76
DO-5 S p e c ific a tio n s
Outputs per Module
16
Commons
1
Rated Voltage
12 VDC
Operating Voltage
5 to 32 VDC
Output Type
N-FET, Open Drain
Isolation
None
Maximum Load
100 mA per channel
Output Power
12 VDC @ 1.6
A, non-isolated, supplied by module
On Response Time
15
ms maximum
Off Response Time
15
ms maximum
Operating Temperature
-20 to 70 °C
Storage Temperature
-40 to +85 °C
Operating Humidity
5 to 98% RH non-condensing
Hot Swap
Yes. Module can be swapped while RTU is running. Hot swap
will not cause a Warm Start. Outputs will be restored within 2
seconds once module is replaced.
DO-5 Wirin g Dia g ra m
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CH 1
CH 3
CH 6
CH 8
0 V
CH 2
CH 4
CH 5
CH 7
CH 9
CH 11
CH 14
CH 16
CH 10
CH 12
CH 13
CH 15
0 V
+12 V Ou tput
+12 V Ou tput
External DC
Power Supply
CH x
0 V
+
Wiring Examples
LOAD
POWER
SUPPLY
+12 V Ou tput
LOAD
CH x
+
Load powered by
DO-5 module
+
When output is energised, output channel is
shorted to the 0 V terminal.
INTERNAL
CIRCUITRY