ADDRESS
DESCRIPTION
DEFAULT
NEW
P37E
1-8E
PROGRAMMING OUTPUT OPTIONS D
1 = Siren Driver to Output (requires a horn speaker, outputs 1&2)
2 = Output Reset/Chime Timers are in Minutes
3 = Output muted for 10 seconds on key-press if alarm
4 = Turn Output OFF during Two Way Voice Mode
5 = Not used
6 = Not used
7 = Not used
8 = Monitored Output (1&2 only) can tell if siren cable is cut
O/P 1-8 =
NONE
P38E
1-8E
OUTPUT ON DELAY TIME
Enter a value 0-9999 Seconds
O/P 1-8 = 0
secs
P39E
1-8E
OUTPUT PULSE TIME
Enter a value 0-255 for 1/10th Sec increments
Output 1 = 3, Output 2 = 7, Output 3 = 3, Output 4 = 10, Output 5-8 = 0
P40E
1-8E
OUTPUT RESET TIME
Enter a value 0-9999 Seconds (Default = 300
Sec) (if option 2 at P37E is on the reset time is in minutes)
Output 1 = 300, Output 2 = 0 (Latching), Output 3 = 300, Output 4 = 5,
Default 5-8 = 0
P41E
1-8E
OUTPUT CHIME MODE TIME
Enter a value 0-255 for 1/10th Sec
increments (Eg: 20 = 2Sec, 50 = 5Sec, 255 = 25.5Sec)
P42E
1-8E
START OF OUTPUT COMMAND CONTROL STATUS MESSAGES
Enter a value 0-99 (Eg: If a Voice Board is fitted to the panel, Enter the
Message Number as programmed in the Voice Boards)
O/P 1-8 = 0
P43E
1-8E
UN-MAP AN OUTPUT
Remove ALL defaults from the Output
P44E
1-8E
ASSIGNING A TIME-ZONE TO AN OUTPUT
Time-zones that control
output 1-8. Outputs 1-8 Enter a time-zone 1-8
NONE
AREAS
ADDRESS
DESCRIPTION
DEFAULT
NEW
P45E
1-2E
AREAS A & B OPTIONS A. 1
= Area A and
2
= Area B.
1 = Arm button required before code to
Arm (set)
2 = Stay button required before code to
Arm (set)
stay mode
3 = Code required to
Arm (set)
4 = Code required to bypass zones
5 = Not used
6 = Send Arm
(Closing)
at the end of the Exit Delay
7 = Can Arm only if All Zones are Sealed (Ready)
8 = Can Arm Stay Mode only if All Zones are Sealed (Ready)
NONE
P46E
1-2E
AREAS A & B OPTIONS B. 1
= Area A and
2
= Area B.
1 = Use near and verified alarm reporting for all zones in this area
2 = Area will Arm at End of Time-Zone
3 = Area will Disarm at Beginning of Time-Zone
4 = Assign beeps to access tags
5 = Not used
6 = Not used
7 = Cannot Arm if Zone Unsealed at end of Exit Delay
8 = Not used
NONE
P47E
1-2E
AREAS A & B ARM INDICATION TO OUTPUT
1
= Area A and
2
= Area B
Area A & B Arm Indication to Output. Enter a value of 1-8 for each of
the 2 Area’s as required.
NONE