Part No. 4801-1020 Rev 2-2015
Super-Saver XL 250 Heater
– 120 Volt, 60Hz, ETL
Page
16
of 22
Table 1
Minor Loss Equivalents
Fitting
2" (5.08 cm) IPS Or Smaller
2” (5.08 cm) IPS To 4” (10.16 cm) IPS
Feet per fitting
Meters per fitting
Feet per fitting
Meters per fitting
45
Elbow
3
1
5
2
90
Elbow
6
2
10
3
Tee
11
4
20
6
Gate Valve
2
1
3
1
Angle Valve
29
9
60
18
Swing Valve
15
5
30
9
Table 2. Maximum Capacity Of Pipe In Thousands Of BTU per Hour
Nominal
Internal
Natural Gas (Methane) @ Pressure Drop Of 0.5 in w.c. (0.2 mbar)
Iron Pipe
Diameter,
Values listed are for 0.6 sp.gr. based on Heat Of Combustion of 1000 BTU/cu .ft
Size,
(IPS)
Length Of Pipe, Feet (multiply ft by 0.3 to convert to meter)
Inch*
Inch*
10
20
30
40
50
60
70
80
90
100
150
200
250
300
1/2
.622
175
120
97
82
73
66
61
57
53
50
40
35
29
25
3/4
.824
360
250
200
170
151
138
125
118
110
103
84
72
59
53
1
1.049
680
465
375
320
285
260
240
220
205
195
160
135
109
100
1-1/4
1.380
1400
950
770
660
580
530
490
460
430
400
325
280
219
206
1-1/2
1.610
2100
1460
1180
990
900
810
750
690
650
620
500
430
325
309
2
2.067
3950
2750
2200
1900
1680
1520
1400
1300
1220
1150
950
800
614
596
2-1/2
2.469
6300
4350
3520
3000
2650
2400
2250
2050
1950
1850
1
1500
0
1280
966
950
3
3.068
1100
0
7700
6250
5300
4750
4300
3900
3700
3450
3250
2650
6
2280
1855
1680
4
4.026
2300
0
1580
0
1280
0
1090
0
9700
8800
8100
7500
7200
6700
5500
1
4600
3783
3432
Table values given in BTUH/1000. To convert to kW, multiply table values by 0.3
* 1 inch = 25.4 mm
Pipe Sizes Determined For Diagram
Pipe Section
Max Gas Capacity Value Determined From Table 2
Pipe Size Determined From Table 2
BTUH
kWh
inches
mm
a-b
280,000
82
1-1/4 in
31.8
b-c
135,000
40
1 in
25.4
b-d
72,000
21
¾ in
19.1
b-f
72,000
21
¾ in.
19.1
c-e
72,000
21
¾ in.
19.1
c-g
72,000
21
¾ in .
19.1
Table 3. Maximum Capacity Of Pipe In Thousands Of BTU per Hour
Nominal
Internal
Liquid Propane (LP) @ Pressure Drop Of 0.5 in w.c.
Iron Pipe
Diameter,
Values listed are for 1.6 sp.gr. based on Heat Of Combustion of 2500 BTU/cu .ft
Size,
(IPS)
Length Of Pipe, Feet (multiply ft by 0.3 to convert to meter)
Inch*
Inch*
10
20
30
40
50
60
80
100
125
150
200
250
300
350
400
1/2
.622
291
200
161
137
122
110
94
84
74
67
58
51
46
43
40
3/4
.824
608
418
336
287
255
231
198
175
155
141
120
107
97
89
83
1
1.049
1146
788
632
541
480
435
372
330
292
265
227
201
182
167
156
1-1/4
1.380
2353
1617
1299
1111
985
892
764
677
600
544
465
412
374
344
320
1-1/2
1.610
3525
2423
1946
1665
1476
1337
1144
1014
899
815
697
618
560
515
479
2
2.067
6789
4666
3747
3207
2842
2575
2204
1954
1731
1569
1343
1190
1078
992
923
Table values given in BTUH/1000. To convert to kW, multiply table values by 0.3.
* 1 inch = 25.4 mm
IMPORTANT
Tables 2 and 3 are based on values given in the Gas Engineers Handbook and are intended as a guide only.
Consult your gas supplier for gas capacity and pipe size information for your particular piping system.