background image

 

Part No. 4801-5309 rev 1-15 

Evolution Back-Up 

7 of 17 

To Set High Limit: 

1.

 

Press the “Mode” button to select the High Limit Indicator. 

2.

 

Press the ”+” and ”–“ buttons to enter the value of the High Limit. 

3.

 

Setting Complete. 

 

To Set Low Limit:

 

1.

 

Press the “Mode” button to select the Low Limit Indicator. 

2.

 

Press the + and – button to enter the value of the Low Limit. 

3.

 

Setting Complete. 

9.  Program Mode Parameters 

Settings that are usually set up once per growout, or maybe even just for summer or winter are referred to 
as program parameters and are accessed by taking the controller to program mode.  To get to program 
mode, press and hold the “Mode” button for five seconds. When the controller has entered program mode, 
the main display will flash between “P1” and the value of this parameter. 

  

The “P1” is known as a parameter number. All the program items for the controller have a parameter 
number assigned to them. The numbers are listed in the table “Program Mode Parameters” below with a 
short description of each parameter.  When in program mode, you change the value of certain parameters 
by using the + and - buttons as needed.  When you have finished with the current setting, press the “Mode” 
button to move to the next parameter.  The program mode parameters for the Evolution Back-Up are 
shown in Table 1. 

10. Calibrate 

Sensors 

The temperature sensors should be calibrated to ensure accurate temperature detection.  To calibrate the 
sensors an independent temperature measurement is required such as a thermometer or thermocouple. 

 

1.

 

Place a thermometer inside the house at the location of each sensor.  Allow a few minutes for the 
temperature to stabilize. 

2.

 

Take readings from the thermometers located at Sensor 1 and Sensor 2. 

3.

 

Use the Program Mode to set calibrations of Sensor 1 and Sensor 2 (Refer  to Table 1). 

Parameter 

Description 

P1 

This selects either English (OFF = Fahrenheit) or Metric (ON = Celsius) temperature 
units. 

P2 

Determines if an alarm is sent on a Back-Up condition.  (ON = Alarm On, OFF = Alarm 
OFF)  An alarm will be generated on an error condition even if P2 is set to OFF.  See 
Section 13. 

P3 

Emergency Timer Percentage. (0% to 100%). This determines the percentage that 
COOL 1 will be run in an Emergency condition.  

P41 

This is the software version number.  Not Changeable. 

PS1 

This is the calibration temperature for Sensor 1. 
Instructions: With the controller operating, use a digital thermometer or similar 
independent temperature measuring device to measure the temperature at Sensor 1 
location.  With PS1 selected, use the + and – buttons to set the calibration temperature 
to the thermometer reading.

 

PS2 

This is the calibration temperature for Sensor 2. 
Instructions: Same as Sensor 1 except substitute PS2 for PS1 in the instructions above.

 

Table 1.  Program Mode Parameters

 

Summary of Contents for Evolution Back-Up

Page 1: ...Part No 4801 5309 Rev 1 15 Owners Manual Evolution Back Up CUMBERLAND Assumption IL 62510 Phone 217 226 4421 Fax 217 226 4420 Evolution Back Up Cumberland 1004 E Illinois St Assumption IL 62510...

Page 2: ...ctions 6 7 1 Toggle Sequence of Mode Button 6 7 2 Checking Adjusting Temperatures and Settings 6 8 Set Limits 6 9 Program Mode Parameters 7 10 Calibrate Sensors 7 10 1 Installation 8 10 2 Unpacking Co...

Page 3: ...switch position 50 60 Hz Room Temperature must be between 32 F 0 C and 122 F 50 C 2 Warnings Warning When this controller is used in a life support heating and ventilation system where failure could...

Page 4: ...nces These modes are Normal Operation Emergency Operation and Override Operation These modes will be explained in more detail below These modes are entered based on information that it has received or...

Page 5: ...lay is also engaged in this mode of operation 4 4 Fail Safe Relay Operation There are two types of Relay strips used in the Evolution 3000 The Normally Open NO strip requires a signal from the control...

Page 6: ...en use the button to increase the value and the button to decrease the value Room Temperature The average of the sensors located inside the house High Limit The temperature inside the house at which t...

Page 7: ...Table 1 10 Calibrate Sensors The temperature sensors should be calibrated to ensure accurate temperature detection To calibrate the sensors an independent temperature measurement is required such as...

Page 8: ...11 2 6 Wire the power supply See Section 11 4 7 Wire the Back Up to the EV 3000 See Wiring Diagrams at the back of this manual 8 Wire the Local Network connection 9 Connect the PowerTrak to the Overri...

Page 9: ...f 17 11 Wiring Diagrams 11 1 Evolution Back Up Assembly Alarm Connections Sensor Connections Tunnel Override Settings Vent Override Settings Backup Connections to Evolution Voltage Selector Switch Pow...

Page 10: ...Connection to Enable Sensor 2 Inset B Sensor 1 2 Connections Sensor 2 Enabled Installed Enabled Vacant Disabled Jumper NOTE Tape Shields to Prevent Damage Inset C Back Up Alarm Connection Internal Wir...

Page 11: ...o pull curtain up to open then reverse wires connected to Open and Close terminals Inset A Vents Override Evolution Back Up Circuit Board PowerTrak Inset A Vent Override To EV 3000 Cont Hot PT Hot PT...

Page 12: ...000 16 Stage Expansion Module Evolution 3000 Cabinet INSET A Inset A AC input on PCB 171 External GND Hot Neutral External GND Hot Neutral External GND Hot Neutral External GND Hot Neutral AC Junction...

Page 13: ...pansion units Back up Local Network Local Network Back up Local network Harness In Expansion Backup Green Red Red Green White Shield Black White Shield Black Black White White Black Orange Orange Gree...

Page 14: ...42 4 5 8 12 493 68 20 6 836 93 33 9 24 055 43 6 1 12 325 68 5 20 3 6 779 93 4 34 1 23 82 43 3 6 3 12 215 68 9 20 5 6 695 93 9 34 4 23 472 43 9 6 6 12 051 69 4 20 8 6 612 94 5 34 7 23 13 44 4 6 9 11 9...

Page 15: ...a shorted sensor wire Check sensor resistance E2 Sensor 2 Error Usually indicates a shorted sensor wire Check sensor resistance Note If Sensor 2 is switched OFF then this error code is not active E3...

Page 16: ...ons and Limitations THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPTION SET FORTH ABOVE SPECIFICALLY GSI MAKES NO FURTHER WARRANTY OF ANY KIND EXPRESS OR IMPLIED INCLUDING WITH...

Page 17: ...Part No 4801 5309 rev 1 15 Evolution Back Up 17 of 17...

Reviews: