cGas Detector Analog Transmitter - Installation Manual
7.5 Alarm Status, Fault Detection and Communication Failure Alerts
If a channel is in alarm, the following letters will be displayed at the end of the
line for that channel.
• low
for low alarm
• mid
for mid alarm
• high
for High alarm
CO2
800 low
CO2
1000 mid
CO2
1200 high
The cGas Detector has built in fault detection, and in the event of a problem
with the measurement circuitry the transmitter will indicate a fault condition
on the display. Normal operation will resume once the fault condition has been
corrected.
NOTE:
If a question mark ? is displayed, the system is reading slightly negative
but not enough to adversely affect the alarm functionality; a re-zeroing is
recommended.
7.6 Change Units (
o
C or
o
F) of Temperature Readings
NOTE:
This menu item only applies if the cGas Detector has the -RHT option
installed.
You can change the factory configured temperature unit type from Celsius to
Fahrenheit (or vice versa) very easily.
From the main display, press ENTER.
Enter passcode 3032 using the UP button and ENTER button.
Enter Password
3032
Press ENTER to access the Calibrate Menu.
Calibrate Menu
Press Enter