11
3.3.2
Setting according to the batteries type
Switches setting
Description of the
battery type
Voltage* with
BOOST OFF
Voltage* with
BOOST ON
Maximum
duration of
BOOST at
+/- 5%
T
BOOST
Maximum
duration of
ABSOPTION at
+/- 5%
T
ABS
A
B
C
D
0
0
0
0
Opened type bat
free electrolyte (wet)
26.8V
28.2V
2H
4H
1
0
0
0
Classic sealed type
bat
(Sealed Lead)
27.6V
28.8V
2H
4H
FACTORY SETTING
0
1
0
0
GEL type bat
27.6V
28.8V
2H
4H
1
1
0
0
AGM type bat**
27.2V
28.8V
2H
4H
0
0
1
0
Spiral type bat
27.2V
28.8V
2H
4H
1
0
1
0
Tin calcium lead bat
28.8V
30.2V
2H
4H
0
1
1
0
Wintering or standby
sealed bat
26.8V
26.8V
0H
0H
1
1
1
0
Stabilized DC power
supply
24V
24V
0H
0H
0
0
0
1
SPE1 open type bat
26.4V
29.6V
2H
4H
1
0
0
1
Lithium Iron Phosphate
( LiFePO4 ) with BMS
(***)
27.6V
28.8V
6H
10H
0
1
0
1
STORMLINE Bat
27.4V
29V
2H
6H
0
1
1
1
Booked
1
1
1
1
Booked
(*) Voltage on + BAT with 10% of the rated current and a tolerance of +/- 1%.
(
**
)
REFRESH is not advised for certain types of AGM batteries
(***) Battery Management System
Some specific settings are possible – please consult us.
3.3.3
Temperature compensation
The STP-NEW-2.8 probe enables the compensation of Absorption voltage and
Floating Voltage depending on the ambient temperature of the battery room.
The coefficient used is -3mV/°C/element.