36
© 2021 All rights reserved. Data subject to change without notice.
cGas Detector Analog Transmitter - Installation Manual
Rev. B | 2021.08
All sensors are calibrated in the factory prior to shipping and should not
require calibration at the time of a routine installation or replacement.
7.2 Navigating the Menu Structure
The three programming push-buttons inside the enclosure are used to navigate
through the cGas Detector menu structure. Refer to Section 5.1
Exterior
Enclosure
for location photo.
ENTER begins a process or moves you to the next screen in the same menu.
The UP or DOWN buttons are used to enter characters/numbers and to
navigate to the next menu item. For simplicity’s sake, directions in this manual
use the UP button.
A line under a character or number indicates that is the space into which you
are entering a character or number. Use the ENTER button to move to the next
space. Or use the UP or DOWN button to change the value in that space.
The > symbol indicates that you are in the edit mode as opposed to scrolling
through available menu items.
After entering and confirming a value you can either Exit the menu or press the
UP button to move to the next item in that menu. All menus are circular and will
bring you back to the Exit screen. Press ENTER to Exit.
7.3 Accessing the Menu with Passcodes
You must enter a passcode to access the menu. From the normal operation
screen, press ENTER to access the password entry screen. Use the UP or
DOWN arrow to scroll to the desired number. Press ENTER to move to the next
position. Continue until the full code is entered and press ENTER when finished.