33
13
Specific
Programming with RS485
13.8V/27.6V
14.4V/28.8V
2H
4H
14
Specific
Programming with CAN bus
13.8V/27.6V
14.4V/28.8V
2H
4H
15
Specific
Programming with UNI-DISPLAY-R
13.8V/27.6V
14.4V/28.8V
2H
4H
Some specific settings are possible – please consult us.
(*) Voltage on + BAT with 10% of the rated current and a tolerance of +/- 1%.
(
**
)
REFRESH is not advised for certain types of AGM batteries
(***) Battery Management System
3.3.3
Programming field 2 : Select special mode
Setting
REFRESH
mode
BOOST
mode
0
OFF
OFF
1
OFF
ON
2
ON
OFF
3
ON
ON
-
The BOOST function allows a faster charging of the batteries. This function is timed in time (see section 3.3.2.)
And is automatically inhibited if the battery is charged: shutdown of the BOOST for a battery current <20% of
the nominal current of the regulator (12% in the case of the Lithium curve Iron Phosphate with BMS).
-
The REFRESH function allows to apply a voltage step periodically to maintain the battery, to promote its
equalization and thus prevent possible sulfating.
3.3.4
Programming field 3 : Select Can address
Setting
REGULATOR_Frame1
Can address
Setting
REGULATOR_Frame1
Can address
0
0x0002 9000
8
0x0002 9008
1
0x0002 9001
9
0x0002 9009
2
0x0002 9002
10
0x0002 900A
3
0x0002 9003
11
0x0002 900B
4
0x0002 9004
12
0x0002 900C
5
0x0002 9005
13
0x0002 900D
6
0x0002 9006
14
0x0002 900E
7
0x0002 9007
15
0x0002 900F