Crown Royal Stoves RS7300E Owner'S Manual Download Page 41

41

AUTHORIZED FURNACE TREATMENT

P: 866-361-7355 

F: 218-283-5786 

W: www.crownroyalstoves.com

Greentech Manufacturing, Inc.    2716 Crescent Dr    International Falls   MN   56649

Greentech Manufacturing Inc. requires the usage of authorized furnace treatment to be used in all Crown Royal Stoves. Treatment is 
to be added to furnace water upon initial start up and is required to remain at satisfactory levels thought the life of the stove.

To ensure the maximum efficiency and longevity of your Crown Royal Stove, water treatment is crucial. Treating systems with 
authorized furnace treatment will prevent corrosion and scale buildup. Calcium and magnesium are commonly found in many water 
supplies. These impurities cause layers of scale that not only decrease heat transfer efficiency but cause pitting on the interior water 
jacket. Over time constant pitting will result in leaks. Once authorized treatment is added it creates the necessary barrier needed to 
prevent the breakdown of metals. Premature corrosion is a result of not treating the water with correct corrosion resistant inhibitor 
or with the wrong dosage.

Water Treatment and Testing Required on all Crown Royal Stoves

All Crown Royal Stoves are required to be shipped with initial recommended gallon(s) of 
authorized treatment. Crown Royal Stoves are backed with a 20 Year Limited Warranty. To retain 
warranty on Crown Royal Stoves it is required to use recommended treatment and submit 
annual samples for testing. Failure to maintain treatment at recommended levels and annual 
water testing will result in a voided warranty.

 

•   Specifically designed for Crown Royal Stoves, closed-loop design.

 

•   Helps protect system from scale, sludge and corrosion.

 

•   Vapors help prevent corrosion throughout the furnace.

 

•   Economical – one gallon/3.78 liters treats 300 gallons/1134 liters of system capacity.

 

•   FREE Water Testing and sample bottles.

Sample Bottles 

Two sample bottles and labels are found with each gallon of treatment.  For additional bottles or labels please contact your local 
dealer or call 866-361-7355.

Warning  

Read entire label located on treatment before opening or using this product.  Keep out of the reach from children.  Do not mix with 
any other chemicals.  Contains Sodium Nitrate and Potassium Hydroxide. Avoid contact with skin, eyes and clothing.  Undiluted 
product causes severe skin and eye irritations.  Wash thoroughly after handling. Do not swallow. Swallowing may cause nausea, 
vomiting, weakness and lowered blood pressure. MADE IN U.S.A.

Storage 

Keep container closed when not in use.  When product is stored it may separate or thicken.  This will not harm the performance.  
Before using, warm to room temperature and stir thoroughly. Keep from freezing.

Summary of Contents for RS7300E

Page 1: ...ETAIN THIS MANUAL CONSERVEZ CE MANUEL UL 391 UL 726 CSA B366 1 OWNER S MANUAL EPA QUALIFIED RS7300E RS7400E Mailing PO Box 1237 Shipping 2716 Crescent Dr International Falls MN 56649 Ph 866 361 7355 F...

Page 2: ...2...

Page 3: ...ol Panel 24 Start Up Operation Filling Water Jacket 25 Firing the Furnace 25 Starting a Wood Fire 25 Daily Fueling Firing 26 Safety 26 Power Failure 26 Maintenance Maintenance Cleaning 27 Daily Weekly...

Page 4: ...4...

Page 5: ...furnaces are often used to heat residential homes garages shops barns businesses greenhouses swimming pools spas domestic hot water radiant in floor heat and snow melt applications RS7300E RS7400E Est...

Page 6: ...6...

Page 7: ...e lighter fluids chemicals or oils 5 Furnace Sizing The size of a furnace should be large enough to provide sufficient heat with out constant reloading Targeted burn times are around 12 hours an adequ...

Page 8: ...8...

Page 9: ...v burnwise How to Use a Moisture Meter Video http www youtube com watch v jM2WGgRcnm0 EPA offers tips on how to properly use a moisture meter to test firewood before using in a wood burning stove or f...

Page 10: ...10...

Page 11: ...as softwood or hardwood The pines spruces and firs are common softwoods and the oaks elms birches and maples are the common hardwoods Softwoods burn rapidly and are more resinous than the hardwoods th...

Page 12: ...ure Load fuel carefully to avoid injury to hands fingers and other body parts that may come in contact with the unit s loading door opening Cleaning of the heat exchanger flue pipe chimney and draft i...

Page 13: ...ovider to ensure that installation is in compliance to regulations and all terms have been met Blocks or Concrete Pad Inspect the ground conditions that you intend to install your furnace on If the ar...

Page 14: ...royalstoves com Greentech Manufacturing Inc 2716 Crescent Dr International Falls MN 56649 RS7300E 51 RS7400E 52 5 RS7300E 72 RS7400E 80 5 6 6 RS7300E 12 RS7400E 14 25 RS7300E 12 RS7400E 14 25 4 4 FRON...

Page 15: ...mney piping it is recommenced by many chimney suppliers to brace every eight feet Also recommended by the chimney manufacture that the height of the pipping does not exceed a total of forty 40 ft When...

Page 16: ...ttom of trench and cover with 6 of gravel or dirt At this point a water barrier is required Several methods are possible but the most important factor is if ground water comes in contact with your hea...

Page 17: ...re is an air conditioning evaporator coil in the plenum install the water to air coil after the a c coil If the central heating system is a hot water boiler system a water to water heat exchanger is n...

Page 18: ...event damage from loss of circulation due to electrical power failure The Crown Royal Stove shall be installed without changing the function of the controls or rewiring the original boiler A wiring in...

Page 19: ...rom outdoor wood furnace Run thermostat wire from the strap on Aquastat to R and G of fan control center Run 115V power to white and black wire of fan center coil Break one wire of gas boiler Aquastat...

Page 20: ...arge or too small it must be altered to fit the heat exchanger properly After installation of the add on water to air exchanger the air flow must be increased to fuel the furnaces electric furnaces an...

Page 21: ...re in the hot water heater If installed on the hot side the hot water heater needs to be turned off and the hot water heater is now a reservoir BRAZED PLATE INSTALLATION Wood Stove Inlet water line fr...

Page 22: ...22 Water to Air Exchanger Ball Valve Fitting Water to Air Exchanger Boiler Drain WATER TO AIR SETUP INSTALLATION...

Page 23: ...es com Greentech Manufacturing Inc 2716 Crescent Dr International Falls MN 56649 Electronic Temperature Controls Blower Capacitor 3 Way Switch Limit Switch Thermo Well Solenoid Damper Door Rope High T...

Page 24: ...using the controls The aqua stat powers the inducer draft blower to maintain the desired water temperature The aqua stat is set at 160 F at the factory which means the inducer will run until the water...

Page 25: ...is reached 180F On this initial start up the water jacket will reach what is called the dew point This creates sweat inside the fire box which may last a couple of days and is normal Condensation wil...

Page 26: ...should never be filled with excess wood so that the flue gas exit is blocked or impeded in any way Burning wood generates carbon monoxide and if the flue gas exit is blocked the carbon monoxide can b...

Page 27: ...firebox Before refueling firebox perform weekly maintenance Use extreme caution when opening and cleaning doors these areas will still be hot CLEAN VERTICAL AND HORIZONAL HEAT EXCHANGERS Simply slide...

Page 28: ...nd add water if low until excess flows from the overflow pipe located in front of the chimney Annually Maintenance Lubricate fan and solenoid shaft Check fan and solenoid to ensure proper air velocity...

Page 29: ...nd ash removal periods the ash pan and loading doors should never be left open This unit should never be left unattended with any of the doors left open CREOSOTE FORMATION REMOVAL When wood is burned...

Page 30: ...led 3 Check that the solenoid damper plate is opening and closing without hang ups 4 Check that the flexible air duct is connected to the blower and the bottom elbow of the furnace 5 Check that the te...

Page 31: ...31...

Page 32: ...32...

Page 33: ...Load Line Neut D C B A A B C D 1 2 3 4 5 6 7 8 8 7 6 5 4 3 2 1 DO NOT SCALE DRAWING 1 UNLESS OTHERWISE SPECIFIED REV DWG NO B SIZE TITLE Q A MFG APPR ENG APPR CHECKED DRAWN DIMENSIONS ARE IN INCHES T...

Page 34: ...34...

Page 35: ...ed in sheltered area insufficient wind to disperse smoke C Furnace sizing Similar to other heating appliances furnace should be properly sized based on the estimated heat loss of the served structure...

Page 36: ...tops properly b Combustion blower wheel spins properly c Blower runs at proper speed verify voltage to blower motor 2 Combustion blower tube not restricted by debris creosote ash etc 3 Flame baffle fl...

Page 37: ...of the wood either too high or too low will affect the amount of visible smoke Wood with a low moisture content less than 10 will burn relatively quicker resulting in some of the fuel going up the ch...

Page 38: ...ER it is loaded B Furnace Size The size of a furnace should be large enough to provide sufficient heat without constant reloading If the target burn time is 12 hours an adequately sized furnace will p...

Page 39: ...tched to the heat load so that cold starts and overfilling are avoided Chimney height should be in accordance with the state and local codes as well as surroundings including neighbors These areas alo...

Page 40: ...40...

Page 41: ...allon s of authorized treatment Crown Royal Stoves are backed with a 20 Year Limited Warranty To retain warranty on Crown Royal Stoves it is required to use recommended treatment and submit annual sam...

Page 42: ...e Information Form Testing facility analyzes the conductivity PH and nitrate levels of water sample Testing results are provided on all samples within 4 6 weeks If testing results are unsatisfactory r...

Page 43: ...aintain treatment recommendation levels and submit annual water samples will result in a voided warranty Annually add of the required amount of treatment yearly this will keep levels balanced Follow d...

Page 44: ...clothing and shoes GET IMMEDIATE MEDICAL ATTENTION INGESTION Give 3 to 4 glasses of water but do not induce vomiting If vomiting occurs give fluids again GET IMMEDIATE MEDICAL ATTENTION DO NOT GIVE AN...

Page 45: ...eration of the furnace or damage incurred due to any heating system failure These furnaces are not intended to be the only source of heat therefore it is recom mended that a back up system is in place...

Page 46: ...46...

Page 47: ...nt in by customer we make sure the stove is registered in original owners name verify mandatory chemical was added to the system and yearly test results were sent in and came back satisfactory when ap...

Page 48: ...48 Warranty Claim Form Have you turned in a warranty claim before YES or NO If yes is the leak in the same place Yes or No Additional Notes or Comments Repair Required...

Page 49: ...m refrigeration to heating due to the wide temperature range of the control stated above Typical applications include walk in freezers beverage coolers supermarket display cases for flowers produce me...

Page 50: ...ICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED ON SEE NOTE TEMPERATURE UP BUTTON TEMPERATURE DOWN BUTTON MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 5 SW1 Refrigeration Cool Heating Heat S...

Page 51: ...omer alarm equipment Binary Input Gold Plated Contacts 24 VAC Block not used TH Thermostat Hot TR Thermostat Return NTC Temperature Sensor PTC Temperature Sensor Fig 3 Line Voltage Application Power S...

Page 52: ...ure will operate the load terminal CI indicates the setpoint temperature will be the Cut In temperature CO indicates the temperature will be the Cut Out temperature See Operation section SOF Sensor Op...

Page 53: ...ential 5 Setpoint temperature 40 Temperature Range 40 Setpoint Cut Out 45 SW1 Cool Set Point SP Cut Out Differential 5 Setpoint temperature 40 Temperature Range HEAT To use as a Heating control SW1 mu...

Page 54: ...ents to prevent a false alarm If the control set back feature is used to change the setpoint the delay period set in AL should consider the time it takes for the system to reach the set back temperatu...

Page 55: ...9 65 2 09 158 70 1 76 167 75 1 48 176 80 1 26 185 85 1 07 194 90 0 92 203 95 0 79 212 100 0 68 221 105 0 59 Temperature F C Resistance K 40 40 613 31 35 640 22 30 668 13 25 697 4 20 727 5 15 758 14 10...

Page 56: ...te rodgers com www emerson com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co TROUBLESHOOTING Temperature differential is wi...

Page 57: ...57...

Page 58: ...OWNER S MANUAL...

Reviews: