All installations and services must be performed by qualified service personnel.

 

B. DRAFT REGULATORS: 

 
A draft regulator is supplied with the furnace and  should be installed according to the regulator manufacturers 
recommendations. With the burner operating, use a draft gauge to adjust the regulator to the proper setting. (refer to 
the instructions enclosed with draft regulator to adjust to the proper setting). When the burner air supply and draft 
are properly adjusted, the overfire draft should be a negative (-).01" to (-).02" WC

  1

, as measured at the 5/16" 

overfire air tap (See Fig. 4). This tap is provided in the upper burner mounting plate. To measure the flue draft, 
punch a small hole in the vent connector pipe as close to the furnace as possible and always before the draft 
regulator. 
 

 

 

 

 

 

 

 

 

Note: 

1. Draft overfire may be positive for high fire applications but not to exceed (+).02" WC. 

 
 
C.  DUCT WORK/AIR CONDITIONING: 

 
If the furnace is used in connection with summer air conditioning (cooling), the furnace should be installed parallel 
with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger. If the 
cooling unit is installed with a parallel flow arrangement, dampers or other means used to control flow of air should 
be provided to prevent chilled air from entering the furnace. If such a damper is manually operated, it must be 
equipped with a means to prevent operation of either unit, unless the damper is in the full heat or cool position. 
 
The duct system should again follow the current design standard of Air Conditioning Contractors of America                 
(ACCA) or ASHRAE Fundamentals volume.The most common location for the A-shaped coil (A style) is shown in 
Fig. 1. 

 

Fig 1: Acceptable locations for the air conditioner evaporator coil. 

 

NOTICE: 

The minimum coil  pan clearance for a drum type heat exchanger is three inches unless specified 

otherwise by the individual coil manufacturer.

 

 

 

 
D.  FILTERS MOUNTED EXTERNAL TO FURNACE 

 
On 

highboy

 furnaces, it is necessary to cut the return air opening in the side or rear casing, depending upon the 

needs of the specific installation. 
The filter rack provided with the furnace, refer to Fig. 2, will serve as a template to scribe a mark for the return air 
opening on the casing. Place the filter rack on a side casing approximately one inch up from the bottom of the 
furnace and centered from side to side. Place the securing flange against the casing when locating the return air 
opening. For your convenience, (4) locator knock-outs have been placed at the proper locations on both the left and 
right side casings. 

Summary of Contents for CSHB60-90XE

Page 1: ...alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional information consult a qualified installer or...

Page 2: ...ry substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWAR...

Page 3: ...R CONDITIONING 4 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANING INSTRUCTIONS 8 III...

Page 4: ...rotected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MATERIAL COMBU...

Page 5: ...oil furnaces If a power venter must be used it is the responsibility of the installer and power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the CSHB6...

Page 6: ...n air inlet pipe diameter is also 4 inch diameter For Riello the combustion air inlet pipe will be reduced to 3 inch diameter with the included Riello side wall vent kit For Beckett the combustion air...

Page 7: ...t dampers or other means used to control flow of air should be provided to prevent chilled air from entering the furnace If such a damper is manually operated it must be equipped with a means to preve...

Page 8: ...k can be anchored to the furnace with screws or pop rivets through the securing flange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions fo...

Page 9: ...he chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and components in burner mounting pla...

Page 10: ...RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information contact Crown Boiler Co P O...

Page 11: ...th access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum cleaner...

Page 12: ...oloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage aro...

Page 13: ...em and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The filter...

Page 14: ...All installations and services must be performed by qualified service personnel APPENDIX A Replacement Parts List 11...

Page 15: ...All installations and services must be performed by qualified service personnel APPENDIX B Wiring Diagrams BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier 12...

Page 16: ...All installations and services must be performed by qualified service personnel All installations and services must be performed by qualified service personnel 13 13...

Reviews: