2.6   Switch Mode Setup - The following gives the switch mode settings of the on board controls that can be 
changed in the field: SWITCH A JP1, JP2, JP3, JP4; S3; SWITCH B - JP101, JP102, JP103, JP104, S103 
(Section 2.3, Figure 2.3). All shown with external alarm = ground.

1) CH1 Prime Mode - Switches from CH1 to the CH2 only if CH1 alarms and CH2 is good. Switches 

back to CH1 when it is no longer in alarm or when both CH1 and CH2 are in alarm

Non-dot - SWITCH A - JP1, JP3, JP4; SWITCH B - JP101, JP103, JP104
Dot - SWITCH A - JP2; SWITCH B - JP102
S3 (SWITCH A), S103 (SWITCH B) - ALL TO OFF.

2) Latch to CH2 Mode - Switches from CH1 to the CH2 if CH1 alarms and CH2 is good. 

Latches to CH2. Push Reset or ground Remote Reset pin to return to CH1 if it has no alarm or both 
CH1 and CH2 are in alarm.

Non-dot - SWITCH A - JP1, JP4; SWITCH B - JP101, JP104
Dot - SWITCH A - JP2, JP3; SWITCH B - JP102, JP103
S3 (SWITCH A), S103 (SWITCH B) - ALL TO OFF.

3)  Minimum  Auto  switching,  Initial  Channel  Select  (ICS)  Mode  - Switch stays on channel last 

selected by Manual or Remote selection after return to Auto if both channel alarms are clear or both 
channels are in alarm. Auto switching occurs only if current channel alarms and the other channel 
is clear.

Non-dot - SWITCH A - JP4, SWITCH B - JP104
Dot - SWITCH A - JP1, JP2, JP3; SWITCH B - JP101, JP102, JP103
S3 (SWITCH A), S103 (SWITCH B) - ALL TO ON.

Factory set mode is generally 1)  CH1 Prime Mode 

2.7  Operation

a.   Set the on board controls as desired (Section 2.4, 2.6, Figure 2.3).
b.   Install the 1582-725 in the equipment rack.
c.   Connect RF to the BNC connectors (J4, J5, J6 (SWA1); J1, J2, J3 (SWA2);

(J8, J9, J10 (SWB2); (J11, J12, J13 (SWB1).

d.   Connect to signals on the MONITORS AND CONTROLS connector, J8, 

as desired (see Figure 2.0, Table 2.0).

e.   Connect power via two power cords.
f.   Manually switch between channels 1 and 2 and be sure switching occurs.
g.   Switch to Auto. Alarm channel 1 and note that automatic switching occurs. 

Remove alarm to channel 1 and note that the output switches as desired. 
Push RESET if in LATCH mode. Repeat for Channel 2.

h.   Check that CH 1 and CH 2 are selected when in Auto and momentary ground is applied to 

J8 pins 1 and 2. Momentarily ground remote Reset pin 4 on J8 to return to Auto operation. 

1582-725 Manual, Rev. B

 

 

  Page 10

    

          4/10/14

Summary of Contents for 1582-725

Page 1: ...proprietary to Cross Technologies Inc but may be reproduced or duplicated without the prior permission of Cross Technologies Inc for purposes of operating the equipment Printed in USA When ordering parts from Cross Technologies Inc be sure to include the equipment model number equipment serial number and a description of the part CROSS TECHNOLOGIES INC 6170 Shiloh Road Alpharetta Georgia 30005 770...

Page 2: ...nship for a period of one year after shipment to customer Cross Technologies Inc s obligation under this warranty is limited to repairing or at Cross Technologies Inc s option replacing parts subassemblies or entire assemblies Cross Technologies Inc shall not be liable for any special indirect or consequential damages This warranty does not cover parts or equipment which have been subject to misus...

Page 3: ...lear Factory set mode is generally 1 CH1 Prime Mode When power is first applied and there are no alarms CH1 is selected On power loss CH2 is the selected channel The Manual Select switch and contact closures to Remote Select pins when in Auto select CH1 or CH2 independent of alarms LEDs indicate alarm and switch conditions for CH1 and CH2 REMOTE or MANUAL operation and power on RF connectors are B...

Page 4: ...ls are in alarm SWITCH RESET Resets switch to CH1 if it is good and switch is in the latch mode Also Resets REMOTE by returning operation to Auto Indicators LEDs CH1 ON LINE Turns green when Channel 1 is selected CH2 ON LINE Turns green when Channel 2 is selected MANUAL Turns red when the Manual Select switch manually selects channel 1 or 2 ALARM CH1 Turns red when an external alarm input closure ...

Page 5: ...s J7A J7B Monitors and Controls Connectors J7A TOP J7B BOTTOM Function Pin Description ALARM 1 IN 13 Ground or Open selectable by JP2 JP102 gives CH1 alarm ALARM 2 IN 14 Ground or Open selectable by JP2 JP102 gives CH2 alarm REMOTE 1 IN 1 When in AUTO momentary ground on this pin selects CH1 REMOTE 2 IN 2 When in AUTO momentary ground on this pin selects CH2 REMOTE RESET IN 4 When in LATCH mode gr...

Page 6: ...sition switch as follows LEFT manually select Channel 1 CENTER AUTO switch position determined by alarm and remote closures RIGHT manually select Channel 2 Switch RESET Resets switch to Channel 1 if it is good and switch is in the latch mode Also resets REMOTE selection to normal AUTO operation Common for the Chassis Common for the Chassis Item Description POWER 1 LED Turns green when power is app...

Page 7: ...de on off 3 pin jumper effective when JP1 is in the non dot position With JP3 in the dot and JP1 in the non dot when channel 1 alarms the 1582 14 switch switches to channel 2 and stays there until the reset button is pushed on the front panel or by an external closure to ground on the remote RESET pin on J8 and then it switches to channel 1 If channel 1 alarms are cleared If in the ICS mode and or...

Page 8: ...ote 1 or Remote 2 pins on J8 and then grounding the Remote reset pin on J8 causing the 1582 14 to go back to Auto in the channel last selected remotely if both channel alarms are clear or both channels are in alarm The initial channel can also be selected if both channel alarms are clear or both channels are in alarm S3 S103 positions 1 2 3 4 to OFF ICS is disabled Minimum Auto switching Return to...

Page 9: ...ALL SWITCH POSITIONS IN THE ON SIDE POWER SUPPLY 2 POWER SUPPLY 1 SHOWN IN THE ICS MODE S4 S5 JP2 JP3 JP15 JP16 JP17 JP18 JP1 JP104 JP102 JP103 JP101 S3 S103 JP10 S104 S105 JP109 JP110 FIGURE 2 3 1582 725 PCB Settings Parts Locations 1582 725 Manual Rev B Page 9 4 10 14 ...

Page 10: ...te selection after return to Auto if both channel alarms are clear or both channels are in alarm Auto switching occurs only if current channel alarms and the other channel is clear Non dot SWITCH A JP4 SWITCH B JP104 Dot SWITCH A JP1 JP2 JP3 SWITCH B JP101 JP102 JP103 S3 SWITCH A S103 SWITCH B ALL TO ON Factory set mode is generally 1 CH1 Prime Mode 2 7 Operation a Set the on board controls as des...

Page 11: ... equipment is not compromised Additional space between units may be required E Circuit Overloading Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of circuits could have on over current protection and supply wiring Appropriate consideration of equipment name plate rating should be used when addressing this concern F Reliable Ea...

Page 12: ...ES INC 6170 Shiloh Road Alpharetta Georgia 30005 770 886 8005 FAX 770 886 7964 Toll Free 888 900 5588 WEB www crosstechnologies com E MAIL info crosstechnologies com Printed in USA 1582 725 Manual Rev B Page 12 4 10 14 ...

Reviews: