background image

 

Part No. 4801-5309 rev 1-15 

Evolution Back-Up 

5 of 17 

4.2 Emergency 

Operation 

In this mode of operation, the system still maintains the temperature as it does in Normal Operation.  In 
addition, it will begin running the first cooling stage (Cool 1) on a 5 minute timer.  The timer percentage is 
determined by the setting in P3 (Emergency Timer Percentage).  This mode of operation is entered if 
communication is lost between the master controller and the Back-Up System.  In this case, the Back-Up 
System assumes that the master controller is lost and tries to maintain the minimum ventilation until 
someone recognizes the problem.  Emergency Operation is indicated by a “LnE” flashing in the display of 
the Back-Up System.  The alarm relay on the Back-Up System is also engaged in this mode operation. 

4.3 Override 

Operation 

In this mode of operation, the system still maintains the temperature as it does in Normal Operation.  In 
addition, it receives commands from the master controller to turn on certain stages of heating or cooling.  
There are many different circumstances that could cause this to happen, in this manual, we will list one of 
the most common.  For example, if communication were lost inside the EV-3000, the master controller 
would be unable to turn the appropriate stages on in the usual way.  Therefore, the master controller would 
communicate to the Back-Up System and indicate which stages that it is trying to turn on.  At this point, 
the Back-Up System would obey the command and turn the appropriate stages on.  For this mode of 
operation to work to its fullest potential, care must be taken to insure that the stage jumpers on the relay 
strips match the stage setting in the master controller (Refer to Section 12).  Override Operation is 
indicated by a “LnO” flashing in the display of the Back-Up System.  The alarm relay is also engaged in 
this mode of operation. 

4.4 

Fail-Safe Relay Operation 

There are two types of Relay strips used in the Evolution 3000.  The Normally Open (NO) strip requires a 
signal from the controller board in order to energize a stage of ventilation.  Should power be removed from 
the EV-3000 the Normally Open Relay strips would not be able to energize a ventilator.  On the other hand 
the Fail-Safe relay strip would close each of the relays in the strip resulting in energizing the ventilators in 
case of a controller power failure.  Each of the relay strips contains four relays for controlling four stages.  
In the EV-3000 there are a total of four relay strips, three will be N.O. and one will be a Fail-Safe.  The 
operator must insure that the Fail Safe relay strip is connected only to stages that should be turned on in 
case of a controller failure.  See the EV-3000 Owners manual Part No. 4801-5307 for a physical 
description of the relay strips.  It is not recommended to place heating equipment on Fail-Safe stages. 

5.  Inlet Operation During Back-up 

The EV-Back-Up contains a relay that can operate the Vents 
and/or Tunnel during Back-up operation of the EV-3000. 
The Inlets will automatically open during back-up. 
Cool 1 controls Vents Inlet.  Cool 3 controls Tunnel Inlets.  
When Cool 1 and Cool 3 are not set, Back-up reverts to Normal 
operation. 
 
 

6.  Setting EV-Back-Up Stage Jumpers 

Pictured at the right is a Stage Relay Board consisting of four 
stage relays and the associated stage jumper for each stage relay.  
The stage jumpers are labeled COOL 1, COOL 2, COOL 3 and 
HEAT.  Location of the jumper places the stage in one of these 
four modes, or if the jumper is 

not

 inserted, the stage is 

not

 

placed on Back-Up.  The jumpers should be placed based on the 
operation of stage equipment and should be the same as assigned 
in the EV-3000 Controller.  Jumpers are placed according the 
following table: 
 

Stage Relay 

Stage Harness 

connector 

cables to 

Terminal Block

 

COOL 3 
COOL 2 
COOL 1 
  HEAT 

Stage 
Jumpers 

STAGE RELAY BOARD 

Summary of Contents for Evolution Back-Up

Page 1: ...Part No 4801 5309 Rev 1 15 Owners Manual Evolution Back Up CUMBERLAND Assumption IL 62510 Phone 217 226 4421 Fax 217 226 4420 Evolution Back Up Cumberland 1004 E Illinois St Assumption IL 62510...

Page 2: ...ctions 6 7 1 Toggle Sequence of Mode Button 6 7 2 Checking Adjusting Temperatures and Settings 6 8 Set Limits 6 9 Program Mode Parameters 7 10 Calibrate Sensors 7 10 1 Installation 8 10 2 Unpacking Co...

Page 3: ...switch position 50 60 Hz Room Temperature must be between 32 F 0 C and 122 F 50 C 2 Warnings Warning When this controller is used in a life support heating and ventilation system where failure could...

Page 4: ...nces These modes are Normal Operation Emergency Operation and Override Operation These modes will be explained in more detail below These modes are entered based on information that it has received or...

Page 5: ...lay is also engaged in this mode of operation 4 4 Fail Safe Relay Operation There are two types of Relay strips used in the Evolution 3000 The Normally Open NO strip requires a signal from the control...

Page 6: ...en use the button to increase the value and the button to decrease the value Room Temperature The average of the sensors located inside the house High Limit The temperature inside the house at which t...

Page 7: ...Table 1 10 Calibrate Sensors The temperature sensors should be calibrated to ensure accurate temperature detection To calibrate the sensors an independent temperature measurement is required such as...

Page 8: ...11 2 6 Wire the power supply See Section 11 4 7 Wire the Back Up to the EV 3000 See Wiring Diagrams at the back of this manual 8 Wire the Local Network connection 9 Connect the PowerTrak to the Overri...

Page 9: ...f 17 11 Wiring Diagrams 11 1 Evolution Back Up Assembly Alarm Connections Sensor Connections Tunnel Override Settings Vent Override Settings Backup Connections to Evolution Voltage Selector Switch Pow...

Page 10: ...Connection to Enable Sensor 2 Inset B Sensor 1 2 Connections Sensor 2 Enabled Installed Enabled Vacant Disabled Jumper NOTE Tape Shields to Prevent Damage Inset C Back Up Alarm Connection Internal Wir...

Page 11: ...o pull curtain up to open then reverse wires connected to Open and Close terminals Inset A Vents Override Evolution Back Up Circuit Board PowerTrak Inset A Vent Override To EV 3000 Cont Hot PT Hot PT...

Page 12: ...000 16 Stage Expansion Module Evolution 3000 Cabinet INSET A Inset A AC input on PCB 171 External GND Hot Neutral External GND Hot Neutral External GND Hot Neutral External GND Hot Neutral AC Junction...

Page 13: ...pansion units Back up Local Network Local Network Back up Local network Harness In Expansion Backup Green Red Red Green White Shield Black White Shield Black Black White White Black Orange Orange Gree...

Page 14: ...42 4 5 8 12 493 68 20 6 836 93 33 9 24 055 43 6 1 12 325 68 5 20 3 6 779 93 4 34 1 23 82 43 3 6 3 12 215 68 9 20 5 6 695 93 9 34 4 23 472 43 9 6 6 12 051 69 4 20 8 6 612 94 5 34 7 23 13 44 4 6 9 11 9...

Page 15: ...a shorted sensor wire Check sensor resistance E2 Sensor 2 Error Usually indicates a shorted sensor wire Check sensor resistance Note If Sensor 2 is switched OFF then this error code is not active E3...

Page 16: ...ons and Limitations THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPTION SET FORTH ABOVE SPECIFICALLY GSI MAKES NO FURTHER WARRANTY OF ANY KIND EXPRESS OR IMPLIED INCLUDING WITH...

Page 17: ...Part No 4801 5309 rev 1 15 Evolution Back Up 17 of 17...

Reviews: