terminals. Check for voltage 

across the inlet valve terminals. If there is 110 to 120 volts present at the inlet valve termi

-

nals when water level is touching the probe tip, replace the L.L.C. board.

1.  Defective water  

 

  inlet valve

2.  Liquid level probe  

 

  limed up

3.  Non-grounded or  

 

  loose terminal  

 

  connections at 

 

  liquid level con- 

 

  trol board

POSSIBLE CAUSE

SOLUTION

1.  Thermostat  is turned  

  OFF (or set too low)

Check the thermostat adjustment to make sure the knob is rotated clockwise to the desired 

temperature setting.

PROBLEM: WATER DOES NOT REACH PROPER TEMPERATURE

POSSIBLE CAUSE

SOLUTION

PROBLEM: WATER WILL NOT REFILL

1.  Water line closed or    

  clogged filter

2.  Valve coil burned out

3. Grounded probe

4.  Defective water level    

  control board

TROUBLE SHOOTING

Check the water system at your facility to make sure the line is open. Replace the water 

filter.

Turn machine off. Disconnect wires from water inlet coil terminals and connect a power 

cord to the terminals. Plug cord into a 120V outlet and verify if water flows when plugged 

in and stops when power is disconnected. If valve fails this test, replace valve.

When the water level gets below the probe tip, water should automatically refill the unit. If 

not, pull wire off the probe terminal. Water should now start flowing into the water boiler.

Disconnect wire from probe terminal. With a voltmeter, check voltage at the water inlet 

coil terminals. This should read 110-120 volts. If no voltage is present, check liquid level 

control (L.L.C.) board. Make sure the L.L.C. board is supplied by 120V across terminals 

T2 & T3. The L.L.C. board is grounded to the body of the machine by contacting the 

board to the mounting bracket. Make sure board is grounded here. Check for loose con

-

nections at terminals. Replace board.

SOLUTION

POSSIBLE CAUSE

PROBLEM:  WATER OVERHEATS, ELEMENTS DO NOT SHUT OFF

Replace the thermostat. You can sometimes operate temporarily by turning the ther

-

mostat knob to off until the boiling stops.

1.  Defective 

  thermostat

4

Reviews: