Press ENTER to access the screen and use the ARROW keys to increase or decrease the number. Press
ENTER to move to the next digit and again to save and Exit the screen.
NOTE:
The ON Delay and OFF Delay are entered in seconds. The maximum length of time that either
can be set to is 9999 (2.7 hours). The default setting from the factory is 0000 seconds, indicating no
ON or OFF Delays are set.
6.9.3 Relay Mode of Operation (Normal or FAILSAFE)
The LPT-M is designed to be fail-safe so the relay is normally energized in a non-alarm state for
failsafe oper
ation. If required, the LPT-M can be confi gured for normal relay operation.
In the Hardware Confi guration Menu (passcode 1001), press either ARROW to scroll through the
menu and select Program Relay. Press ENTER to select. Scroll through the menu and choose Relay
Failsafe. Press ENTER to select Yes or No. Press the DOWN ARROW to save and Exit the screen.
6.9.4 Relay Alarm Level Assignment
One level of alarm can be set to trigger the relay. Choose from LOW, MID, HIGH or FAULT.