11

GG-2

Contrast

Adjust contrast to allow for best 

viewing of LCD.

Relay Test

The relay test menu allows the relay 

outputs to be tested individually 

for correct output functions. Select 

the relay to be tested with the 

alphanumeric keys.

Press YES to Set relay. NO to exit.

Relay has been set. Press NO to clear 

the relay and exit once the relay 

output function has been verified.

ESC back to Config main menu. Press 

YES to save changes. Press ESC again 

to exit without saving changes.

Latch for Warn Relay: Allows warning 

relay of channel being programmed to 

latch. A latched relay must be cleared 

by pressing the RESET button, once 

the gas has cleared.
Horn: Allows horn relay and buzzer to 

activate during a Warn condition.

Alarm Setpoint: Use this field to 

change the default alarm setpoint.

Direction: Use this field to change the 

default direction setting. For example, 

oxygen level monitoring may require 

downscale alarming.
Latch for Alarm Relay: Allows alarm 

relay of channel being programmed 

to latch once activated. A latched 

relay must be cleared by pressing 

the RESET button, once the gas has 

cleared.

Location Name: Use this field to 

name the location of the sensor being 

programmed. To delete the existing 

label, ENTER and then PREV to delete 

characters.

ESC to return to Config menu.

Clock

Set current time and date.

Summary of Contents for GG-2

Page 1: ...Installation and Operation Manual GG 2 2 CHANNEL GAS DETECTION CONTROL PANEL...

Page 2: ...y in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should b...

Page 3: ...ng com General description 4 Installation 4 Locating the GG2 4 Installation guidelines 4 Wiring 5 Operation 7 Start up 8 Keypad 8 LCD Operator Interface 8 Menu Tree 9 Navigating the Menu 9 Normal oper...

Page 4: ...r They are electrically connected to the controller via three conductor cables The onboard relays have 10 second on off time delays to prevent unnecessary cycling during a fault warning or alarm condi...

Page 5: ...sure cover to prevent debris from falling into the equipment To maintain NEMA 4X IP 66 rating of the enclosure conduit fittings of the same rating or better must be used AC Power Wiring Power should b...

Page 6: ...0 3 shielded cable Belden 8772 or equivalent Length of cable should not exceed 1 500 feet Analog Output Wiring The analog output is 4 20 mA signal for monitoring by plant PLC or other analog input equ...

Page 7: ...xposed to the gas is connected to the proper input and responds causing appropriate alarm functions Keypad All operator functions are performed from the membrane switches on the front of the panel Sil...

Page 8: ...8 GG 2 Chl CAL Mode Alarm Warn ENGINE ROOM Chl CAL Mode Alarm Warn ENGINE ROOM Chl CAL Mode Alarm Warn ENGINE ROOM Chl CAL Mode Ch2 ENGINE ROOM 249 249 249 PPM NH3 PPM NH3 PPM NH3 Menu Tree...

Page 9: ...Main Menu The main menu can be accessed by pressing the menu key at any time Use the alpha numeric keys to select a sub menu or NEXT to advance to the next menu screen ESC to return to the normal oper...

Page 10: ...hanumeric keys Enter number 1 or 2 to configure that channel repeat same steps for both channels State Allows for turning on or off a channel For example if a sensor is removed from the system that ch...

Page 11: ...tch A latched relay must be cleared by pressing the RESET button once the gas has cleared Horn Allows horn relay and buzzer to activate during a Warn condition Alarm Setpoint Use this field to change...

Page 12: ...ttery is indicated replace old battery with a Type CR2450 Li Coin Cell Input Power Requirements 100 240 VAC 1 3 A 50 60 Hz Output 24 VDC power available for sensors and audio visual devices 1 2A 40 C...

Page 13: ...t by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a proper storage inst...

Page 14: ...14 GG 2...

Page 15: ...15 GG 2...

Page 16: ...ctiengineering com 866 394 5861 GG2 DOC1 1 20211103...

Reviews: