Chapter 4. Operation
4-14
Version 1.0b Mar 2003
The Alarm Buffer can be cleared by pressing the "c" key. Note that each entry in the buffer is "time
stamped" with the actual time of occurrence. So it is important to properly set the Date & Time as
described previously.
Another important diagnostic display is the Performance Monitor display. This display is also
accessible from the root menu, as item "4". The display looks similar to the following.
LOCAL
<<< Performance Display >>>
P1A P1B P1C P1D P2A P2B P2C P2D
Line CV: 0 0 0 0 0 0 0 0
Line ES: 0 0 0 0 0 0 0 0
Path CV: 0 0 0 0 0 0 0 0
Path ES: 0 0 0 0 0 0 0 0
Path SES: 0 0 0 0 0 0 0 0
Path UAS: 0 0 0 0 0 0 0 0
P3A P3B P3C P3D P4A P4B P4C P4D Opt
Line CV: 0 0 0 0 0 0 0 0 0
Line ES: 0 0 0 0 0 0 0 0 0
Path CV: 0 0 0 0 0 0 0 0 0
Path ES: 0 0 0 0 0 0 0 0 0
Path SES: 0 0 0 0 0 0 0 0 0
Path UAS: 0 0 0 0 0 0 0 0 0
All 16 channels are shown, 4 for each of 4 ports, plus the optical performance.
The very last item on the root menu is the Alarm Cut Off function. To turn off an activated audible
or visual alarm, the ACU pushbutton on the front of the unit may be pushed or in terminal mode,
the alarm may be cut off for the local or remote unit. Press item "5" from the root menu. The
"Audible Alarm Cut-off" LED will light on the front panel to indicate ACO.
This completes the overview of the LCD and Console mode configuration and status monitoring of
the MULTIPLEXER UNIT.
Summary of Contents for FMUX-01
Page 1: ......
Page 2: ......
Page 16: ...Chapter 1 Introduction 1 10 Multiplexer Unit Apr 2003 This page left blank intentionally...
Page 55: ...notes A 7...
Page 56: ...notes A 8...
Page 58: ......
Page 59: ......