background image

Chapter 1: Wiring Diagrams

Storage Temperature

-20 to 50°C (-4 to 122°F)

Environment Type

Indoor use only

Pollution Degree

2

Installation Category

2

Altitude

2000 Meters Max. (5661 Ft. Max)

Operating Relative Humidity
(maximum)

0 to 10°C (32 to 50°F) Non condensing

10 to 30°C (50 to 86°F) 95 % (± 3 %) Non condensing

30 to 40°C (86 to 104°F) 95 % (± 3 %) Non condensing

IP rating (IEC 60529)

54

Nema Rating (Nema 250)

12

Flame Rating (UL94)

5VA-0

Flame Rating (IEC 60695 or IEC
60707)

FV-0

IK rating (degree of mechanical protec-
tion — impact, IEC 62262)

08

Main supply voltage fluctuations shall not /- 10% of the nominal supply voltage.

EDGE Power Module - Functional ratings

Enclosure dimensions

Height

400 mm (15.75 inches)

Width

368 mm (14.5 inches)

Depth

154 mm (6 inches)

Clearance around the enclosure

Top

305 mm (12 inches)

Bottom

305 mm (12 inches)

Left side

254 mm (10 inches)

Right side

178 mm (7 inches)

Weight

6 192 grams (13.65 lbs)

Inputs

Specifications

SSR current sensor input

Frequencies range: 40–70 Hz

Accuracy of ±0.6A for AC load <20A in a normal environment

6

891–00548

EDGE Power Module Wiring Diagrams

Summary of Contents for EDGE 074-11770

Page 1: ...EDGE Power Module 4 Outputs EDGE Power Module 2 Outputs Models 074 11770 074 11771 Wiring Diagrams 891 00548 Version 3 0 Date 07 15 18...

Page 2: ...ns photos and specifications in this manual are based on the latest information available at the time of publication The right is reserved to make changes at any time without notice 2 891 00548 EDGE P...

Page 3: ...igure 1 3 Wiring Diagram With a SPST Disconnect Switch page 4 Figure 1 4 Wiring Diagram With a DPST Disconnect Switch page 5 Figure 1 1 Grounding 1 2 3 4 064 11343 064 11343 064 11343 064 11343 Proper...

Page 4: ...ferrite bead in the EDGE Power module enclosure To variable module L1 L2 N L2 N From electrical distribution panel 100 240VAC Output L2 N wire return must not share the same wire as the load Figure 1...

Page 5: ...50 60 Hz 240 VAC 2000 W 8 33 A 50 60 Hz Motor inductive loads 10 5 A MAX Full Load amperage on the motor nameplate is not the maximum amp When varying the amperage might be higher Nb of Units Max curr...

Page 6: ...or IEC 60707 FV 0 IK rating degree of mechanical protec tion impact IEC 62262 08 Main supply voltage fluctuations shall not exceed 10 of the nominal supply voltage EDGE Power Module Functional ratings...

Page 7: ...wable loss of performance in a noisy environment Accuracy of 0 8A from initial reading with a load of 1 precision used for testing purpose 0 10Vdc outputs 0 10Vdc accuracy 1 means 0 1V 891 00548 EDGE...