LPT-M - Operation Manual
Press ENTER and use the ARROW keys to scroll through the menu and choose SP Low. Press ENTER
and use the ARROW key to choose ASCENDING or DESCENDING.
Press ENTER again to change the setpoint value by using the ARROW keys to increase or decrease
the number. Press ENTER to move to the next digit and again to save and Exit the screen.
NOTE:
An Ascending alarm is used when the normal gas level starts out below the alarm setting
and when the reading goes above it, the alarm will trip. A descending alarm is used when the
normal gas level starts above the alarm setting and when the reading goes below it, the alarm will
trip. The descending alarm is commonly used with Oxygen sensors.
6.11.2 MID Alarm Setpoint
Follow the same procedure as the
6.11.1 Setting the LOW Alarm Setpoint
, choosing the SP Mid menu
option.