background image

All installations and services must be performed by qualified service personnel.

 

F.  BURNER INSTALLATION: 
 
NOTICE:

  Remove all cardboard packing from around chamber before installing burner. 

The oil burner will mount on three stud mounting bolts on the lower mounting plate covering the opening in the 
front of the heat exchanger. The end of the burner tube should be inserted no further than 1/4 inch back from the 
inside surface of the combustion chamber. A distance further than 1/4 inch back from the inside chamber wall may 
cause impingement and sooting. This unit is equipped with a chamber retainer (refer to Fig.4). This retainer secures 
the chamber during shipping and helps to maintain insertion depth. 

DO NOT

 remove this retainer when installing 

burner. 

 

Fig. 4: Typical location of the overfire air tap and components in burner mounting plate area 

 

 

Fig. 5: Burner insertion illustration (Top view) 

 

 

When mounting the burner, the mounting plate (Fig. 4) must be removed to provide access to the area in front of the 
combustion chamber. A fiber insulating sleeve or amulet is provided on the burner tube of specific burners.(see Fig. 
5). See burner application chart for type of insulator.  Do not allow the burner tube or end cone to physically touch 
or protrude into the chamber, as excess heat transfer could result in destruction of the tube, end cone or both. The 
burner tube/end cone is properly positioned, when the end is ¼ inch back from the inside surface of the combustion 
chamber wall. 

 

 
 
 

Summary of Contents for CSHB60-90XE

Page 1: ...alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional information consult a qualified installer or...

Page 2: ...ry substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWAR...

Page 3: ...R CONDITIONING 4 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANING INSTRUCTIONS 8 III...

Page 4: ...rotected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MATERIAL COMBU...

Page 5: ...oil furnaces If a power venter must be used it is the responsibility of the installer and power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the CSHB6...

Page 6: ...n air inlet pipe diameter is also 4 inch diameter For Riello the combustion air inlet pipe will be reduced to 3 inch diameter with the included Riello side wall vent kit For Beckett the combustion air...

Page 7: ...t dampers or other means used to control flow of air should be provided to prevent chilled air from entering the furnace If such a damper is manually operated it must be equipped with a means to preve...

Page 8: ...k can be anchored to the furnace with screws or pop rivets through the securing flange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions fo...

Page 9: ...he chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and components in burner mounting pla...

Page 10: ...RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information contact Crown Boiler Co P O...

Page 11: ...th access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum cleaner...

Page 12: ...oloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage aro...

Page 13: ...em and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The filter...

Page 14: ...All installations and services must be performed by qualified service personnel APPENDIX A Replacement Parts List 11...

Page 15: ...All installations and services must be performed by qualified service personnel APPENDIX B Wiring Diagrams BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier 12...

Page 16: ...All installations and services must be performed by qualified service personnel All installations and services must be performed by qualified service personnel 13 13...

Reviews: